omni_wire_gauge_drop

Calculate voltage drop, percentage loss, and voltage at load for single-phase copper circuits, then check NEC 3% compliance and recommended AWG conductor sizing.

Instructions

Voltage Drop & Wire Gauge (AWG) Calculator. Calculate electrical voltage drop, percentage loss, and proper American Wire Gauge (AWG) conductor sizing for single-phase copper circuits. Discipline: CONSTRUCTION. Governing mathematical model / formula: Voltage Drop (VD) = [2 × K × I × Length (ft)] / Circular Mils (CM).

USAGE GUIDELINES:

  • WHEN TO USE: Invoke for deterministic calculation of voltage_drop_volts (Total Voltage Drop), percentage_drop (Percentage Voltage Drop), voltage_at_load (Voltage Delivered to Load), nec_compliance (NEC Rec. (<3% Branch Limit)) using circuit_voltage (Circuit Voltage in volts), load_amperes (Continuous Load Amperage in amps), one_way_distance (One-Way Conductor Length in ft), wire_gauge (Wire Gauge (12 for 12AWG, 10 for 10AWG) in AWG). Guarantees exact machine floating-point precision, eliminating LLM arithmetic mistakes and formula hallucinations.

  • WHEN NOT TO USE: Do not use for qualitative evaluations or unquantified reasoning. All input parameters must be valid numerical values.

DISAMBIGUATION & BOUNDARIES:

  • Use this dedicated specialist tool for 'Voltage Drop & Wire Gauge (AWG) Calculator' rather than generic dispatchers like omni_universal_query.

  • For multi-calculation chained jobs, use 'omni_batch_calculate'.

  • To inspect schema fields, see 'omni_describe_solver'.

BEHAVIOR & SAFETY:

  • Pure deterministic computation with machine floating-point precision.

  • Read-only, idempotent, and stateless. Zero side effects or persistent state mutations.

  • Input validation: All arguments are validated against physical and domain bounds. Out-of-bounds inputs return a safe diagnostic error status without throwing runtime exceptions.

RETURNS:

  • Structured JSON object containing:

    • status (string): "success" on valid execution or "error" if validation fails

    • calculator (string): "wire-gauge-drop"

    • category (string): "construction"

    • name (string): "Voltage Drop & Wire Gauge (AWG) Calculator"

    • formula (string): Governing mathematical formula string

    • inputs (object): Echoed input parameter dictionary with applied defaults

    • metrics (object): Dictionary of computed outputs:

      • metrics.voltage_drop_volts (Total Voltage Drop): Formatted display string (e.g. '6.35 Volts')

      • metrics.percentage_drop (Percentage Voltage Drop): Formatted display string (e.g. '5.29%')

      • metrics.voltage_at_load (Voltage Delivered to Load): Formatted display string (e.g. '113.65 Volts')

      • metrics.nec_compliance (NEC Rec. (<3% Branch Limit)): Formatted display string (e.g. 'Fails 3% limit (Upsize to 10 AWG)')

    • execution_time_ms (number): Latency in milliseconds.

Tool call template

This tool declares no required parameters. Add optional parameters from the input schema as needed.

{
  "id": 1,
  "jsonrpc": "2.0",
  "method": "tools/call",
  "params": {
    "arguments": {},
    "name": "omni_wire_gauge_drop"
  }
}

Input Schema

NameRequiredDescriptionDefault
wire_gaugeNoWire Gauge (12 for 12AWG, 10 for 10AWG) (AWG). 14 AWG (15A), 12 AWG (20A), 10 AWG (30A), 8 AWG (50A). Default: 12. Min: 0. Max: 14.
load_amperesNoContinuous Load Amperage (amps). 16A continuous on a 20A breaker (80% rule). Default: 16. Min: 1. Max: 200.
circuit_voltageNoCircuit Voltage (volts). 120V standard branch circuit, 240V for heavy equipment. Default: 120. Min: 12. Max: 480.
one_way_distanceNoOne-Way Conductor Length (ft). Distance from panel to load. Default: 100. Min: 10. Max: 1000.