omni_generator_kw_kva_sizing
Calculate standby generator sizing by combining continuous kW load with locked-rotor motor starting kVA inrush, yielding recommended kW, peak starting kVA, and running kVA.
Instructions
Standby Generator kW vs Starting kVA Sizing Calculator. Calculate emergency standby generator sizing, accounting for locked rotor motor inrush starting kVA and continuous running kW loads. Discipline: ENERGY. Governing mathematical model / formula: Generator Starting kVA = Running kVA + Σ (Motor HP × Starting Inrush Multiplier).
USAGE GUIDELINES:
WHEN TO USE: Invoke for deterministic calculation of recommended_gen_kw (Recommended Generator kW), starting_kva_peak (Peak Starting Surge kVA), continuous_running_kva (Continuous Operating kVA), max_motor_inrush_kva (Motor Inrush Demand) using continuous_kw (Continuous Running Load (kW) in kW), largest_motor_hp (Largest Single Motor (HP) in HP), motor_start_type (Motor Starter (1 = Across-Line DOL, 2 = Soft Starter, 3 = VFD)), power_factor (Generator Power Factor (Typically 0.8)). Guarantees exact machine floating-point precision, eliminating LLM arithmetic mistakes and formula hallucinations.
WHEN NOT TO USE: Do not use for qualitative evaluations or unquantified reasoning. All input parameters must be valid numerical values.
DISAMBIGUATION & BOUNDARIES:
Use this dedicated specialist tool for 'Standby Generator kW vs Starting kVA Sizing Calculator' rather than generic dispatchers like omni_universal_query.
For multi-calculation chained jobs, use 'omni_batch_calculate'.
To inspect schema fields, see 'omni_describe_solver'.
BEHAVIOR & SAFETY:
Pure deterministic computation with machine floating-point precision.
Read-only, idempotent, and stateless. Zero side effects or persistent state mutations.
Input validation: All arguments are validated against physical and domain bounds. Out-of-bounds inputs return a safe diagnostic error status without throwing runtime exceptions.
RETURNS:
Structured JSON object containing:
status (string): "success" on valid execution or "error" if validation fails
calculator (string): "generator-kw-kva-sizing"
category (string): "energy"
name (string): "Standby Generator kW vs Starting kVA Sizing Calculator"
formula (string): Governing mathematical formula string
inputs (object): Echoed input parameter dictionary with applied defaults
metrics (object): Dictionary of computed outputs:
metrics.recommended_gen_kw (Recommended Generator kW): Formatted display string (e.g. '35 kW Standby')
metrics.starting_kva_peak (Peak Starting Surge kVA): Formatted display string (e.g. '58.2 kVA')
metrics.continuous_running_kva (Continuous Operating kVA): Formatted display string (e.g. '27.5 kVA')
metrics.max_motor_inrush_kva (Motor Inrush Demand): Formatted display string (e.g. '30.0 kVA')
execution_time_ms (number): Latency in milliseconds.
Tool call template
This tool declares no required parameters. Add optional parameters from the input schema as needed.
{
"id": 1,
"jsonrpc": "2.0",
"method": "tools/call",
"params": {
"arguments": {},
"name": "omni_generator_kw_kva_sizing"
}
}Input Schema
| Name | Required | Description | Default |
|---|---|---|---|
| power_factor | No | Generator Power Factor (Typically 0.8). Standard 3-phase generator rating is 0.8 PF. Default: 0.8. Min: 0.7. Max: 1. | |
| continuous_kw | No | Continuous Running Load (kW) (kW). Base lighting, computers, refrigeration, servers. Default: 22. Min: 5. Max: 500. | |
| largest_motor_hp | No | Largest Single Motor (HP) (HP). Well pump, elevator, or air conditioning compressor. Default: 5. Min: 0.5. Max: 100. | |
| motor_start_type | No | Motor Starter (1 = Across-Line DOL, 2 = Soft Starter, 3 = VFD). DOL = 6x inrush, Soft-start = 3x, VFD = 1.2x. Default: 1. Min: 1. Max: 3. |