xae_links
Inspect PLC instance I/O variable links and list unlinked variables, stale link targets, and links XAE could not restore, so you can diagnose missing or broken I/O mappings.
Instructions
Variable links of the PLC instance: every AT %I*/%Q* variable (from the instance's XML) with its link targets (the project's mapping table, ProduceMappingInfo); lists the unlinked ones — array elements too, the usual reason an output never moves — and links whose variable is gone. plc_project_path: plc_path, iec_project_path or instance_path. What could not be read is said (unlinked_count null), never counted as 0. not_restored: links the saved project keeps but XAE could not restore (RestoreInfo in the .tsproj / .xti, e.g. ANotFound after a variable moved) — ProduceMappingInfo does not list them.
Input Schema
| Name | Required | Description | Default |
|---|---|---|---|
| plc_project_path | Yes |
Output Schema
| Name | Required | Description | Default |
|---|---|---|---|
No arguments | |||