liquid_loop_hydraulics
Size liquid-cooling loops by calculating coolant flow from heat load and Delta-T, pipe velocity, and pressure drop from friction, fittings, and quick-disconnect couplings; flags >3.0 m/s.
Instructions
Size a liquid-cooling loop (for example an NVL72 rack or a liquid load bank).
Computes the required coolant flow from heat load and Delta-T (Q = m_dot * cp * dT), the mean velocity in the pipe, and the pressure drop from pipe friction, local loss coefficients (zeta) and quick-disconnect couplings (from published Cv values). coolant: "water" or "pg25" (25 % propylene glycol), or pass your own density, specific heat and viscosity. Flags velocities above the 3.0 m/s field guideline.
Tool call template
Replace each placeholder with a value matching the input schema. Only required parameters are included; add optional parameters as needed.
{
"id": 1,
"jsonrpc": "2.0",
"method": "tools/call",
"params": {
"arguments": {
"heat_kw": "<heat_kw>",
"delta_t_k": "<delta_t_k>",
"pipe_inner_diameter_mm": "<pipe_inner_diameter_mm>"
},
"name": "liquid_loop_hydraulics"
}
}Input Schema
| Name | Required | Description | Default |
|---|---|---|---|
| coolant | No | pg25 | |
| heat_kw | Yes | ||
| delta_t_k | Yes | ||
| coupling_cv | No | ||
| density_kg_m3 | No | ||
| pipe_length_m | No | ||
| viscosity_pa_s | No | ||
| pipe_roughness_mm | No | ||
| specific_heat_kj_kgk | No | ||
| pipe_inner_diameter_mm | Yes | ||
| sum_local_loss_coefficients | No |