classify_corrosion_coupon
Classifies copper and silver corrosion coupon results per ANSI/ISA-71.04 by normalizing film thickness to 30 days and reporting the worse room class (G1/G2/G3/GX).
Instructions
Classify a corrosion coupon result under ANSI/ISA-71.04-2013 (G1/G2/G3/GX).
Normalises the measured film thickness to 30 days (R30 = X * 30 / T), classifies copper and silver separately, and reports the room class as the worse of the two. A copper-only result cannot prove G1. Field blanks are reported but never subtracted.
Tool call template
Replace each placeholder with a value matching the input schema. Only required parameters are included; add optional parameters as needed.
{
"id": 1,
"jsonrpc": "2.0",
"method": "tools/call",
"params": {
"arguments": {
"copper_film_angstrom": "<copper_film_angstrom>",
"exposure_days": "<exposure_days>"
},
"name": "classify_corrosion_coupon"
}
}Input Schema
| Name | Required | Description | Default |
|---|---|---|---|
| exposure_days | Yes | ||
| copper_film_angstrom | Yes | ||
| silver_film_angstrom | No | ||
| copper_blank_angstrom | No | ||
| silver_blank_angstrom | No |