datacenter-mcp-server
Mission-critical data center engineering tools for AI agents. 8 professional-grade calculation engines covering cooling, power, GPU thermal optimization, UPS/battery sizing, tier classification, and commissioning workflows.
Built on the Model Context Protocol (MCP) standard — works with Claude Desktop, Cursor, Windsurf, Cline, and any MCP-compatible client.
Quick Start
Claude Desktop
Add to your claude_desktop_config.json:
{
"mcpServers": {
"datacenter": {
"command": "npx",
"args": ["-y", "datacenter-mcp-server"]
}
}
}Cursor / Windsurf
Add to your MCP settings:
{
"datacenter": {
"command": "npx",
"args": ["-y", "datacenter-mcp-server"]
}
}HTTP Mode (Remote)
TRANSPORT=http PORT=3001 API_KEY=your-secret npx datacenter-mcp-serverRelated MCP server: thermal-mcp-server
Tools
dc_calculate_cooling_load
Calculate ASHRAE-compliant cooling requirements for any data center facility. Inputs include IT load, redundancy level, climate zone, altitude, and humidity targets. Returns tonnage, airflow, chilled water capacity, and energy estimates.
dc_analyze_power_redundancy
Analyze electrical distribution from utility feed through UPS, PDU, and rack-level power. Supports N, N+1, 2N, and 2N+1 redundancy configurations with efficiency and cost analysis.
dc_assess_tier_classification
Evaluate facility design against Uptime Institute Tier I-IV standards. Identifies compliance gaps and provides actionable upgrade recommendations.
dc_generate_commissioning_plan
Generate L1-L5 commissioning workflows with phase sequencing, test procedures, and documentation requirements per ASHRAE Guideline 0.
dc_analyze_rack_density
Analyze rack power density configurations from 5 kW to 100+ kW per rack. Covers cooling strategy selection, weight loading, and power distribution.
dc_gpu_cooling_optimizer
Optimize cooling infrastructure for GPU/AI workloads (H100, A100, H200, B200, GB200). Calculates thermal loads, recommends cooling strategies (air, rear-door, direct liquid, immersion), sizes CDUs, and projects energy savings.
dc_ups_battery_sizing
Size UPS modules and battery systems with N/N+1/2N/2N+1 redundancy. Compares VRLA vs lithium-ion with 10-year TCO analysis, floor space estimates, and weight calculations.
dc_reference_lookup
Query ASHRAE standards, Uptime Institute tier requirements, and industry best practices for data center design and operations.
Engineering Standards
All calculations comply with:
ASHRAE TC 9.9 thermal guidelines
Uptime Institute Tier Standard topology
NFPA 70 / NEC electrical code
ASHRAE Guideline 0 commissioning
Development
# Install dependencies
npm install
# Build
npm run build
# Run tests (264 tests across 7 suites)
npm test
# Start in stdio mode (MCP default)
npm start
# Start in HTTP mode
npm run start:http
# Inspect with MCP Inspector
npm run inspectArchitecture
src/
index.ts # MCP server entry point, tool registration
types.ts # TypeScript interfaces for all tools
constants.ts # Engineering constants and reference data
middleware.ts # Express middleware (auth, rate limiting, CORS)
schemas/ # Zod validation schemas per tool
services/ # Calculation engines per tool
tests/ # Jest test suites (264 tests)License
MIT - NextGen Mission Critical
Available Tools
8 toolsdc_analyze_power_redundancyPower Redundancy AnalyzerARead-onlyIdempotent
Analyze power redundancy configuration for a mission-critical data center.
Calculates UPS module count and sizing, generator count and total capacity, PDU requirements and switchgear feeds, electrical efficiency chain losses, UPS loading percentage, and concurrent maintainability / fault tolerance assessment.
Supports N, N+1, 2N, and 2N+1 redundancy configurations.
Args:
it_load_kw (number): Total IT load in kW
redundancy_config (string): "N", "N+1", "2N", or "2N+1"
ups_module_size_kw (number): Individual UPS module capacity (default: 500 kW)
generator_size_kw (number): Individual generator capacity (default: 2000 kW)
ups_efficiency (number): UPS efficiency 0.8-0.99 (default: 0.95)
pdu_efficiency (number): PDU efficiency 0.9-0.999 (default: 0.98)
transformer_efficiency (number): Transformer efficiency (default: 0.985)
Returns structured JSON with complete power infrastructure sizing and recommendations.
Examples:
"Size a 2N UPS system for 3 MW" -> it_load_kw: 3000, redundancy_config: "2N"
"What do I need for N+1 at 1.5 MW with 750 kW UPS modules?" -> it_load_kw: 1500, redundancy_config: "N+1", ups_module_size_kw: 750
Inputs: it_load_kw (required), redundancy_config (required), pdu_efficiency, ups_efficiency, +3 more.
dc_analyze_rack_densityRack Density AnalyzerARead-onlyIdempotent
Analyze rack density classification and recommend appropriate cooling strategies.
Classifies rack density (low/medium/high/ultra-high/liquid-cooled), recommends cooling approach, estimates airflow requirements per rack, and flags containment and liquid cooling thresholds.
Args:
rack_count (number): Total number of racks
avg_kw_per_rack (number): Average power per rack in kW
floor_area_sqft (number): Optional white space area for W/sqft calculation
cooling_type (string): Optional current/planned cooling type
Returns density classification, recommended cooling strategy, airflow estimates, and recommendations.
Examples:
"I have 200 racks at 8 kW each in 10,000 sqft" -> rack_count: 200, avg_kw_per_rack: 8, floor_area_sqft: 10000
"Cooling strategy for 50 GPU racks at 40 kW" -> rack_count: 50, avg_kw_per_rack: 40
Inputs: rack_count (required), avg_kw_per_rack (required), cooling_type, floor_area_sqft.
dc_assess_tier_classificationTier Classification AssessmentARead-onlyIdempotent
Assess a data center's Uptime Institute Tier classification based on its infrastructure configuration.
Evaluates power redundancy, cooling redundancy, distribution paths, concurrent maintainability, and fault tolerance against Tier I-IV requirements. Identifies gaps between current infrastructure and target tier.
Args:
target_tier (number): Target Tier level 1-4
power_redundancy (string): Current power config ("N", "N+1", "2N", "2N+1")
cooling_redundancy (string): Current cooling config
distribution_paths (number): Number of independent power paths
concurrently_maintainable (boolean): Can maintain without IT impact?
fault_tolerant (boolean): Automatic fault handling?
generator_backed (boolean): Generator backup available?
ups_runtime_minutes (number): UPS battery runtime (default: 10)
fire_suppression (boolean): Clean agent suppression installed?
monitoring_system (boolean): BMS/DCIM installed?
Returns target vs achieved tier, gap analysis with severity ratings, uptime expectations, and recommendations.
Examples:
"Does my N+1 facility qualify for Tier III?" -> target_tier: 3, power_redundancy: "N+1", cooling_redundancy: "N+1", distribution_paths: 1, concurrently_maintainable: false, fault_tolerant: false, generator_backed: true
"Assess our 2N facility against Tier IV" -> target_tier: 4, power_redundancy: "2N", cooling_redundancy: "2N", distribution_paths: 2, concurrently_maintainable: true, fault_tolerant: true, generator_backed: true
Inputs: target_tier (required), fault_tolerant (required), generator_backed (required), power_redundancy (required), +6 more.
dc_calculate_cooling_loadData Center Cooling Load CalculatorARead-onlyIdempotent
Calculate the total cooling load for a data center facility based on IT load, PUE, and environmental factors.
This tool computes cooling capacity requirements in kW, tons, and BTU/hr, estimates required airflow in CFM, rates the facility's PUE efficiency, and provides actionable recommendations for cooling system design.
Accounts for: IT heat rejection, electrical overhead losses, lighting loads, humidification, and altitude derating above 5,000 ft.
Args:
it_load_kw (number): Total IT electrical load in kW
pue (number): Power Usage Effectiveness ratio (1.0-3.0)
safety_factor (number): Design margin (default 1.15 = 15%)
lighting_area_sqft (number): Floor area for lighting heat gain
include_humidification (boolean): Include humidification load
altitude_ft (number): Site altitude for equipment derating
design_outdoor_temp_f (number): ASHRAE design day temperature
Returns structured JSON with cooling_load_kw, cooling_load_tons, cooling_load_btu, estimated_airflow_cfm, pue_rating, and engineering recommendations.
Examples:
"Calculate cooling for a 2 MW data center with PUE of 1.4" -> it_load_kw: 2000, pue: 1.4
"What cooling do I need for 500 kW at 6000 ft altitude?" -> it_load_kw: 500, pue: 1.5, altitude_ft: 6000
Inputs: pue (required), it_load_kw (required), altitude_ft, safety_factor, +3 more.
dc_generate_commissioning_planCommissioning Plan GeneratorARead-onlyIdempotent
Generate a comprehensive data center commissioning plan following ASHRAE guidelines (Levels 1-5).
Creates a structured commissioning plan with test procedures, durations, milestones, and prerequisites scaled to facility size and tier complexity.
Commissioning Levels:
L1: Factory Witness Testing
L2: Component Verification & Startup
L3: System Functional Performance Testing
L4: Integrated Systems Testing (load bank, concurrent maintenance, fault injection)
L5: Operational Sustainability (seasonal verification)
Args:
facility_size_kw (number): Design IT capacity in kW
tier_level (number): Target Tier 1-4 (affects test complexity)
include_levels (number[]): Which commissioning levels to include [1,2,3,4,5]
custom_systems (string[]): Optional custom systems list
Returns structured plan with phases, test procedures, durations, milestones, and recommendations.
Examples:
"Generate a full Cx plan for a 5 MW Tier III facility" -> facility_size_kw: 5000, tier_level: 3, include_levels: [1,2,3,4,5]
"Just L3 and L4 for a 1 MW Tier II" -> facility_size_kw: 1000, tier_level: 2, include_levels: [3,4]
Inputs: tier_level (required), include_levels (required), facility_size_kw (required), custom_systems.
dc_gpu_cooling_optimizerGPU Power & Cooling OptimizerARead-onlyIdempotent
Optimize cooling infrastructure for GPU/AI workloads. Calculates thermal loads for modern GPU clusters (H100, A100, H200, B200, GB200), recommends cooling strategies (air, rear-door, direct liquid, immersion), and projects energy costs and savings.
Handles the unique thermal challenges of AI/ML deployments: extreme power density (30-120+ kW/rack), liquid cooling CDU sizing, coolant flow rates, and PUE impact analysis.
Args:
gpu_count (number): Total number of GPUs
gpu_model (string): "H100", "A100", "H200", "B200", or "GB200"
rack_count (number): Number of racks housing GPUs
cooling_type (string): "air", "direct_liquid", "rear_door", or "immersion"
ambient_temp_f (number): Ambient temperature in °F (default: 95)
pue_target (number): Target PUE ratio (default: 1.3)
Returns total heat load, per-rack density, cooling strategy recommendation, CDU sizing, coolant flow rates, chilled water plant capacity, annual energy costs, and liquid vs air savings analysis.
Examples:
"Cool 64 H100 GPUs across 8 racks with liquid cooling" -> gpu_count: 64, gpu_model: "H100", rack_count: 8, cooling_type: "direct_liquid"
"What cooling do I need for 16 GB200s?" -> gpu_count: 16, gpu_model: "GB200", rack_count: 2, cooling_type: "immersion"
Inputs: gpu_count (required), gpu_model (required), pue_target (required), rack_count (required), +3 more.
dc_reference_lookupData Center Reference DataARead-onlyIdempotent
Look up data center engineering reference data including Tier requirements, PUE benchmarks, rack density classifications, and commissioning phases.
Args:
category (string): One of "tier_requirements", "pue_benchmarks", "rack_density", "commissioning_phases"
tier (number): Optional — filter tier requirements by specific tier (1-4)
Returns reference data tables for data center engineering decisions.
Examples:
"What are the Tier III requirements?" -> category: "tier_requirements", tier: 3
"Show me PUE benchmarks" -> category: "pue_benchmarks"
"Rack density classifications" -> category: "rack_density"
Inputs: category (required), tier.
dc_ups_battery_sizingUPS & Battery Sizing CalculatorARead-onlyIdempotent
Size UPS systems and battery plants for mission-critical data center facilities. Calculates UPS module count, battery string sizing, floor space, structural load, and 10-year Total Cost of Ownership comparing VRLA vs Lithium-Ion batteries.
Supports all standard redundancy configurations (N, N+1, 2N, 2N+1) and both battery technologies with lifecycle cost analysis including replacement cycles.
Args:
critical_load_kw (number): Critical IT load in kW
redundancy (string): "N", "N+1", "2N", or "2N+1"
runtime_minutes (number): Required battery runtime (5, 10, 15, or 30)
battery_type (string): "VRLA" or "lithium_ion"
ups_efficiency (number): UPS efficiency 0.8-0.99 (default: 0.96)
growth_factor (number): Design growth margin 1.0-2.0 (default: 1.2)
Returns UPS module sizing, battery string count, energy capacity, floor space requirements, weight estimates, 10-year TCO comparison, and recommendations.
Examples:
"Size a 2N UPS with 15 min lithium batteries for 2 MW" -> critical_load_kw: 2000, redundancy: "2N", runtime_minutes: 15, battery_type: "lithium_ion"
"Compare VRLA vs lithium for 500 kW N+1" -> critical_load_kw: 500, redundancy: "N+1", runtime_minutes: 10, battery_type: "VRLA"
Inputs: redundancy (required), battery_type (required), runtime_minutes (required), critical_load_kw (required), +3 more.
Tool Schema Changelog
Recent tool additions, removals, and schema changes observed during successful MCP inspections.
Loading tool schema changelog…
TDQS
Scored across 8 tools
Each tool addresses a distinct data center engineering concern—cooling, power redundancy, tier assessment, commissioning, rack density, GPU cooling, UPS sizing, and reference lookup. There is no semantic overlap that would cause an agent to select the wrong tool.
Most tools follow a verb_noun pattern (dc_calculate_cooling_load, dc_analyze_power_redundancy, dc_generate_commissioning_plan), but three deviate: dc_gpu_cooling_optimizer, dc_ups_battery_sizing, and dc_reference_lookup use noun-based phrasing. This mixed convention undermines predictability.
Eight tools is a well-scoped count for a data center engineering server. Each tool adds meaningful capability, and the set is neither bloated nor too sparse.
The server covers core design and analysis tasks including cooling, power, redundancy, tier classification, commissioning, and GPU-specific cooling. Minor gaps exist (e.g., no energy cost or physical security tools), but the domain is well covered.
Maintenance
Related MCP Connectors
27 engineering compliance and calculation tools for the built environment (UK, EU, UAE).
Heating, ventilation and energy engineering calculations and diagnostics for AI agents.
Design, solve and simulate HVAC systems from real components, weather years and buildings.
AI data-center design engine: size, validate & lay out Rubin-era data centers. Korea live.
Related MCP Servers
- AlicenseAqualityDmaintenanceEnables AI agents to perform unit-aware engineering calculations with automatic unit conversion, dependency resolution, and access to 500+ units across 75+ categories through the CalcsLive calculation engine.321 npmMIT
- AlicenseNot gradedqualityCmaintenanceA physics engine for liquid-cooled GPU systems, exposed as an AI-callable MCP server. Enables thermal analysis, coolant comparison, flow optimization, and rack-level sizing via natural language queries.1MIT
- AlicenseAqualityDmaintenanceEstimates GPU requirements, training/inference costs, and cloud-vs-on-prem TCO for AI workloads using deterministic calculators.121MIT

security-orchestraofficial
FlicenseNot gradedqualityCmaintenanceProvides deterministic, standards-based calculations for data center critical power infrastructure. Enables site selection, generator sizing, UPS sizing, NFPA 110 compliance, and more via 50+ AI agents and 8 compound chains.-