We provide all the information about MCP servers via our MCP API.
curl -X GET 'https://glama.ai/api/mcp/v1/servers/tbrennem-source/sf-permits-mcp'
If you have feedback or need assistance with the MCP directory API, please join our Discord server
--- Page 1 ---
~ 1 ~
2025
San Francisco Green Building Code
Amendments to the
2025 California Green Building Standards Code
(CALGreen)
Operative date: January 1, 2026
--- Page 2 ---
~ 2 ~
Text Format:
Unchanged language from the 2025 California Code is shaded, and may
include bold and/or italicized formatting.
San Francisco amendments are printed in unformatted ("plain") text, and may
include bold and/or italicized formatting.
[ ← ] An arrow represents the location of language that has been deleted by San Francisco from
the 2025 California Code.
A solid line represents a change from the original published edition of the 2025 San Francisco
Green Building Code.
Chapter 1
ADMINISTRATION
SECTION 101 – GENERAL
101.1 Revise this section as follows:
101.1 Title. These regulations shall be known as the [ ← ] San Francisco Green
Building [ ← ] Code, and may be cited as such, and will be referred to herein as “this
code”. [ ← ] The [ ← ] San Francisco Green Building [ ← ] Code is Part 11 of thirteen parts of
the official compilation and publication of the adoption, amendment and repeal of building
regulations to the California Code of Regulations, Title 24, [ ← ] and Chapter 13C of San
Francisco Building Inspection Commission Amendments to the California Building Standards
Code.
101.2 Revise this section as follows:
101.2 Purpose. The purpose of this [ ← ] chapter is to promote the health, safety and general
welfare of San Francisco residents, workers, and visitors by [ ← ] minimizing waste of energy,
water, and other resources in the construction and operation of buildings in the City and County
of San Francisco and by providing a healthy indoor environment. The green building practices
required by this chapter will also further the goal of reducing the greenhouse gas emissions in the
City and County of San Francisco to 61 percent below 1990 levels by the year 2030, as stated in
San Francisco Environment Code Chapter 9.
101.3 Revise this section as follows:
101.3 Scope. The provisions of this code shall apply to the planning, design, operation,
construction, use and occupancy of every newly constructed building or structure, unless
otherwise indicated in this code, as well as alterations to existing buildings throughout [ ← ] the
City and County of San Francisco.
While [ ← ] this code [ ← ] references green building programs, the City and County of San
Francisco does not confer certification [ ← ] under any green building program.
101.3.1 Revise this section as follows:
101.3.1 [ ← ] Regulated buildings, structures and applications. Provisions of this code shall
apply to the following buildings, structures, and applications regulated by state agencies as
specified in Sections 103 through 106 [ ← ] of California Green Building Standards Code Title
--- Page 3 ---
~ 3 ~
24 Part 11, modified by local ordinance with supplemental requirements applicable to occupancy
types A, B, I, M, E and R as defined by California Building Code Title 24 Section 302 (2022
2025) as amended pursuant to Section 101.7. When adopted by a state agency, the provisions of
this code shall be enforced by the appropriate enforcing agency, but only to the extent of
authority granted to such agency by statute.
101.4 Revise this section as follows:
101.4 Appendices. [ ← ] [Reserved]
101.6 Revise this section as follows:
101.6.1 Differences. In the event of any differences between these building standards and the
standard reference documents, the text of [ ← ] this Chapter shall govern.
101.6.3 Revise this section as follows:
101.6.3 Conflicts. When the requirements of this code conflict with the requirements of any
other part of the California Building Standards Code, Title 24, any provision contained
elsewhere in the San Francisco Municipal Code, or any regulation or requirement adopted by the
Public Utilities Commission or other City agency under its Charter authority, the most restrictive
requirement shall prevail.
101.7 Revise this section as follows:
101.7 City [ ← ] and county amendments, additions [ ← ] and deletions. This code includes
the amendments, deletions, and additions to California green building requirements which
maintain stricter local green building standards.
101.10 Revise this section as follows:
101.10 [ ← ] Equivalency. Wherever reference is made to the LEED® or GreenPoint Rated
systems, a comparable equivalent rating system may be used if approved by the Director. The
applicable LEED®, GreenPoint Rated or equivalent versions of performance standards for
applications subject to this chapter are:
LEED v4 for Interior Design and Construction (LEED v4 ID+C)
LEED v4 for Building Design and Construction (LEED v4 BD+C)
LEED v4 for Homes Design and Construction
GreenPoint Rated (GPR) Single Family New Home Construction – 9.0 10.0 or current
GreenPoint Rated (GPR) Multifamily New Home Construction – 9.0 or current
GreenPoint Rated (GPR) Existing Multifamily –v1.0 2.0 or current
Wherever specific LEED prerequisites or credits are cited, such references are to LEED v4
BD+C. More recent LEED and GreenPoint Rated versions may be used, provided the credits and
points achieved are as or at least as stringent as LEED v4 BD+C or GPR v9.0 10.0.
Wherever the LEED or GreenPoint Rated systems include a minimum energy or other
performance requirement, the permit applicant may choose to meet the minimum performance
requirements with an alternative equivalent method approved by the Director.
Compliance with any of these requirements may be verified and/or certified by any means,
including third-party review or equivalent requirements verified via other rating systems, as
approved by the Director.
101.11 Revise this section as follows:
101.11 Effective use of this code. The following steps shall be used to establish which
provisions of this code are applicable to a specific occupancy:
1. Establish the type of occupancy.
[ ← ] 2. Find the section which covers the established occupancy.
3. Identify the minimum requirements of this code for the [ ← ] established occupancy in
Sections 4 and 5.
--- Page 4 ---
~ 4 ~
[ ← ] 4. Administrative Bulletin 93, provided by the Department of Building Inspection,
summarizes how the requirements of San Francisco Green Building Code and relevant local
requirements may be met. Appendices to Administrative Bulletin 93 include tabular summaries
of required measures, and provide submittal forms.
Chapter 2
DEFINITIONS
SECTION 202 – DEFINITIONS
202 Add and amend the following definitions:
ELECTRIC VEHICLE CHARGING SPACE (EV Space). A space intended for future
installation of EV charging equipment and charging of electric vehicles. The EV Space need not
be reserved exclusively for electric vehicle charging.
ELECTRIC VEHICLE CHARGING STATION (EVCS). One or more electric vehicle
charging spaces served by electric vehicle charger(s) or other charging equipment allowing
charging of electric vehicles. For purposes of determining compliance with accessibility
requirements, when the permitted length of time a vehicle may occupy an electric vehicle
charging station differs from the permitted duration of stay in publicly accessible parking spaces
in the same parking area, electric vehicle charging stations are not considered parking
spaces. When the permitted duration of stay in a space served by electric vehicle charger(s) is the
same as other publicly accessible parking spaces in the same parking area, EVCS may be
considered parking spaces. The EVCS need not be reserved exclusively for electric vehicle
charging.
GREENPOINT RATED, GREENPOINTS and GREENPOINTS CHECKLIST. The
residential green building rating system and checklist and certification methodology of the non-
profit organization Build It Green.
HISTORICAL RESOURCE. A property that meets the terms of the definitions in Section
21084.1 of the CEQA Statute (The California Environmental Quality Act [Public Resources
Code Section 21084.1]) and Section 15064.5 of the CEQA Guidelines, as determined by the San
Francisco Planning Department.
LARGE COMMERCIAL BUILDING. A commercial building or addition of Group B, M, A,
I, or E, occupancy that is 25,000 gross square feet or more.
LEED® and LEED® CHECKLIST. The Leadership in Energy and Environment Design
rating system, certification methodology, and checklist of the United States Green Building
Council (USGBC).
MAJOR ALTERATIONS. Alterations and additions where interior finishes are removed and
significant upgrades to structural and mechanical, electrical, and/or plumbing systems are
proposed where areas of such construction are 25,000 gross square feet or more in Group B, M,
or R occupancies of existing buildings.
MIXED-FUEL BUILDING. A building that uses natural gas or propane as fuel for space
heating, water heating (including pools and spas), cooking appliances or clothes drying
appliances, or is plumbed for such equipment.
--- Page 5 ---
~ 5 ~
NEW LARGE COMMERCIAL INTERIORS. First-time tenant improvements where areas of
such construction are over 25,000 gross square feet or more in Group B or M occupancy areas of
existing buildings.
NEWLY CONSTRUCTED (or NEW CONSTRUCTION). A newly constructed building (or
new construction) is a building that has never before been used or occupied for any purpose
and does not include additions, alterations or repairs.
TOTAL ENERGY DESIGN RATING. A metric required by the California Energy
Commission to be applied to low-rise residential construction in order to comply with California
Title 24 Part 6 Energy Standards. The Total Energy Design Rating has two components: (a) the
Energy Efficiency Design Rating; and (b) the Solar Electric Generation and Demand Flexibility
Design Rating. The Solar Electric Generation and Demand Flexibility Design Rating is
subtracted from the Energy Efficiency Design Rating to determine the Total Energy Design
Rating. California Energy Standards require that each building must separately comply with the
Energy Efficiency Design Rating and the Total Energy Design Rating.
RESIDENTIAL LONG-TERM BICYCLE PARKING. [HCD] A secure locker, weather
protected enclosure, or storage room that provides bicycle parking for more than twelve hours
that allows individual locking of bicycles to a permanently anchored parking device or rack.
RESIDENTIAL SHORT-TERM BICYCLE PARKING. [HCD] A permanently anchored
bicycle parking device, rack or lockers, in an unsheltered, open area, that provides bicycle
parking for twelve hours or less that allows individual locking of bicycles to the parking device
or rack.
Chapter 3
GREEN BUILDING
SECTION 301 – GENERAL
301.1 Revise this section as follows:
301.1 Scope. Buildings in the City and County of San Francisco shall be designed to include the
green building measures specified as mandatory [ ← ] under the California Green Building
Standards Code (CalGreen).
Additional green building requirements established by the City and County of San Francisco
are mandatory for:
(1) Newly constructed Group R occupancy buildings,
(2) Newly constructed buildings of Group B, M, A, and I occupancies that are 25,000 gross
square feet or more,
(3) New first-time build-outs of commercial interiors that are 25,000 gross square feet or
more in buildings of Group B or M occupancies, and
--- Page 6 ---
~ 6 ~
(4) Major alterations that are 25,000 gross square feet or more in existing buildings of Group
B, M or R occupancies, where interior finishes are removed and significant upgrades to structural
and mechanical, electrical and/or plumbing systems are proposed.
SECTION 302 – MIXED OCCUPANCY BUILDINGS
302.1 Revise this section as follows:
302.1 Mixed Occupancy Buildings. In mixed occupancy buildings, each portion of a building
shall comply with the specific [ ← ] measures applicable to each specific occupancy as required
by California Code of Regulations Title 24 Part 11 and the San Francisco Green Building Code.
However, to fulfill any requirements of San Francisco Green Building Code Sections 4.103
through 4.105 and 5.103 through 5.105, as applicable, the project sponsor may apply a single
required green building standard tothe entire building.
Exceptions:
1. [HCD] Accessory structures and accessory occupancies serving residential buildings
shall comply with Chapter 4 and Appendix A4, as applicable.
2. [HCD] For the purposes of CALGreen, live/work units, complying with Section 419 of
the California Building Code, shall not be considered mixed occupancies. Live/work units shall
comply with Chapter 4 and Appendix A4, as applicable.
SECTION 303 – PHASED PROJECTS
303.1.1.1 Add the following section:
303.1.1.1 Maintenance of required features. Any structure subject to this chapter shall
maintain the green building features required herein, or equivalent, regardless of subsequent
alterations, additions, or changes of use, unless subject to subsequent or more stringent
requirements.
304 Modify the following section:
SECTION 304 – VOLUNTARY TIERS
[ ← ] This section not applicable in San Francisco.
305 Modify the following section:
SECTION 305 [OSHPD 1] – CALGREEN TIER 1 AND
CALGREEN TIER 2
[ ← ] This section not applicable in San Francisco.
306 Modify the following section:
SECTION 306 [ ← ] – VOLUNTARY MEASURES
[ ← ] This section not applicable in San Francisco.
Chapter 4
RESIDENTIAL MANDATORY MEASURES
--- Page 7 ---
~ 7 ~
Division 4.1
PLANNING AND DESIGN
SECTION 4.101 – GENERAL
4101.1 Revise the section as follows:
4.101.1 Scope. The provisions of this division outline planning, design and development
methods that include environmentally responsible site selection, building design, building siting
and development to protect, restore and enhance the environmental quality of the
site, [ ← ] respect the integrity of adjacent properties and promote the health, safety and welfare
of San Francisco residents.
4.103 Replace this section as follows:
[ ← ] SECTION 4.103 – REQUIREMENTS FOR GROUP R
OCCUPANCY BUILDINGS
4.103.1 New low-rise residential buildings.
4.103.1.1 Rating requirements
New residential buildings must be GreenPoint Rated and applicants must submit
documentation demonstrating that a minimum of 75 GreenPoints from the GreenPoints Single
Family New Construction Checklist or the GreenPoints Multifamily New Construction Checklist
will be achieved. Alternatively, this rating requirement may be met by obtaining LEED Silver
certification.
4.103.1.2 Stormwater management
Projects subject to this section shall meet the San Francisco Public Utilities Commission
stormwater management requirements.
4.103.2 New high-rise residential buildings
4.103.2.1 Rating requirement
Permit applicants must submit documentation to achieve LEED® “Silver” certification.
Alternatively, this rating requirement may be met by obtaining the GreenPoint Rated designation
and submitting documentation demonstrating that a minimum of 75 GreenPoints from the
GreenPoint Rated Multifamily New Construction checklist will be achieved.
4.103.2.2 [Reserved]
4.103.2.3 Construction debris management. Permit applicants must submit documentation
verifying the diversion of a minimum 75 percent of the projects construction and demolition
debris. The waste management plan necessary to meet this requirement shall be updated as
necessary and shall be accessible during construction for examination by the Department of
Building Inspection. Permit applicants must also meet the requirements of San Francisco
Environment Code Chapter 14 and San Francisco Building Code Chapter 13B (Construction and
Demolition Debris Recovery Program.)
4.103.2.4 Stormwater management. Projects subject to this section shall meet the San
Francisco Public Utilities Commission stormwater management requirements.
4.103.2.4.1 Construction activity stormwater pollution prevention. All projects, whether
greater or lesser than one acre, must develop and implement construction activity pollution
prevention and site run-off controls adopted by the San Francisco Public Utilities Commission.
4.103.3 Major Alterations to Existing Group R Occupancy Buildings.
--- Page 8 ---
~ 8 ~
4.103.3.1 Rating Requirement.
Permit applicants must submit documentation to achieve a LEED® Silver rating. Alternatively,
this rating requirement may be met by obtaining the GreenPoint Rated designation and
submitting documentation demonstrating that a minimum of 75 GreenPoints from the
GreenPoint Rated Multifamily checklist will be achieved. Major alterations applying to less than
80% of the building’s gross floor area may alternately submit documentation demonstrating that
49 points from the GreenPoint Rated Existing Multifamily checklist have been achieved within
the project area.
4.103.3.2 Low-Emitting Materials.
Alterations utilizing LEED must submit documentation verifying that low-emitting materials
are used, subject to on-site verification, meeting at least the following categories of materials
covered under LEED EQ Credit Low-Emitting Materials wherever applicable: interior paints and
coatings applied on-site, interior sealants and adhesives applied on site, flooring, and composite
wood.
Alterations utilizing GreenPoint Rated must submit documentation to verify the use of low-
emitting materials meeting the GreenPoint Rated Multifamily New Homes measures for low-
emitting coatings, adhesives and sealants, and carpet systems.
4.104 Replace this section as follows:
SECTION 4.104 – [ ← ] HISTORIC PRESERVATION
4.104.1 On-site retention of historical features. For alterations of buildings determined to be
historical resources, after demonstrating compliance with all applicable codes, including the
2022 California Building Energy Efficiency Standards (Title 24, Part 6) and the 2022 California
Historical Building Code (Title 24, Part 8), the minimum points or credits required under this
chapter shall be reduced for retention and in-situ reuse or restoration of certain character defining
features, as described in Table 4.104A. Retention includes the rehabilitation and repair of
character-defining features that conform to the Secretary of the Interior’s Standards for the
Treatment of Historic Properties.
TABLE 4.104.A
SIGNIFICANT HISTORICAL
ARCHITECTURAL
FEATURES
PERCENT
RETAINED*
ADJUSTMENT
TO MINIMUM
LEED POINT
REQUIREMENT
ADJUSTMENT TO
MINIMUM
GREENPOINTS
REQUIREMENT
Windows @ principal façade(s) 100% 4 15
Other windows At least 50% 1 3
Other windows 100% 2 6
Exterior doors @ principal
façade(s)
100% 1 3
Siding or wall finish @ principal
façade(s)
100% 1 4
Trim & casing @ wall openings
on principal façade(s)
100% 1 3
Roof cornices or decorative eaves
visible from right-of-way
100% 1 3
--- Page 9 ---
~ 9 ~
Sub-cornices, belt courses, water
tables, and running trim visible
from right-of-way
100% 1 3
Character-defining elements of
significant interior spaces
100% 4 15
Other exterior ornamentation (e.g.
cartouches, corbels, quoins, etc.)
visible from right-of-way
80% 1 3
4.104.2. Adjustment to Green Credit for Retention of Historic Features. Where the historical
resource is a portion of the total project, the LEED or GreenPoint Rated requirement shall be
adjusted to equal the percentage of gross floor area of the historical resource compared to the
total project gross floor area.
4.105 Replace this section as follows:
SECTION 4.105 – [ ← ] DEMOLITION OF EXISTING
STRUCTURES
4.105.1 Adjustments to Rating Requirements for Building Demolition and
Density. Applications subject to the San Francisco Green Building Code, whereby construction
of a new building is proposed within five years of the demolition of a building on the site, where
such demolition occurred after the effective date of the Green Building Ordinance - November 3,
2008 - the sustainability requirements for new buildings pursuant to the San Francisco Green
Building Code shall be increased as follows:
4.105.1.1 LEED® Projects. For projects attaining a LEED® certification:
(1) Where the building demolished was an historical resource, the required points shall be
increased by 10 points.
(2) Where the building demolished was not an historical resource, the required points shall be
increased by 6 additional points.
(3) Where the building demolished was not an historical resource and the number of
dwellings in the residential portion of the replacement structure are tripled, the required points
shall be increased by 5 additional points.
4.105.1.2 GreenPoint Rated Projects. For projects attaining GreenPoint Rated:
(1) Where the building demolished was an historical resource, the required points shall be
increased by 25 additional points.
(2) Where the building demolished was not an historical resource, the required points shall be
increased by 20 additional points.
(3) Where the building demolished was not an historical resource and the number of
dwellings in the residential portion of the replacement structure are tripled, the required points
shall be increased by 17 additional points.
SECTION 4.106 – SITE DEVELOPMENT
4.106.4 Revise this section as follows:
4.106.4 Electric vehicle (EV) charging for new construction. New construction shall comply
with Section 4.106.4.1 or 4.106.4.2 to facilitate future installation and use of EV chargers.
Electric vehicle supply equipment (EVSE) shall be installed in accordance with the California
Electrical Code, Article 625.
--- Page 10 ---
~ 10 ~
Exceptions:
1. On a case-by-case basis, where the local enforcing agency has determined EV charging
and infrastructure are not feasible based upon one or more of the following conditions:
1.1 Where there is no local utility power supply or the local utility is unable to supply
adequate power.
1.2 Where there is evidence suitable to the local enforcing agency substantiating that
additional local utility infrastructure design requirements, directly related to the implementation
of Section 4.106.4, [ ← ] increase the utility side cost to the homeowner or the developer by
more than $400 per parking space. In such cases, buildings subject to Section 4.106.4 shall
maximize the number of EV Charging Spaces, up to a utility side cost of a maximum of $400 per
space. Cost shall be determined by dividing the increase in local utility infrastructure cost
attributable to compliance with this section by the sum of parking spaces and EV Charging
Spaces.
2. Accessory Dwelling Units (ADU) and Junior Accessory Dwelling Units (JADU) without
additional parking facilities.
4.106.4.1 New one-and-two-family dwellings and townhouses with attached or
adjacent private garages. [ ← ] For each parking space, install a 40-Amp 208 or 240-volt
branch circuit, including raceway, electrical panel capacity, overprotection devices, wire, and
termination point such as a receptacle. The termination point shall be in close proximity to the
proposed EV charger location. Raceways are required to be continuous at enclosed, inaccessible,
or concealed areas and spaces. Raceway for each circuit shall not be less than trade size 1
(nominal 1-inch inside diameter).
4.106.4.1.1 Identification. The service panel or subpanel circuit directory shall identify the
overcurrent protective device space(s) reserved for future EV charging as [ ← ] “EV READY”
for full circuits. The raceway termination location shall be permanently and visibly marked
as [ ← ] “EV READY” for full circuits.
4.106.4.2.2.1.2 Electric vehicle charging stations (EVCS) dimensions. The charging spaces
shall be designed to comply with the following:
1. The minimum length of each EV space shall be 18 feet (5486 mm).
2. The minimum width of each EV space shall be 9 feet (2743 mm).
3. One in every 25 charging spaces, but not less than one, shall also have an 8-foot (2438 mm)
wide minimum aisle. A 5-foot (1524 mm) wide minimum aisle shall be permitted provided the
minimum width of the EV space is 12 feet (3658 mm).
a. Surface slope for this EV space and the aisle shall not exceed 1 unit vertical in 48 units
horizontal (2.083 percent slope) in any direction.
b. Notwithstanding any other applicable requirements, when an EV charger is installed
serving an accessible parking space, the space may be considered a parking space if the duration
of stay is not subject to any limitations different from those generally applied to other publicly
accessible parking spaces in the same parking area. If the duration of stay in an accessible space
equipped with an EV charger is subject to limitations different from those generally applied to
other publicly accessible parking spaces in the same parking area, the space is not a parking
space.
4.106.4.2.2.1.3 Accessible EV spaces. In addition to the requirements in Sections 4.106.4.2.2.1.1
and 4.106.4.2.2.1.2, all EVSE, when installed, shall comply with the accessibility provisions for
EV chargers in the California Building Code, Chapter 11B. EV ready spaces and EVCS in
multifamily developments shall comply with California Building Code, Chapter 11A, Section
--- Page 11 ---
~ 11 ~
1109A. Accessible spaces must meet the dimensions specified in Section 4.106 .4.2.2.1.2,
Planning Code Section 154, or other applicable accessibility requirements, whichever would
result in the largest space size.
4.106.4.2.3 EV space requirements.
1. Single EV space required. [ ← ] Where a single EV space is required, install a full
circuit with a minimum of 40-Amp 208 or 240 Volt capacity, including listed raceway, sufficient
electrical panel capacity, overcurrent protection devices, wire, and termination point such as a
receptacle. The termination point shall be in close proximity to the proposed EV charger
location. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter).
2. Multiple EV spaces required. Construction documents shall indicate the raceway
termination point and the location of installed or future EV spaces, receptacles, or EV chargers.
Construction documents shall also provide information on amperage of installed or future
receptacles or EVSE, raceway method(s), wiring schematics and electrical load calculations.
Plan design shall be based upon a 40-ampere minimum branch circuit. Required raceways and
related components that are planned to be installed underground, enclosed, inaccessible or in
concealed areas and spaces shall be installed at the time of original construction.
Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV
branch circuit is installed in close proximity to the location or the proposed location of the EV
space at the time of original construction in accordance with the California Electrical Code.
a. Multiple Levels of Parking:
i. Branch circuit panelboard(s) shall be installed at each parking level with service
capacity dedicated to EV Capable Spaces and EV spaces proportional to the number of vehicle
spaces on each level, including panelboard(s) space and capacity. The circuits and overcurrent
protective devices shall remain reserved exclusively for EV charging.
Exception: Circuits and overcurrent protective devices in panelboards not located on the
same level may contribute to the requirements of 4.106.4.2.4(b), provided the circuits are
reserved exclusively for EV charging. For example, the circuit serving an EV Space dedicated to
a condominium owner may connect to the electrical panelboard of the corresponding
condominium.
ii. Install raceway or sleeves where penetrations to walls, floors, or other partitions will be
necessary to install panels, raceways, or related electrical components necessary per site
conditions for future installation of branch circuits. All such penetrations must comply with
applicable codes, including but not limited to the San Francisco Electrical Code and the San
Francisco Fire Code.
NOTES:
Electric vehicle charging infrastructure and housing are critical priorities for the City and
County of San Francisco. Automated Load Management Systems, energy efficiency, and
selection of low-amperage technologies can help mitigate increases to peak electric load. Where
the installation of a utility electrical transformer may be determined to be necessary in the
context of compliance with Section 4.106.4.2.4 of this chapter, SF Building Code
Section 106A.1.17.1, or other provisions of the San Francisco Electrical Code, and where such
transformer cannot be accommodated on the project site due to the combination of project site
dimensions, San Francisco Building Code, San Francisco Electrical Code, and applicable utility
regulations, the Director of Public Works is encouraged to issue a Sidewalk Vault Encroachment
Permit, provided that the fronting property owner complies with all requirements governing
--- Page 12 ---
~ 12 ~
street occupancy, including but not limited to the San Francisco Public Works Code and
Department of Public Works Order 165,553.
4.106.4.2.4 Identification. The service panel or subpanel circuit directory shall identify the
overcurrent protective device space(s) reserved for future EV charging purposes as “EVSE
READY” for full circuits and otherwise “EVSE CAPABLE” in accordance with the California
Electrical Code.
Division 4.2
ENERGY EFFICIENCY
SECTION 4.201 – GENERAL
4.201 Add the following section:
4.201.2. Better roofs.
(a) Newly constructed Group R occupancy buildings are required by California Title 24 Part 6
Energy Standards to install photovoltaic (PV) energy systems. For newly constructed
multifamily buildings the minimum size of such systems is required by Section 170.2(f) and
170.2(g) to be not less than the smaller of PV system size determined by Equation 170.2-C or
Equation 170.2-D, or the total of all Solar Access Roof Area (SARA) multiplied by 14 W/ft2.
Projects that constitute a Large Development Project or Small Development Project under the
Stormwater Management Ordinance (Public Works Code secs 147-147.6) may exclude from
SARA any roof area where both:
(1) The area is occupied by living roof, meaning the area of media for growing plants, and
(2) The area occupied by living roof contributes to determination of compliance with the
Stormwater Management Ordinance, as documented by a Preliminary Stormwater Control Plan
or a Modified Compliance Application submitted to the San Francisco Public Utilities
Commission.
(b) In any final Stormwater Control Plan approved by the San Francisco Public Utilities
Commission, including where such approval may occur subsequent to addenda to a Site Permit
wherein compliance with California Title 24 Part 6 Energy Standards is documented, the
applicant shall ensure the area occupied by living roof contributing to determination of
compliance with the Stormwater Management Ordinance is no less than the square footage
approved for exclusion from SARA.
4.201.3 Energy Performance.
(a) All-electric buildings. A newly constructed residential all-electric building shall be
designed and constructed such that the Energy Budget for the proposed building is no greater
than the corresponding Energy Budget for a Standard Design Building compliant with California
Title 24 Part 6 Energy Standards.
(b) Mixed-fuel residential buildings. A newly constructed mixed-fuel residential building
shall be designed and constructed such that the Energy Budget is no greater than 90% of the Title
24 Part 6 Energy Budget for the Standard Design Building as calculated by compliance software
approved by the California Energy Commission.
--- Page 13 ---
~ 13 ~
Chapter 5
NONRESIDENTIAL MANDATORY MEASURES
Division 5.1
PLANNING AND DESIGN
SECTION 5.101 – GENERAL
5.101.1 Modify the section as follows:
5.101.1 Scope. The provisions of this chapter outline planning, design and development methods
that include environmentally responsible site selection, building design, building siting and
development to protect, restore, and enhance the environmental quality of the site, [ ← ] respect
the integrity of adjacent properties, and promote the health, safety and welfare of San Francisco
residents.
5.103 Replace this section as follows:
SECTION 5.103 [ ← ] – REQUIREMENTS FOR GROUP A, B, I,
E and M BUILDINGS
5.103.1 New large commercial buildings.
5.103.1 New large commercial buildings.
5.103.1.1 Rating requirement. Permit applicants must submit documentation to achieve LEED
“Gold” certification.
5.103.1.2 Indoor water use reduction. Permit applicants must submit documentation verifying
that project meets maximum prescriptive fixture flow rates in accordance with the California
Plumbing Code. The project must also achieve the LEED WE Prerequisite Indoor Water Use
Reduction (WEp2) and a minimum 30 percent reduction in the use of indoor potable water, as
calculated to meet the LEED WE credit Indoor Water Use Reduction (WEc2).
5.103.1.3 Construction waste management. Permit applicants must submit documentation
verifying the diversion of a minimum 75 percent of the project’s construction and demolition
waste, as calculated to meet LEED MR Prerequisite Construction and Demolition Waste
Management Planning and LEED MR Credit Construction and Demolition Waste Management.
Permit applicants must also meet the requirements of San Francisco Environment Code Chapter
14 and San Francisco Building Code Chapter 13B (Construction and Demolition Debris
Recovery Program). The waste management plan necessary to meet this requirement shall be
updated as necessary and shall be accessible during construction for examination by the
Department of Building Inspection.
5.103.1.4 Commissioning. Permit applicants must submit documentation verifying that the
facility has been or will meet the criteria necessary to achieve CALGreen section 5.410.2 and
Option 1 of LEED EA credit (Enhanced Commissioning), in addition to LEED EA Prerequisite
(Fundamental Commissioning) and Verification.
5.103.1.6 Stormwater management. Projects subject to this section shall meet the San
Francisco Public Utilities Commission stormwater management requirements. All new building
--- Page 14 ---
~ 14 ~
projects must develop and implement an Erosion and Sediment Control Plan or Stormwater
Pollution Prevention Plan and implement site run-off controls adopted by the San Francisco
Public Utilities Commission as applicable.
5.103.1.7 Energy performance. [Reserved]
5.103.1.8 Temporary ventilation and IAQ management during construction. Permit
applicants must submit documentation verifying that an Indoor Air Quality Management Plan is
prepared and implemented which meets LEED EQ Credit Construction Indoor Air Quality
Management and Title 24 Part 11 Sections 5.504.1 and 5.504.3.
5.103.1.9 Low-Emitting Materials. Permit applicants must submit documentation verifying that
low-emitting materials are used, subject to on-site verification, meeting at least the following
categories of materials covered under LEED EQ Credit Low-Emitting Materials wherever
applicable: interior paints and coatings applied on-site, interior sealants and adhesives applied on
site, flooring, and composite wood.
5.103.1.10 CALGreen mandatory measures. The following measures are mandatory in
California for new non-residential buildings. Optionally, similar LEED credits can be used as
alternative compliance paths, as noted below:
Title 24 Part 11 Section(s) Topic/Requirement Alternate Compliance Option:
5.106.8 Light pollution
reduction
Meet LEED SS Credit Light Pollution Reduction
5.508.1.2 Halons not allowed
in HVAC,
refrigeration and
fire suppression
equipment.
Meet LEED EA Credit Enhanced Refrigerant
Management, and additionally document that all
HVAC&R systems do not contain CFCs or halons.
5.103.3 Major alterations to existing non-residential buildings.
5.103.3.1 Rating requirement. Permit applicants must submit documentation to achieve LEED
“Gold” certification.
5.103.3.2 Low emitting materials. Permit applicants must submit documentation verifying that
low-emitting materials are used, subject to in-site verification, meeting at least the following
categories of materials covered under LEED EQ Credit Low-Emitting Materials: interior paints
and coatings applied on-site, interior sealants and adhesives applied on site, flooring, and
composite wood.
5.103.3.3 Electric vehicle charging. Section 5.106.5.3 of this chapter shall apply to major
alterations and newly-constructed parking facilities associated with existing Group A, B, I, and
M occupancy buildings where electrical service to the building will be upgraded. In major
alterations where existing electrical service will not be upgraded, all requirements under Section
5.106.5 shall apply to the maximum extent that:
(1) does not require upgrade to existing service; and
(2) the Director does not determine that compliance with Section 5.106.5.3.3 and Title 24
Chapter 11B, if applicable, is technically infeasible, as defined in California Building Code
Chapter 2, Section 202.
5.103.4 New large commercial interiors.
--- Page 15 ---
~ 15 ~
5.103.4.1 Rating requirement. Permit applicants must submit documentation to achieve LEED
“Gold” certification.
5.103.4.2 Low emitting materials. Permit applicants must submit documentation verifying that
low-emitting materials are used, subject to in-site verification, meeting at least the following
categories of materials covered under LEED EQ Credit Low-Emitting Materials: interior paints
and coatings applied on-site, interior sealants and adhesives applied on site, flooring, and
composite wood.
5.104 Replace this section as follows:
SECTION 5.104 [ ← ] – HISTORIC PRESERVATION
5.104.1 On-site Retention of Historical Features. For alterations of buildings determined to be
historical resources, after demonstrating compliance with all applicable codes, including the
2022 California Building Energy Efficiency Standards (Title 24, Part 6) and the 2022 California
Historical Building Code (Title 24, Part 8), the minimum points or credits required under this
chapter shall be reduced for retention and in-situ reuse or restoration of certain character defining
features, as described in Table 5.104A. Retention includes the rehabilitation and repair of
character-defining features that conform to the Secretary of the Interior’s Standards for the
Treatment of Historic Properties.
TABLE 5.104.A
SIGNIFICANT HISTORICAL
ARCHITECTURAL FEATURES
PERCENT
RETAINED*
ADJUSTMENT TO
MINIMUM LEED POINT
REQUIREMENT
ADJUSTMENT TO MINIMUM
GREENPOINTS
REQUIREMENT
Windows @ principal
façade(s) 100% 4 15
Other windows At least 50% 1 3
Other windows 100% 2 6
Exterior doors @ principal
façade(s) 100% 1 3
Siding or wall finish @
principal façade(s) 100% 1 4
Trim & casing @ wall
openings on principal
façade(s)
100% 1 3
Roof cornices or decorative
eaves visible from right-of-
way
100% 1 3
Sub-cornices, belt courses,
water tables, and running
trim visible from right-of-
way
100% 1 3
Character-defining elements
of significant interior spaces 100% 4 15
Other exterior
ornamentation (e.g.
cartouches, corbels, quoins,
80% 1 3
--- Page 16 ---
~ 16 ~
etc.) visible from right-of-
way
5.104.2. Adjustment to Green Credit for Retention of Historic Features. Where the historical
resource is a portion of the total project, the LEED or GreenPoint Rated point requirement shall
be adjusted to equal the percentage of gross floor area of the historical resource compared to the
total project gross floor area.
5.105 Replace this section as follows:
SECTION 5.105 – [ ← ] DEMOLITION OF EXISTING
STRUCTURES
5.105.1 Adjustments to rating requirements. Applications subject to the San Francisco Green
Building Code, whereby construction of a new building is proposed within five years of the
demolition of a building on the site, where such demolition occurred after November 3, 2008, the
sustainability requirements for new buildings pursuant to the San Francisco Green Building Code
shall be increased as follows:
5.105.1.1 LEED® projects. For projects attaining a LEED® certification:
(1) Where the building demolished was an historical resource, the required points shall be
increased by 10 points, which is 10% of the total available in the LEED® rating system, absent
demolition.
(2) Where the building demolished was not an historical resource, the required points shall be
increased by 6 additional points, which is 10% of the maximum total required points under this
chapter, absent demolition.
(3) Where the building demolished was not an historical resource and the number of
dwellings in the residential portion of the replacement structure are tripled, the required points
shall be increased by 5 additional points, which is 8% of the maximum total required points
under this chapter, absent demolition.
5.105.1.2 GreenPoint rated projects. For projects attaining GreenPoint Rated:
(1) Where the building demolished was an historical resource, the required points shall be
increased by 25 additional points.
(2) Where the building demolished was not an historical resource, the required points shall be
increased by 20 additional points.
(3) Where the building demolished was not an historical resource and the number of
dwellings in the residential portion of the replacement structure are tripled, the required points
shall be increased by 17 additional points.
SECTION 5.106 – SITE DEVELOPMENT
5.106.5.3 Revise this section as follows:
5.106.5.3 Revise this section as follows:
5.106.5.3 Electric vehicle (EV) charging. [N] Construction to provide electric vehicle
infrastructure and facilitate electric vehicle charging shall comply with Section 5.106.5.3.1 EV
capable spaces, Section 5.106.5.3.2 Electric vehicle charging stations (EVCS)-Power allocation
method and associated Table 5.106.5.3.6, and shall be provided in accordance with regulations in
the California Building Code and the California Electrical Code.
Exceptions: (Relocated from 2019 CALGreen Section 5.106.5.3.3 and edited)
--- Page 17 ---
~ 17 ~
1. On a case-by-case basis where the local enforcing agency has determined compliance with
this section is not feasible based upon one of the following conditions:
a. Where there is no local utility power supply.
b. Where the local utility is unable to supply adequate power.
c. Where there is evidence suitable to the local enforcement agency substantiating that
additional local utility infrastructure design requirements, directly related to the implementation
of Section 5.106.5.3, may adversely impact the construction cost of the project.
2. [ ← ] Areas of parking facilities served by parking lifts, including but not limited to,
automated mechanical-access open parking garages as defined in the California Building Code; or
parking facilities otherwise incapable of supporting electric vehicle charging.
3. In major alterations, where there is evidence substantiating that meeting the requirements
of this section present an unreasonable hardship or are technically infeasible, the Director may
upon request from the project sponsor consider an appeal to reduce the number of EV Spaces
required.
TABLE 5.106.5.3.1
TOTAL NUMBER OF
ACTUAL PARKING
SPACES
NUMBER OF
REQUIRED EV
CAPABLE SPACES
Other than Office and Retail
NUMBER OF REQUIRED
EVCS [ ← ] 2 3
Office and Retail
NUMBER OF
REQUIRED EVCS 2,3
1-41-9 2 01 2
10-25 5 23 4
26-50 11 46 8
51-75 19 510 14
76-100 26 913 20
101-150 38 1319 29
151-200 53 1827 40
201 and over [ ← ]30 percent of
total 1
[ ← ] 33 50 percent of EV
capable spaces 1
75 percent of EV
capable spaces1
1. Calculation for spaces shall be rounded up to the nearest whole number.
2. [ ← ]Each EVSE shall reduce the number of required EV capable spaces by the same number.
3. At least one Level 2 EVSE shall be provided.
Division 5.2
ENERGY EFFICIENCY
SECTION 5.201 – GENERAL
5.201 Add the following section:
5.201.1.1 Energy performance.
--- Page 18 ---
~ 18 ~
(a) All-electric buildings. A newly constructed all-electric non-residential building shall
demonstrate the Energy Budget for the proposed building is no greater than the Energy Budget
calculated for the Standard Design Building meeting California Title 24 Part 6 Energy Standards.
(b) Mixed-fuel buildings. A newly constructed mixed-fuel non-residential building shall
demonstrate the Energy Budget for the proposed building is no greater than 90% of the Title 24
Part 6 Energy Budget for the Standard Design Building meeting California Title 24 Part 6
Energy Standards.
Exception: Buildings consisting primarily of occupancy F, L, or H are exempt from this
Section.
5.201.1.2. Better roofs.
(a) California Title 24 Part 6 Energy Standards section 140.10 requires newly constructed
buildings of uses noted in Table 140.10-A to install photovoltaic (PV) energy systems, and
requires the minimum size of such systems to be not less than the smaller of PV direct current
size determined by Equation 140.10-A, or the total of all Solar Access Roof Area (SARA)
multiplied by 14 W/ft
2. Projects that constitute a Large Development Project or Small
Development Project under the Stormwater Management Ordinance (Public Works Code secs
147-147.6) may exclude from SARA any roof area where both:
(1) The area is occupied by living roof, meaning the area of media for growing plants, and
(2) The area occupied by living roof contributes to determination of compliance with the
Stormwater Management Ordinance, as documented by a Preliminary Stormwater Control Plan
or a Modified Compliance Application submitted to the San Francisco Public Utilities
Commission.
(b) In any final Stormwater Control Plan approved by the San Francisco Public Utilities
Commission, including where such approval may occur subsequent to addenda to a Site Permit
wherein compliance with California Title 24 Part 6 Energy Standards is documented, the
applicant shall ensure the area occupied by living roof contributing to determination of
compliance with the Stormwater Management Ordinance is no less than the square footage
approved for exclusion from SARA.
Chapter 7
INSTALLER AND SPECIAL INSPECTOR
QUALIFICATIONS
SECTION 701 – GENERAL
701.1 Add the following section:
701.1 These requirements apply to installers and Special inspectors with regards to the
requirements of this chapter.
SECTION 702 – QUALIFICATIONS
702.2 Modify certification number 2 as follows:
702.2 Special inspection. …
--- Page 19 ---
~ 19 ~
2. Certification by a statewide energy consulting or verification organization,[ ← ]
building performance contractors, [ ← ] home energy auditors, and ICC Certified CALGreen
Inspectors.
702.3 Add the following section:
702.3 Special inspection. The Director of the Department of Building Inspection may require
special inspection to verify compliance with this code or other laws that are enforced by the
agency. The special inspector shall be a qualified person who shall demonstrate competence, to
the satisfaction of the Director of the Department of Building Inspection, for inspection of the
particular type of construction or operation requiring special inspection. In addition, the special
inspector shall have a certification from a recognized state, national, or international association,
as determined by the Director of the Department of Building Inspection. The area of certification
shall be closely related to the primary job function, as determined by the local agency.
SECTION 703 – VERIFICATIONS
703.1 Modify the section as follows:
703.1 Documentation. Documentation used to show compliance with this code shall include but
is not limited to, construction documents, plans, specifications, builder or installer certification,
inspection reports, or other methods acceptable to the [ ← ] Director of the Department of
Building Inspection which demonstrate substantial conformance. When specific documentation
or special inspection is necessary to verify compliance, that method of compliance will be
specified in [ ← ] Administrative Bulletin 93.