{ "name": "RULE21", "description": "California Rule 21 volt-var curve", "type": "volt-var", "points": [ [0.95, 0.44], [0.99, 0.0], [1.01, 0.0], [1.05, -0.44] ], "units": { "voltage": "per-unit", "var": "per-unit (of rated kVA)" }, "notes": [ "California Rule 21 default volt-var curve", "Voltage range: 0.95 - 1.05 pu", "Reactive power range: -0.44 to +0.44 pu (44% of rated kVA)", "Positive values = absorb vars (inductive), negative = inject vars (capacitive)", "Tighter deadband than IEEE 1547 for better voltage regulation" ] }