hot_water_cylinderWork out the daily hot water demand of a dwelling and the size of cylinder a heat pump needs, using the formula in MIS 3005-D 3.5.2 and the BS 6700 guidance reproduced in MGD 007.
The demand is 45 litres a day for each of N, where N is the greater of the number of bedrooms plus one and the number of people actually living there. For a new build, where occupancy is unknown, the bedroom count is used.
The cylinder does not have to hold a whole day's demand, because it reheats as it empties. What it must cover is the largest draw-off before the heat pump catches up, which is why a larger heat pump needs a smaller cylinder: reheat time is volume times temperature rise, divided by 14.3 times the kW.
The result gives the BS 6700 minimum, a recommended size rounded to a volume cylinders are made in, and the reheat time. Note that cylinder volume is not the whole story: a heat pump cylinder needs a much larger coil than a boiler cylinder, because the water arrives cooler and there is less temperature difference to drive heat across the surface.
Method from MIS 3005-D. These calculators follow the published MCS methods, for understanding a system and checking a quotation. Anything that gets installed still needs a design and a site survey from a certified installer.
Input Schema
| Name | Required | Description | Default |
|---|---|---|---|
| bedrooms | Yes | Number of bedrooms in the property. Required. | |
| bathrooms | No | Number of bathrooms with a bath. Defaults to 1. | |
| occupants | No | Number of people who actually live there, if known. MIS 3005-D takes the greater of this and bedrooms plus one. Leave it out for a new build, where the occupancy is not yet known. | |
| storageTemp | No | Temperature the cylinder is stored at, in Celsius. Defaults to 55, which is a common heat pump setting. A weekly pasteurisation cycle above 60 is separate. | |
| coldWaterTemp | No | Incoming mains temperature in Celsius. Defaults to 10. | |
| heatPumpOutputKw | No | Heat output of the heat pump in kW when it is heating the cylinder. A larger heat pump reheats faster, so it needs less stored volume. Defaults to 6. |
Output Schema
| Name | Required | Description | Default |
|---|---|---|---|
| notes | Yes | ||
| method | Yes | ||
| bedrooms | Yes | ||
| bathrooms | Yes | ||
| occupants | No | ||
| references | Yes | ||
| storageTemp | Yes | ||
| coldWaterTemp | Yes | ||
| reheatMinutes | Yes | Roughly how long the heat pump takes to bring the whole cylinder up from cold, ignoring standing losses. | |
| occupancyBasis | Yes | Which of the two gave the larger figure. | |
| designOccupancy | Yes | N in the MIS 3005-D formula: the greater of bedrooms plus one and the known occupants. | |
| energyPerDayKwh | Yes | Heat needed each day to raise the daily demand from mains temperature to storage temperature. | |
| heatPumpOutputKw | Yes | ||
| dailyDemandLitres | Yes | Average daily hot water demand: 45 litres for each of N. | |
| minimumCylinderLitres | Yes | The BS 6700 minimum for this number of bathrooms and this heat pump output, before the allowance MGD 007 adds for extra bathing capacity. | |
| recommendedCylinderLitres | Yes | Cylinder volume from the BS 6700 guidance in MGD 007, given the number of baths and the heat pump output. |