Well Pressure Tank Size Calculator (Drawdown and Pump Run Time)
calc_well_pressure_tank_sizeWhat size well pressure tank you need: the drawdown for your pump's flow and minimum run time, the minimum total tank volume at your pressure-switch setting, and the smallest Amtrol Well-X-Trol model that delivers it. Formula: Required drawdown = pump gpm × run minutes. Acceptance factor = (cut-out − cut-in) ÷ (cut-out + 14.7). Minimum total tank volume = drawdown ÷ acceptance factor. A tank's drawdown = volume × acceptance factor (capped at its maximum acceptance factor). Run time = drawdown ÷ gpm.
Input Schema
| Name | Required | Description | Default |
|---|---|---|---|
| pump_gpm | No | Pump flow rate (gpm); default 10 | |
| tank_gal | No | Your tank's total volume (optional) (gal); default 0 | |
| cut_in_psi | No | Pressure switch cut-in; default 40; one of 20 = 20 psi, 30 = 30 psi, 40 = 40 psi, 50 = 50 psi, 60 = 60 psi | |
| cut_out_psi | No | Pressure switch cut-out; default 60; one of 40 = 40 psi, 50 = 50 psi, 60 = 60 psi, 70 = 70 psi, 80 = 80 psi | |
| run_minutes | No | Minimum pump run time; default 1; one of 1 = 1 minute (pumps up to 3/4 hp), 2 = 2 minutes (pumps over 3/4 hp) |