Conduit Fill Calculator (NEC Chapter 9, EMT and PVC)
calc_conduit_fillConduit fill for THHN/THWN-2 wires in EMT or Schedule 40 PVC: total wire area, percent fill against the NEC 53/31/40% limits, whether it fits, the smallest conduit that does, and the maximum number of same-size wires. Formula: Wire area = Σ count × Table 5 area (14 AWG 0.0097, 12 AWG 0.0133, 10 AWG 0.0211, 8 AWG 0.0366, 6 AWG 0.0507 sq in …). Allowed = Table 4 conduit area × 53% (1 wire), 31% (2) or 40% (3+). Same-size maximum = allowed ÷ wire area, rounded up only at 0.8 or more.
Input Schema
| Name | Required | Description | Default |
|---|---|---|---|
| size | No | Trade size; default 3/4 | |
| conduit | No | Conduit type; default emt | |
| count_1 | No | 1 AWG THHN wires; default 0 | |
| count_2 | No | 2 AWG THHN wires; default 0 | |
| count_3 | No | 3 AWG THHN wires; default 0 | |
| count_4 | No | 4 AWG THHN wires; default 0 | |
| count_6 | No | 6 AWG THHN wires; default 0 | |
| count_8 | No | 8 AWG THHN wires; default 0 | |
| count_10 | No | 10 AWG THHN wires; default 0 | |
| count_12 | No | 12 AWG THHN wires; default 0 | |
| count_14 | No | 14 AWG THHN wires; default 6 | |
| count_1_0 | No | 1/0 AWG THHN wires; default 0 |