Electrical Box Fill Calculator (NEC 314.16)
calc_box_fillRequired box volume under NEC 314.16 from your conductors, devices, clamps, fittings and grounds, checked against a standard metal box from Table 314.16(A) or your box's marked volume. Formula: Required volume = Σ(conductors × Table 314.16(B) allowance) + 1 allowance for clamps + 1 per fitting type + 2 per yoke + 1 for all grounds, each at the largest conductor size present. Allowances: 18 AWG 1.50, 16 AWG 1.75, 14 AWG 2.00, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00, 6 AWG 5.00 cu in.
Input Schema
| Name | Required | Description | Default |
|---|---|---|---|
| box | No | Box; default dev_3x2x2_5 | |
| yokes | No | Devices (yokes/straps: switch, receptacle); default 1 | |
| clamps | No | Internal cable clamps; default 0; one of 0 = None, 1 = Yes (one or more) | |
| count_6 | No | 6 AWG conductors; default 0 | |
| count_8 | No | 8 AWG conductors; default 0 | |
| grounds | No | Equipment grounding conductors; default 1; one of 1 = Yes (one or more), 0 = None | |
| count_10 | No | 10 AWG conductors; default 0 | |
| count_12 | No | 12 AWG conductors; default 0 | |
| count_14 | No | 14 AWG conductors; default 4 | |
| box_volume_cuin | No | Marked box volume (for "Other") (cu in); default 0 | |
| support_fittings | No | Luminaire stud/hickey types present; default 0 |