Overcurrent Time-Current Selectivity and Homopolar Coordinator

sodural_calc_selectivity_tcc
Read-onlyIdempotent

Evaluate inverse-time and definite-time overcurrent relay tripping curves, two-relay chronometric coordination margins across fault ranges in A and s, analytical Time Multiplier Setting (TMS) inversion, switchboard thermal withstand I2t checks, and zero-sequence capacitive 3Ic0 versus 51N/67N earth-fault selectivity. When to use: Use this tool when plotting time-current trip timings or verifying upstream-downstream relay grading margins; do NOT use for CT flux saturation audits, arc-flash PPE energy, or HV distance zones (call sodural_audit_protection_plan_physics, brain_calc_arc_flash_ct_comtrade, or sodural_calc_ansi21_87t_hv instead). Behavior: Stateless, read-only SI calculation with zero side effects (HTTP rate-limited at 120 req/min/IP); invalid numeric bounds or missing relay/feeder data in native modes raise JSON-RPC -32602. Defaults to mode="coordination_pair" (ikMin=1000 A, ikMax=20000 A, deltaTTarget=0.20 s, tms=1.0, lang="fr"). Returns: mode, singleCurve, coordinationPair, homopolarAnalysis, operatingTimeSec, solvedTms, calculationTrace, and legalNotice.

Tool call template

This tool declares no required parameters. Add optional parameters from the input schema as needed.

{
  "id": 1,
  "jsonrpc": "2.0",
  "method": "tools/call",
  "params": {
    "arguments": {},
    "name": "sodural_calc_selectivity_tcc"
  }
}

Input Schema

NameRequiredDescriptionDefault
ikNoSteady-state symmetrical short-circuit current Ik in kiloamperes (kA).
ipNoAsymmetrical peak short-circuit current Ip in kiloamperes (kA).
tdNoUS time-dial multiplier TD for inverse-time curves (defaults to 1.0).
tkNoShort-circuit fault clearing duration Tk in seconds (s) for switchboard withstand.
tmsNoDimensionless time multiplier setting TMS (defaults to 1.0).
ippkNoProspective initial symmetrical fault current Ik" in kiloamperes (kA).
langNoLocalization language code for labels and diagnostics ("fr" or "en", defaults to "fr").fr
modeNoAnalysis mode: single_curve, coordination_pair, homopolar, full, relay_time, special_curve, solve_tms, switchboard_withstand, or inverse-time curve lookup (defaults to "coordination_pair").coordination_pair
busIdNoMV switchboard busbar identifier evaluated during homopolar earth-fault grading.
ikMaxNoMaximum prospective three-phase fault current Ik3_max in A (defaults to 20000 A).
ikMinNoMinimum prospective two-phase fault current Ik2_min in A (defaults to 1000 A).
relayNoProtective relay curve family, pickup, TMS, definite delay, and instantaneous settings.
pickupNoRelay startup pickup threshold Is in primary amperes (A).
currentNoTest fault current in primary amperes (A) for TCC tripping evaluation.
feedersNoList of MV feeders evaluated for 3Ic0 capacitive return and 51N/67N earth-fault selectivity.
tkRatedNoSwitchboard rated short-time withstand duration in seconds (s).
curveCodeNoInverse time-current curve family identifier such as SI, VI, EI, LTI, DT, RI, or US_CO8.
ithRatedKaNoSwitchboard rated short-time thermal withstand current Ith in kiloamperes (kA).
targetTimeSNoTarget relay operating time t in seconds (s) for analytical solve_tms.
deltaTTargetNoTarget chronometric selectivity time margin delta-t in s (defaults to 0.20 s).
groundingInfoNoNeutral earthing scheme parameters (type, neutralLimitA, bpnAmp, and RCA angle).
upstreamRelayNoProtective relay curve family, pickup, TMS, definite delay, and instantaneous settings.
includeCatalogNoTrue to include the list of available time-current curve codes (defaults to false).
downstreamRelayNoProtective relay curve family, pickup, TMS, definite delay, and instantaneous settings.
voltageRatioDownToUpNoDownstream-to-upstream voltage transformation ratio for current referral (defaults to 1.0).

Output Schema

NameRequiredDescriptionDefault
modeNoExecuted time-current selectivity or homopolar calculation sub-mode.
solvedTmsNoAnalytically inverted Time Multiplier Setting TMS matching targetTimeS.
legalNoticeNoNon-substitution intellectual-property banner adapted to the caller permission tier.
singleCurveNoSingle-relay operating time evaluation at the requested current.
calculationTraceNoTransparent audit trail listing inputs, defaults, SI formulas, constants, and engineering assumptions.
coordinationPairNoTwo-relay coordination grading margin summary across [ikMin, ikMax].
operatingTimeSecNoEvaluated single-point tripping duration in seconds (s) for curve modes.
homopolarAnalysisNoZero-sequence capacitive sum and per-feeder 51N/67N selectivity summary.

Schema Changelog

Changes observed during successful MCP inspections.

  1. Changed65 schema fields changed
    • changedInput schema / properties / busId / description
      Previous value: -"Identifiant du jeu de barres pour l’analyse homopolaire."New value: +"MV switchboard busbar identifier evaluated during homopolar earth-fault grading."
    • changedInput schema / properties / current / description
      Previous value: -"Courant d’essai en ampères (A) pour calcul de temps TCC."New value: +"Test fault current in primary amperes (A) for TCC tripping evaluation."
    • addedInput schema / properties / current / maximum
      Added value: +500000
    • addedInput schema / properties / current / minimum
      Added value: +0.001
    • changedInput schema / properties / curveCode / description
      Previous value: -"Code courbe IEC/modèle analytique/Spéciale (SI, VI, EI, LTI, IEEE_MI, IEEE_VI, IEEE_EI, RI, IEC_STI, US_CO8, US_CO2_P20, US_CO2_P40)."New value: +"Inverse time-current curve family identifier such as SI, VI, EI, LTI, DT, RI, or US_CO8."
    • addedInput schema / properties / deltaTTarget / default
      Added value: +0.2
    • changedInput schema / properties / deltaTTarget / description
      Previous value: -"Marge chronométrique cible Δt (s), défaut 0.20."New value: +"Target chronometric selectivity time margin delta-t in s (defaults to 0.20 s)."
    • addedInput schema / properties / deltaTTarget / maximum
      Added value: +30
    • addedInput schema / properties / deltaTTarget / minimum
      Added value: +0.01
    • addedInput schema / properties / downstreamRelay / additionalProperties
      Added value: +true
    • changedInput schema / properties / downstreamRelay / description
      Previous value: -"Réglages relais aval."New value: +"Protective relay curve family, pickup, TMS, definite delay, and instantaneous settings."
    • addedInput schema / properties / downstreamRelay / properties
      Added value: +{
      +  "curveType": {
      +    "description": "Time-current curve identifier such as SI, VI, EI, LTI, DT, or RI.",
      +    "type": "string"
      +  },
      +  "delayS": {
      +    "description": "Definite-time trip delay in seconds (s).",
      +    "minimum": 0,
      +    "type": "number"
      +  },
      +  "instDelayS": {
      +    "description": "Instantaneous high-set intentional delay in seconds (s).",
      +    "minimum": 0,
      +    "type": "number"
      +  },
      +  "instPickupA": {
      +    "description": "Instantaneous high-set pickup threshold I>> in primary amperes (A).",
      +    "minimum": 0,
      +    "type": "number"
      +  },
      +  "pickupA": {
      +    "description": "Overcurrent pickup threshold Is in primary amperes (A).",
      +    "minimum": 0.1,
      +    "type": "number"
      +  },
      +  "tms": {
      +    "description": "Dimensionless time multiplier setting TMS for inverse-time curves.",
      +    "minimum": 0.01,
      +    "type": "number"
      +  }
      +}
    • changedInput schema / properties / feeders / description
      Previous value: -"Liste des départs pour analyse 3Ic0 / 51N / 67N."New value: +"List of MV feeders evaluated for 3Ic0 capacitive return and 51N/67N earth-fault selectivity."
    • addedInput schema / properties / feeders / items
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "MV feeder zero-sequence capacitive and earth-fault coordination entry.",
      +  "properties": {
      +    "id": {
      +      "description": "Unique MV feeder bay identifier (e.g. \"FEEDER_01\").",
      +      "type": "string"
      +    },
      +    "lengthM": {
      +      "description": "Feeder cable route length in meters (m) for 3Ic0 estimation.",
      +      "minimum": 0,
      +      "type": "number"
      +    },
      +    "threeI0MinAmp": {
      +      "description": "Minimum earth-fault current seen on the feeder in amperes (A).",
      +      "minimum": 0,
      +      "type": "number"
      +    },
      +    "threeIc0Amp": {
      +      "description": "Measured or precomputed zero-sequence capacitive current 3Ic0 in amperes (A).",
      +      "minimum": 0,
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedInput schema / properties / groundingInfo / additionalProperties
      Added value: +true
    • changedInput schema / properties / groundingInfo / description
      Previous value: -"Paramètres de mise à la terre du neutre (type, neutralLimitA, bpnAmp...)."New value: +"Neutral earthing scheme parameters (type, neutralLimitA, bpnAmp, and RCA angle)."
    • addedInput schema / properties / groundingInfo / properties
      Added value: +{
      +  "neutralLimitA": {
      +    "description": "Neutral resistor or reactor earth-fault limit current in amperes (A).",
      +    "minimum": 0,
      +    "type": "number"
      +  },
      +  "type": {
      +    "description": "Neutral earthing mode (\"bpn\", \"compensated\", \"isolated\", or \"solid\").",
      +    "type": "string"
      +  }
      +}
    • changedInput schema / properties / ik / description
      Previous value: -"Courant permanent Ik (kA) pour switchboard_withstand."New value: +"Steady-state symmetrical short-circuit current Ik in kiloamperes (kA)."
    • addedInput schema / properties / ik / minimum
      Added value: +0.01
    • addedInput schema / properties / ikMax / default
      Added value: +20000
    • changedInput schema / properties / ikMax / description
      Previous value: -"Courant court-circuit max Ik3_max (A), défaut 20000."New value: +"Maximum prospective three-phase fault current Ik3_max in A (defaults to 20000 A)."
    • addedInput schema / properties / ikMax / maximum
      Added value: +500000
    • addedInput schema / properties / ikMax / minimum
      Added value: +1
    • addedInput schema / properties / ikMin / default
      Added value: +1000
    • changedInput schema / properties / ikMin / description
      Previous value: -"Courant court-circuit min Ik2_min (A), défaut 1000."New value: +"Minimum prospective two-phase fault current Ik2_min in A (defaults to 1000 A)."
    • addedInput schema / properties / ikMin / maximum
      Added value: +500000
    • addedInput schema / properties / ikMin / minimum
      Added value: +1
    • addedInput schema / properties / includeCatalog / default
      Added value: +false
    • changedInput schema / properties / includeCatalog / description
      Previous value: -"Inclut la liste des courbes IEC/modèle analytique disponibles."New value: +"True to include the list of available time-current curve codes (defaults to false)."
    • changedInput schema / properties / ip / description
      Previous value: -"Courant de crête Ip (kA) pour switchboard_withstand."New value: +"Asymmetrical peak short-circuit current Ip in kiloamperes (kA)."
    • addedInput schema / properties / ip / minimum
      Added value: +0.01
    • changedInput schema / properties / ippk / description
      Previous value: -"Courant crête Ipk ou Ik\" (kA) pour switchboard_withstand."New value: +"Prospective initial symmetrical fault current Ik\" in kiloamperes (kA)."
    • addedInput schema / properties / ippk / minimum
      Added value: +0.01
    • changedInput schema / properties / ithRatedKa / description
      Previous value: -"Tenue thermique assignée tableau Ith (kA)."New value: +"Switchboard rated short-time thermal withstand current Ith in kiloamperes (kA)."
    • addedInput schema / properties / ithRatedKa / minimum
      Added value: +0.1
    • addedInput schema / properties / lang / default
      Added value: +"fr"
    • changedInput schema / properties / lang / description
      Previous value: -"Langue des diagnostics (fr|en)."New value: +"Localization language code for labels and diagnostics (\"fr\" or \"en\", defaults to \"fr\")."
    • addedInput schema / properties / mode / default
      Added value: +"coordination_pair"
    • changedInput schema / properties / mode / description
      Previous value: -"Mode d’analyse souhaité (défaut: coordination_pair si amont/aval fournis, sinon single_curve/homopolar)."New value: +"Analysis mode: single_curve, coordination_pair, homopolar, full, relay_time, special_curve, solve_tms, switchboard_withstand, or inverse-time curve lookup (defaults to \"coordination_pair\")."
    • removedInput schema / properties / mode / enum
      Removed value: -[
      -  "single_curve",
      -  "coordination_pair",
      -  "homopolar",
      -  "full",
      -  "relay_time",
      -  "iec_curve",
      -  "ieee_curve",
      -  "special_curve",
      -  "solve_tms",
      -  "switchboard_withstand"
      -]
    • changedInput schema / properties / pickup / description
      Previous value: -"Seuil de démarrage Is (A) pour modes Brain iec_curve / ieee_curve / special_curve / solve_tms / relay_time."New value: +"Relay startup pickup threshold Is in primary amperes (A)."
    • addedInput schema / properties / pickup / minimum
      Added value: +0.001
    • addedInput schema / properties / relay / additionalProperties
      Added value: +true
    • changedInput schema / properties / relay / description
      Previous value: -"Réglages relais unique (curveType, pickupA, tms, delayS, instPickupA, instDelayS...)."New value: +"Protective relay curve family, pickup, TMS, definite delay, and instantaneous settings."
    • addedInput schema / properties / relay / properties
      Added value: +{
      +  "curveType": {
      +    "description": "Time-current curve identifier such as SI, VI, EI, LTI, DT, or RI.",
      +    "type": "string"
      +  },
      +  "delayS": {
      +    "description": "Definite-time trip delay in seconds (s).",
      +    "minimum": 0,
      +    "type": "number"
      +  },
      +  "instDelayS": {
      +    "description": "Instantaneous high-set intentional delay in seconds (s).",
      +    "minimum": 0,
      +    "type": "number"
      +  },
      +  "instPickupA": {
      +    "description": "Instantaneous high-set pickup threshold I>> in primary amperes (A).",
      +    "minimum": 0,
      +    "type": "number"
      +  },
      +  "pickupA": {
      +    "description": "Overcurrent pickup threshold Is in primary amperes (A).",
      +    "minimum": 0.1,
      +    "type": "number"
      +  },
      +  "tms": {
      +    "description": "Dimensionless time multiplier setting TMS for inverse-time curves.",
      +    "minimum": 0.01,
      +    "type": "number"
      +  }
      +}
    • changedInput schema / properties / targetTimeS / description
      Previous value: -"Temps cible t (s) pour le solveur analytique solve_tms."New value: +"Target relay operating time t in seconds (s) for analytical solve_tms."
    • addedInput schema / properties / targetTimeS / minimum
      Added value: +0.001
    • addedInput schema / properties / td / default
      Added value: +1
    • changedInput schema / properties / td / description
      Previous value: -"Time Dial (modèle analytique)."New value: +"US time-dial multiplier TD for inverse-time curves (defaults to 1.0)."
    • addedInput schema / properties / td / minimum
      Added value: +0.01
    • changedInput schema / properties / tk / description
      Previous value: -"Durée court-circuit Tk (s) pour vérification tenue tableau."New value: +"Short-circuit fault clearing duration Tk in seconds (s) for switchboard withstand."
    • addedInput schema / properties / tk / minimum
      Added value: +0.01
    • changedInput schema / properties / tkRated / description
      Previous value: -"Durée assignée tenue tableau (s)."New value: +"Switchboard rated short-time withstand duration in seconds (s)."
    • addedInput schema / properties / tkRated / minimum
      Added value: +0.01
    • addedInput schema / properties / tms / default
      Added value: +1
    • changedInput schema / properties / tms / description
      Previous value: -"Time Multiplier Setting (IEC / RI)."New value: +"Dimensionless time multiplier setting TMS (defaults to 1.0)."
    • addedInput schema / properties / tms / minimum
      Added value: +0.01
    • addedInput schema / properties / upstreamRelay / additionalProperties
      Added value: +true
    • changedInput schema / properties / upstreamRelay / description
      Previous value: -"Réglages relais amont."New value: +"Protective relay curve family, pickup, TMS, definite delay, and instantaneous settings."
    • addedInput schema / properties / upstreamRelay / properties
      Added value: +{
      +  "curveType": {
      +    "description": "Time-current curve identifier such as SI, VI, EI, LTI, DT, or RI.",
      +    "type": "string"
      +  },
      +  "delayS": {
      +    "description": "Definite-time trip delay in seconds (s).",
      +    "minimum": 0,
      +    "type": "number"
      +  },
      +  "instDelayS": {
      +    "description": "Instantaneous high-set intentional delay in seconds (s).",
      +    "minimum": 0,
      +    "type": "number"
      +  },
      +  "instPickupA": {
      +    "description": "Instantaneous high-set pickup threshold I>> in primary amperes (A).",
      +    "minimum": 0,
      +    "type": "number"
      +  },
      +  "pickupA": {
      +    "description": "Overcurrent pickup threshold Is in primary amperes (A).",
      +    "minimum": 0.1,
      +    "type": "number"
      +  },
      +  "tms": {
      +    "description": "Dimensionless time multiplier setting TMS for inverse-time curves.",
      +    "minimum": 0.01,
      +    "type": "number"
      +  }
      +}
    • addedInput schema / properties / voltageRatioDownToUp / default
      Added value: +1
    • changedInput schema / properties / voltageRatioDownToUp / description
      Previous value: -"Rapport de tension aval/amont pour ramener le courant au primaire amont (défaut 1.0)."New value: +"Downstream-to-upstream voltage transformation ratio for current referral (defaults to 1.0)."
    • addedInput schema / properties / voltageRatioDownToUp / maximum
      Added value: +100
    • addedInput schema / properties / voltageRatioDownToUp / minimum
      Added value: +0.01
    • changedOutput schema / (root)
      Previous value: -nullNew value: +{
      +  "additionalProperties": true,
      +  "description": "Time-current selectivity, TMS solver, and homopolar coordination result with trace and legal notice.",
      +  "properties": {
      +    "calculationTrace": {
      +      "additionalProperties": true,
      +      "description": "Transparent audit trail listing inputs, defaults, SI formulas, constants, and engineering assumptions.",
      +      "properties": {
      +        "defaultsApplied": {
      +          "additionalProperties": true,
      +          "description": "Default SI parameters injected when optional inputs are omitted.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "engineeringAssumptions": {
      +          "description": "Boundary conditions assumed by the calculation engine.",
      +          "items": {
      +            "description": "Validity assumption constraining interpretation.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "formulasAndConstants": {
      +          "additionalProperties": true,
      +          "description": "Mathematical formulas and constants applied during evaluation.",
      +          "properties": {
      +            "constants": {
      +              "additionalProperties": true,
      +              "description": "Physical constants and conversion coefficients in SI units.",
      +              "properties": {},
      +              "type": "object"
      +            },
      +            "formulas": {
      +              "description": "Evaluated physical formulas.",
      +              "items": {
      +                "description": "Symbolic SI physics equation.",
      +                "type": "string"
      +              },
      +              "type": "array"
      +            }
      +          },
      +          "type": "object"
      +        },
      +        "inputsProvided": {
      +          "additionalProperties": true,
      +          "description": "Caller-supplied parameters normalized before execution.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "mode": {
      +          "description": "Executed physics calculation sub-mode for this call.",
      +          "type": "string"
      +        },
      +        "physicalPrinciples": {
      +          "description": "Ordered physical principles backing the solver.",
      +          "items": {
      +            "description": "Physical principle governing the analytical model.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "tool": {
      +          "description": "Canonical MCP tool identifier recorded by the calculation tracer.",
      +          "type": "string"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "coordinationPair": {
      +      "additionalProperties": true,
      +      "description": "Two-relay coordination grading margin summary across [ikMin, ikMax].",
      +      "properties": {
      +        "isCoordinated": {
      +          "description": "True when upstream/downstream pair satisfies deltaTTarget everywhere.",
      +          "type": "boolean"
      +        },
      +        "minDeltaT": {
      +          "description": "Minimum time grading margin across [ikMin, ikMax] in seconds (s).",
      +          "type": "number"
      +        },
      +        "minMarginS": {
      +          "description": "Minimum chronometric selectivity margin alias in seconds (s).",
      +          "type": "number"
      +        },
      +        "status": {
      +          "description": "Overall pair selectivity verdict (\"SELECTIVE\" or non-selective state).",
      +          "type": "string"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "homopolarAnalysis": {
      +      "additionalProperties": true,
      +      "description": "Zero-sequence capacitive sum and per-feeder 51N/67N selectivity summary.",
      +      "properties": {
      +        "busId": {
      +          "description": "Evaluated MV busbar identifier for earth-fault grading.",
      +          "type": "string"
      +        },
      +        "totalThreeIc0Amp": {
      +          "description": "Total busbar zero-sequence capacitive current 3Ic0 in amperes (A).",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "legalNotice": {
      +      "description": "Non-substitution intellectual-property banner adapted to the caller permission tier.",
      +      "type": "string"
      +    },
      +    "mode": {
      +      "description": "Executed time-current selectivity or homopolar calculation sub-mode.",
      +      "type": "string"
      +    },
      +    "operatingTimeSec": {
      +      "description": "Evaluated single-point tripping duration in seconds (s) for curve modes.",
      +      "type": "number"
      +    },
      +    "singleCurve": {
      +      "additionalProperties": true,
      +      "description": "Single-relay operating time evaluation at the requested current.",
      +      "properties": {
      +        "currentA": {
      +          "description": "Evaluated primary test current in amperes (A).",
      +          "type": "number"
      +        },
      +        "operatingTimeSec": {
      +          "description": "Computed relay trip operating time in seconds (s).",
      +          "type": "number"
      +        },
      +        "trips": {
      +          "description": "True when the test current exceeds pickup and initiates tripping.",
      +          "type": "boolean"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "solvedTms": {
      +      "description": "Analytically inverted Time Multiplier Setting TMS matching targetTimeS.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
  2. First observed

TDQS

A4.6/5.0
Behavior5/5

Does the description disclose side effects, auth requirements, rate limits, or destructive behavior?

Goes well past the annotations (which only supply readOnly/idempotent/non-destructive/closed-world) by declaring statelessness, a concrete HTTP rate limit of 120 req/min/IP, and the exact failure mode (JSON-RPC -32602 on invalid bounds or missing relay/feeder data in native modes). It also discloses the default mode and its default parameter values, which is real operational context an agent needs before calling.

Agents need to know what a tool does to the world before calling it. Descriptions should go beyond structured annotations to explain consequences.

Conciseness4/5

Is the description appropriately sized, front-loaded, and free of redundancy?

Well front-loaded and clearly segmented into purpose / when-to-use / behavior / returns, which suits a tool of this complexity. The opening sentence is dense enough to require re-reading, and the "Returns" enumeration largely restates the existing output schema.

Shorter descriptions cost fewer tokens and are easier for agents to parse. Every sentence should earn its place.

Completeness5/5

Given the tool's complexity, does the description cover enough for an agent to succeed on first attempt?

For a 25-parameter tool with nested objects, the definition still covers purpose, exclusions, side-effect profile, rate limits, error semantics, and defaults. Because a full output schema exists, the description does not need to explain return values in depth, and it does not leave any calling decision unresolved.

Complex tools with many parameters or behaviors need more documentation. Simple tools need less. This dimension scales expectations accordingly.

Parameters3/5

Does the description clarify parameter syntax, constraints, interactions, or defaults beyond what the schema provides?

Schema description coverage is 100% and all 25 parameters are individually documented, so the baseline is 3. The description adds the mode default (coordination_pair) and several default values, but it does not address the notable unit hazard between kA-valued `ik` and A-valued `ikMin`/`ikMax`, nor which parameters each mode requires.

Input schemas describe structure but not intent. Descriptions should explain non-obvious parameter relationships and valid value ranges.

Purpose5/5

Does the description clearly state what the tool does and how it differs from similar tools?

Opens with a specific verb ("Evaluate") and enumerates the concrete resources: inverse/definite-time overcurrent curves, two-relay chronometric margins, TMS inversion, I2t thermal withstand, and 3Ic0 vs 51N/67N selectivity. It also names the sibling tools it is not (arc-flash, CT saturation, ANSI21/87T), so an agent can discriminate it without opening any schema.

Agents choose between tools based on descriptions. A clear purpose with a specific verb and resource helps agents select the right tool.

Usage Guidelines5/5

Does the description explain when to use this tool, when not to, or what alternatives exist?

Contains an explicit "When to use" clause tied to TCC plotting and upstream-downstream grading, plus an explicit "do NOT use for" list with three named alternative tools for each excluded case. The selection rule is fully resolved in the description text.

Agents often have multiple tools that could apply. Explicit usage guidance like "use X instead of Y when Z" prevents misuse.

Try in Browser

Glama MCP Gateway

Add one secure layer between your agents and this server.

Resources