addedInput schema / additionalProperties
Added value: +true
changedInput schema / properties / cables / description
Previous value: -"List of MV cable feeders with length and capacitance"New value: +"Non-empty array of MV cable feeders (1..500); defaults to standard 20 kV substation preset if omitted."
addedInput schema / properties / cables / items / additionalProperties
Added value: +true
changedInput schema / properties / cables / items / description
Previous value: -"MV feeder cable length and zero-sequence capacitance entry."New value: +"MV cable feeder zero-sequence capacitive contribution entry."
addedInput schema / properties / cables / items / properties / capacitanceUfPerKm / default
Added value: +0.35
changedInput schema / properties / cables / items / properties / capacitanceUfPerKm / description
Previous value: -"Zero-sequence capacitance C0 in uF/km (default: 0.35)"New value: +"Zero-sequence phase-to-ground capacitance C0 in uF/km (defaults to 0.35 uF/km)."
addedInput schema / properties / cables / items / properties / capacitanceUfPerKm / maximum
Added value: +10
addedInput schema / properties / cables / items / properties / capacitanceUfPerKm / minimum
Added value: +0
addedInput schema / properties / cables / items / properties / conductorsPerPhase / default
Added value: +1
changedInput schema / properties / cables / items / properties / conductorsPerPhase / description
Previous value: -"Number of parallel cables per phase (default: 1)"New value: +"Number of parallel single-core conductors per phase (1..50, defaults to 1)."
addedInput schema / properties / cables / items / properties / conductorsPerPhase / maximum
Added value: +50
addedInput schema / properties / cables / items / properties / conductorsPerPhase / minimum
Added value: +1
addedInput schema / properties / cables / items / properties / enabled
Added value: +{
+ "default": true,
+ "description": "True if feeder is energized and contributes to 3Ic0 (defaults to true).",
+ "type": "boolean"
+}
changedInput schema / properties / cables / items / properties / id / description
Previous value: -"Unique MV feeder bay identifier (e.g. \"FEEDER_01\")."New value: +"Unique MV feeder circuit bay identifier (e.g. \"FEEDER_01\")."
changedInput schema / properties / cables / items / properties / lengthKm / description
Previous value: -"Cable length in km"New value: +"Cable route length in km (0..500 km, defaults to 1 km when lengthMeters omitted)."
addedInput schema / properties / cables / items / properties / lengthKm / maximum
Added value: +500
addedInput schema / properties / cables / items / properties / lengthKm / minimum
Added value: +0
changedInput schema / properties / cables / items / properties / lengthMeters / description
Previous value: -"Cable length in meters (alternative to lengthKm)"New value: +"Cable route length in meters (0..500000 m, overrides lengthKm when provided)."
addedInput schema / properties / cables / items / properties / lengthMeters / maximum
Added value: +500000
addedInput schema / properties / cables / items / properties / lengthMeters / minimum
Added value: +0
addedInput schema / properties / faultDurationSec / default
Added value: +5
changedInput schema / properties / faultDurationSec / description
Previous value: -"Thermal withstand fault duration in seconds (default: 5)"New value: +"Neutral reactor adiabatic thermal withstand duration in seconds (0.1..600 s, defaults to 5 s)."
addedInput schema / properties / faultDurationSec / maximum
Added value: +600
addedInput schema / properties / faultDurationSec / minimum
Added value: +0.1
addedInput schema / properties / faultLimitFactor / default
Added value: +2
changedInput schema / properties / faultLimitFactor / description
Previous value: -"Single-phase fault limit factor k_limit (default: 2.0)"New value: +"Single-phase earth-fault current limit multiplier k_limit (1..20, defaults to 2.0)."
addedInput schema / properties / faultLimitFactor / maximum
Added value: +20
addedInput schema / properties / faultLimitFactor / minimum
Added value: +1
addedInput schema / properties / freqHz / default
Added value: +50
changedInput schema / properties / freqHz / description
Previous value: -"Network frequency in Hz (50 or 60, default: 50)"New value: +"Nominal AC power network frequency in Hz (1..100 Hz, defaults to 50 Hz)."
addedInput schema / properties / freqHz / maximum
Added value: +100
addedInput schema / properties / freqHz / minimum
Added value: +1
addedInput schema / properties / pickupFactor / default
Added value: +2
changedInput schema / properties / pickupFactor / description
Previous value: -"51N pickup factor k_pickup (default: 2.0)"New value: +"Minimum 51N residual relay pickup factor relative to 3Ic0 (1..20, defaults to 2.0)."
addedInput schema / properties / pickupFactor / maximum
Added value: +20
addedInput schema / properties / pickupFactor / minimum
Added value: +1
addedInput schema / properties / safetyMarginPct / default
Added value: +20
changedInput schema / properties / safetyMarginPct / description
Previous value: -"Safety margin percentage (default: 20%)"New value: +"Capacitive network expansion safety margin percentage added to 3Ic0 (0..200%, defaults to 20%)."
addedInput schema / properties / safetyMarginPct / maximum
Added value: +200
addedInput schema / properties / safetyMarginPct / minimum
Added value: +0
addedInput schema / properties / voltageKv / default
Added value: +20.5
changedInput schema / properties / voltageKv / description
Previous value: -"Nominal network voltage Un in kV (e.g. 20 for 20 kV)"New value: +"Nominal MV busbar line-to-line voltage Un in kV (0.1..500 kV, defaults to 20.5 kV)."
addedInput schema / properties / voltageKv / maximum
Added value: +500
addedInput schema / properties / voltageKv / minimum
Added value: +0.1
changedInput schema / properties / voltageUnKv / description
Previous value: -"Alias of voltageKv (network phase-to-phase voltage in kV, default: 20.5)"New value: +"Alias of voltageKv specifying nominal phase-to-phase voltage Un in kV (0.1..500 kV)."
addedInput schema / properties / voltageUnKv / maximum
Added value: +500
addedInput schema / properties / voltageUnKv / minimum
Added value: +0.1
addedInput schema / properties / xrRatio / default
Added value: +0.4
changedInput schema / properties / xrRatio / description
Previous value: -"Neutral reactor X/R ratio (default: 0.4)"New value: +"Neutral earthing reactor inductive-to-resistive X/R ratio (0.01..100, defaults to 0.4)."
addedInput schema / properties / xrRatio / maximum
Added value: +100
addedInput schema / properties / xrRatio / minimum
Added value: +0.01
removedInput schema / required
Removed value: -[]
changedOutput schema / (root)
Previous value: -nullNew value: +{
+ "additionalProperties": true,
+ "description": "Neutral Earthing Reactor (BPN) sizing report with calculationTrace and legalNotice.",
+ "properties": {
+ "cables": {
+ "description": "Per-feeder zero-sequence capacitive return summary.",
+ "items": {
+ "additionalProperties": true,
+ "description": "Evaluated MV cable capacitive current breakdown.",
+ "properties": {
+ "contributionPercent": {
+ "description": "Percentage share of total busbar capacitive current.",
+ "type": "number"
+ },
+ "icA": {
+ "description": "Feeder zero-sequence capacitive charging current in A.",
+ "type": "number"
+ },
+ "id": {
+ "description": "MV cable feeder identifier.",
+ "type": "string"
+ }
+ },
+ "type": "object"
+ },
+ "type": "array"
+ },
+ "calculationTrace": {
+ "additionalProperties": true,
+ "description": "Transparent audit trail listing inputs, defaults, SI formulas, constants, and engineering assumptions.",
+ "properties": {
+ "defaultsApplied": {
+ "additionalProperties": true,
+ "description": "Default SI parameters injected when optional inputs are omitted.",
+ "properties": {},
+ "type": "object"
+ },
+ "engineeringAssumptions": {
+ "description": "Boundary conditions assumed by the calculation engine.",
+ "items": {
+ "description": "Validity assumption constraining interpretation.",
+ "type": "string"
+ },
+ "type": "array"
+ },
+ "formulasAndConstants": {
+ "additionalProperties": true,
+ "description": "Mathematical formulas and constants applied during evaluation.",
+ "properties": {
+ "constants": {
+ "additionalProperties": true,
+ "description": "Physical constants and conversion coefficients in SI units.",
+ "properties": {},
+ "type": "object"
+ },
+ "formulas": {
+ "description": "Evaluated physical formulas.",
+ "items": {
+ "description": "Symbolic SI physics equation.",
+ "type": "string"
+ },
+ "type": "array"
+ }
+ },
+ "type": "object"
+ },
+ "inputsProvided": {
+ "additionalProperties": true,
+ "description": "Caller-supplied parameters normalized before execution.",
+ "properties": {},
+ "type": "object"
+ },
+ "mode": {
+ "description": "Executed physics calculation sub-mode for this call.",
+ "type": "string"
+ },
+ "physicalPrinciples": {
+ "description": "Ordered physical principles backing the solver.",
+ "items": {
+ "description": "Physical principle governing the analytical model.",
+ "type": "string"
+ },
+ "type": "array"
+ },
+ "tool": {
+ "description": "Canonical MCP tool identifier recorded by the calculation tracer.",
+ "type": "string"
+ }
+ },
+ "type": "object"
+ },
+ "inputs": {
+ "additionalProperties": true,
+ "description": "Normalized BPN sizing input parameters.",
+ "properties": {
+ "freqHz": {
+ "description": "Evaluated network frequency in Hz.",
+ "type": "number"
+ },
+ "marginPercent": {
+ "description": "Applied capacitive expansion safety margin in %.",
+ "type": "number"
+ },
+ "voltageUnKv": {
+ "description": "Evaluated nominal line-to-line voltage Un in kV.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+ },
+ "insulationLevels": {
+ "additionalProperties": true,
+ "description": "Phase-to-earth insulation coordination withstand levels in kV.",
+ "properties": {
+ "um": {
+ "description": "Highest equipment voltage Um in kV.",
+ "type": "number"
+ },
+ "up": {
+ "description": "Rated lightning impulse withstand voltage in kV.",
+ "type": "number"
+ },
+ "uw": {
+ "description": "Short-duration power-frequency withstand voltage in kV.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+ },
+ "legalNotice": {
+ "description": "Non-substitution intellectual-property banner adapted to the caller permission tier.",
+ "type": "string"
+ },
+ "summary": {
+ "additionalProperties": true,
+ "description": "Neutral earthing impedance, current thresholds, and standard rating summary.",
+ "properties": {
+ "activeCablesCount": {
+ "description": "Count of energized feeders included in 3Ic0 sum.",
+ "type": "number"
+ },
+ "icSumA": {
+ "description": "Total unmargined zero-sequence capacitive current 3Ic0 in A.",
+ "type": "number"
+ },
+ "icTotalWithMarginA": {
+ "description": "Design capacitive current including expansion margin in A.",
+ "type": "number"
+ },
+ "pickupMinA": {
+ "description": "Minimum 51N residual protection pickup threshold in A.",
+ "type": "number"
+ },
+ "ratedFaultCurrentA": {
+ "description": "Selected neutral rated earth-fault current Ifln in A.",
+ "type": "number"
+ },
+ "recommendedZnOhm": {
+ "description": "Recommended neutral element impedance Zn = Z0NE/3 in ohms.",
+ "type": "number"
+ },
+ "rnOhms": {
+ "description": "Neutral earthing active resistance Rn in ohms.",
+ "type": "number"
+ },
+ "totalCablesCount": {
+ "description": "Total number of MV feeder records evaluated.",
+ "type": "number"
+ },
+ "totalCapacitiveCurrentA": {
+ "description": "Rounded aggregate zero-sequence capacitive current in A.",
+ "type": "number"
+ },
+ "xnMilliHenry": {
+ "description": "Neutral earthing inductance Ln in millihenries.",
+ "type": "number"
+ },
+ "z0neOhms": {
+ "description": "Required per-phase zero-sequence impedance Z0NE in ohms.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+ }
+ },
+ "type": "object"
+}