addedInput schema / properties / bus / additionalProperties
Added value: +true
changedInput schema / properties / bus / description
Previous value: -"Jeu de barres HTB : nominalKv, uMinKv, ik3MaxKa, ik1MinKa, xrRatio, freqHz."New value: +"HV busbar voltage, minimum operating voltage, fault levels, and source X/R ratio."
addedInput schema / properties / bus / properties
Added value: +{
+ "freqHz": {
+ "default": 50,
+ "description": "Nominal grid operating frequency in Hz (defaults to 50 Hz).",
+ "maximum": 100,
+ "minimum": 10,
+ "type": "number"
+ },
+ "ik1MinKa": {
+ "default": 3.5,
+ "description": "Minimum single-phase earth-fault current in kA (defaults to 3.5 kA).",
+ "minimum": 0.05,
+ "type": "number"
+ },
+ "ik3MaxKa": {
+ "default": 25,
+ "description": "Maximum three-phase short-circuit current at HV bus in kA (defaults to 25 kA).",
+ "minimum": 0.1,
+ "type": "number"
+ },
+ "nominalKv": {
+ "default": 225,
+ "description": "HV bus nominal phase-to-phase voltage in kV (defaults to 225 kV).",
+ "minimum": 1,
+ "type": "number"
+ },
+ "uMinKv": {
+ "description": "Minimum operating busbar voltage in kV for load encroachment checks.",
+ "minimum": 1,
+ "type": "number"
+ },
+ "xrRatio": {
+ "default": 15,
+ "description": "Equivalent upstream source fault X/R ratio (defaults to 15).",
+ "minimum": 0.5,
+ "type": "number"
+ }
+}
addedInput schema / properties / lang / default
Added value: +"fr"
changedInput schema / properties / lang / description
Previous value: -"Langue des libellés (fr | en)."New value: +"Localization language code for labels and diagnostics (\"fr\" or \"en\", defaults to \"fr\")."
addedInput schema / properties / line / additionalProperties
Added value: +true
changedInput schema / properties / line / description
Previous value: -"Ligne HTB : lengthKm, z1MagOhmPerKm, z1AngDeg, z0MagOhmPerKm, z0AngDeg, ctPrimaryA, ctSecondaryA, vtSecondaryPhaseV, arcLengthM."New value: +"Transmission line sequence impedances, CT/VT ratios, and fault arc length."
addedInput schema / properties / line / properties
Added value: +{
+ "arcLengthM": {
+ "default": 2.5,
+ "description": "Maximum phase-to-earth fault arc length in meters (defaults to 2.5 m).",
+ "minimum": 0,
+ "type": "number"
+ },
+ "ctPrimaryA": {
+ "default": 1000,
+ "description": "Line bay CT primary rating in amperes (defaults to 1000 A).",
+ "minimum": 10,
+ "type": "number"
+ },
+ "ctSecondaryA": {
+ "default": 1,
+ "description": "Line bay CT secondary rating in amperes (1 or 5 A, defaults to 1 A).",
+ "type": "number"
+ },
+ "lengthKm": {
+ "default": 35,
+ "description": "Protected transmission line length in km (defaults to 35 km).",
+ "minimum": 0.05,
+ "type": "number"
+ },
+ "vtSecondaryPhaseV": {
+ "default": 57.735,
+ "description": "Line VT secondary phase-to-neutral voltage in V (defaults to 57.735 V).",
+ "minimum": 10,
+ "type": "number"
+ },
+ "z0AngDeg": {
+ "default": 72,
+ "description": "Zero-sequence impedance phase angle in degrees (defaults to 72 deg).",
+ "type": "number"
+ },
+ "z0MagOhmPerKm": {
+ "default": 1.18,
+ "description": "Zero-sequence impedance magnitude |Z0| in ohm/km (defaults to 1.18).",
+ "minimum": 0.01,
+ "type": "number"
+ },
+ "z1AngDeg": {
+ "default": 78,
+ "description": "Positive-sequence impedance phase angle in degrees (defaults to 78 deg).",
+ "type": "number"
+ },
+ "z1MagOhmPerKm": {
+ "default": 0.39,
+ "description": "Positive-sequence impedance magnitude |Z1| in ohm/km (defaults to 0.39).",
+ "minimum": 0.01,
+ "type": "number"
+ }
+}
addedInput schema / properties / mode / default
Added value: +"standalone_hv_protection_settings"
changedInput schema / properties / mode / description
Previous value: -"Mode d’exécution HTB (défaut: standalone_hv_protection_settings)."New value: +"HV protection calculation mode selector (defaults to \"standalone_hv_protection_settings\")."
addedInput schema / properties / transformer / additionalProperties
Added value: +true
changedInput schema / properties / transformer / description
Previous value: -"Transformateur HTB/HTA (2W ou 3W si tertKv/tertMva/isThreeWinding fourni) : snMva, snOnanMva, hvKv, lvKv, tertKv, secMva, tertMva, isThreeWinding, vectorGroup, uccPct, maxPosTapPct, maxNegTapPct, hvCtPrimaryA, hvCtSecondaryA, lvCtPrimaryA, lvCtSecondaryA, tertCtPrimaryA, is1Pu, k1SlopePct, is2Pu, k2SlopePct, harmonic2fBlockPct, harmonic5fBlockPct."New value: +"Two- or three-winding power transformer nameplate, OLTC tap excursion, CT matching, and 87T slope settings."
addedInput schema / properties / transformer / properties
Added value: +{
+ "hvKv": {
+ "description": "HV winding rated line-to-line voltage in kV (defaults to bus nominalKv).",
+ "minimum": 1,
+ "type": "number"
+ },
+ "is1Pu": {
+ "default": 0.25,
+ "description": "Differential 87T basic pickup threshold Is1 in per-unit (defaults to 0.25 pu).",
+ "minimum": 0.05,
+ "type": "number"
+ },
+ "k1SlopePct": {
+ "default": 25,
+ "description": "Lower differential bias slope K1 in % (defaults to 25%).",
+ "minimum": 5,
+ "type": "number"
+ },
+ "k2SlopePct": {
+ "default": 60,
+ "description": "High-fault differential bias slope K2 in % (defaults to 60%).",
+ "minimum": 10,
+ "type": "number"
+ },
+ "lvKv": {
+ "default": 21,
+ "description": "Secondary MV winding rated line-to-line voltage in kV (defaults to 21 kV).",
+ "minimum": 0.4,
+ "type": "number"
+ },
+ "maxNegTapPct": {
+ "default": 12,
+ "description": "Maximum negative OLTC tap excursion in % (defaults to 12%).",
+ "maximum": 40,
+ "minimum": 0,
+ "type": "number"
+ },
+ "maxPosTapPct": {
+ "default": 12,
+ "description": "Maximum positive OLTC tap excursion in % (defaults to 12%).",
+ "maximum": 40,
+ "minimum": 0,
+ "type": "number"
+ },
+ "snMva": {
+ "default": 63,
+ "description": "Power transformer rated apparent power Sn in MVA (defaults to 63 MVA).",
+ "minimum": 0.5,
+ "type": "number"
+ },
+ "tertKv": {
+ "description": "Optional tertiary winding voltage in kV triggering three-winding 87T analysis.",
+ "minimum": 0.4,
+ "type": "number"
+ },
+ "uccPct": {
+ "default": 12.5,
+ "description": "Transformer short-circuit impedance percentage Ucc (defaults to 12.5%).",
+ "maximum": 50,
+ "minimum": 1,
+ "type": "number"
+ },
+ "vectorGroup": {
+ "default": "YNd11",
+ "description": "Winding phase-shift vector group string (defaults to \"YNd11\").",
+ "type": "string"
+ }
+}
changedOutput schema / (root)
Previous value: -nullNew value: +{
+ "additionalProperties": true,
+ "description": "Standalone HV ANSI 21 distance and ANSI 87T differential settings with trace and legal notice.",
+ "properties": {
+ "ansi21": {
+ "additionalProperties": true,
+ "description": "Distance ANSI 21 zone settings, kZ0 residual vector, arc resistance, and load blinder checks.",
+ "properties": {
+ "lineSummary": {
+ "additionalProperties": true,
+ "description": "Primary and secondary line impedance summary.",
+ "properties": {
+ "z1PrimOhm": {
+ "description": "Total line positive-sequence impedance in primary ohms.",
+ "type": "number"
+ },
+ "z1SecOhm": {
+ "description": "Total line positive-sequence impedance in secondary ohms.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+ },
+ "zones": {
+ "description": "Computed Z1, Z2, Z3, and Z4_REV impedance reaches.",
+ "items": {
+ "additionalProperties": true,
+ "description": "Distance protection zone reach and delay record.",
+ "properties": {},
+ "type": "object"
+ },
+ "type": "array"
+ }
+ },
+ "type": "object"
+ },
+ "ansi87t": {
+ "additionalProperties": true,
+ "description": "Differential 87T CT ratio matching, recommended settings, and OLTC stability summary.",
+ "properties": {
+ "isThreeWinding": {
+ "description": "True when tertiary parameters triggered three-winding 87T evaluation.",
+ "type": "boolean"
+ },
+ "oltcStability": {
+ "additionalProperties": true,
+ "description": "Extreme OLTC tap-changer through-fault stability verification.",
+ "properties": {
+ "allStableUnder085Criterion": {
+ "description": "True when 0.85 * Iop stays above worst OLTC tap spill current.",
+ "type": "boolean"
+ },
+ "worstTapMismatchPct": {
+ "description": "Worst-case OLTC tap ratio mismatch percentage (%).",
+ "type": "number"
+ }
+ },
+ "type": "object"
+ },
+ "recommendedSettings": {
+ "additionalProperties": true,
+ "description": "Recommended 87T pickup, high-set, slope, and harmonic restraint parameters.",
+ "properties": {
+ "idPickupPu": {
+ "description": "Recommended 87T differential pickup Id> in per-unit (pu).",
+ "type": "number"
+ },
+ "k1SlopePct": {
+ "description": "Recommended lower restraint slope K1 in percentage (%).",
+ "type": "number"
+ }
+ },
+ "type": "object"
+ }
+ },
+ "type": "object"
+ },
+ "busMetrics": {
+ "additionalProperties": true,
+ "description": "Busbar fault impedance, line impedance, and SIR classification metrics.",
+ "properties": {
+ "lineClassification": {
+ "description": "SIR line length classification (\"SHORT_HIGH_SIR\", \"MEDIUM_SIR\", or \"LONG_LOW_SIR\").",
+ "type": "string"
+ },
+ "nominalKv": {
+ "description": "Evaluated HV busbar nominal voltage in kV.",
+ "type": "number"
+ },
+ "sirRatio": {
+ "description": "Source Impedance Ratio Zs / Z1_line governing short/long line behavior.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+ },
+ "calculationTrace": {
+ "additionalProperties": true,
+ "description": "Transparent audit trail listing inputs, defaults, SI formulas, constants, and engineering assumptions.",
+ "properties": {
+ "defaultsApplied": {
+ "additionalProperties": true,
+ "description": "Default SI parameters injected when optional inputs are omitted.",
+ "properties": {},
+ "type": "object"
+ },
+ "engineeringAssumptions": {
+ "description": "Boundary conditions assumed by the calculation engine.",
+ "items": {
+ "description": "Validity assumption constraining interpretation.",
+ "type": "string"
+ },
+ "type": "array"
+ },
+ "formulasAndConstants": {
+ "additionalProperties": true,
+ "description": "Mathematical formulas and constants applied during evaluation.",
+ "properties": {
+ "constants": {
+ "additionalProperties": true,
+ "description": "Physical constants and conversion coefficients in SI units.",
+ "properties": {},
+ "type": "object"
+ },
+ "formulas": {
+ "description": "Evaluated physical formulas.",
+ "items": {
+ "description": "Symbolic SI physics equation.",
+ "type": "string"
+ },
+ "type": "array"
+ }
+ },
+ "type": "object"
+ },
+ "inputsProvided": {
+ "additionalProperties": true,
+ "description": "Caller-supplied parameters normalized before execution.",
+ "properties": {},
+ "type": "object"
+ },
+ "mode": {
+ "description": "Executed physics calculation sub-mode for this call.",
+ "type": "string"
+ },
+ "physicalPrinciples": {
+ "description": "Ordered physical principles backing the solver.",
+ "items": {
+ "description": "Physical principle governing the analytical model.",
+ "type": "string"
+ },
+ "type": "array"
+ },
+ "tool": {
+ "description": "Canonical MCP tool identifier recorded by the calculation tracer.",
+ "type": "string"
+ }
+ },
+ "type": "object"
+ },
+ "lang": {
+ "description": "Resolved localization language code (\"fr\" or \"en\").",
+ "type": "string"
+ },
+ "legalNotice": {
+ "description": "Non-substitution intellectual-property banner adapted to the caller permission tier.",
+ "type": "string"
+ },
+ "mode": {
+ "description": "Executed HV distance 21 / differential 87T calculation mode.",
+ "type": "string"
+ },
+ "si2sRequired": {
+ "description": "Always false confirming standalone calculation without external study database.",
+ "type": "boolean"
+ }
+ },
+ "type": "object"
+}