Transformer Loss, TCO, Acoustics & DGA Calculator

brain_calc_transformer_ecodesign_dga
Read-onlyIdempotent

Evaluate transformer no-load/load loss limits (P0, Pk), Peak Efficiency Index (PEI) at 75 C reference temperature, 30-year Total Cost of Ownership (TCO) NPV and CO2 emissions, Maekawa Fresnel acoustic barrier diffraction, altitude-corrected dielectric withstand levels, and Duval Triangle 1 dissolved-gas diagnostics. When to use: Use for transformer efficiency compliance, lifecycle TCO, boundary noise, dielectric levels, or oil gas ratios. Do not use for: Cold-load magnetizing inrush thresholds or transformer oil retention fire bunds -- call sodural_calc_transformer_inrush or brain_calc_fm_global_fire_smoke_gis instead. Behavior: Runs stateless, read-only thermal-economic and dielectric SI solvers with zero side effects (120 req/min/IP HTTP ceiling); invalid types raise JSON-RPC -32602, defaulting to mode="audit", lang="fr" on a 1000 kVA liquid preset. Returns: mode, overallStatus, ecodesign, tco30Years, acoustics, dielectric, dga, pei, calculationTrace, and legalNotice.

Tool call template

This tool declares no required parameters. Add optional parameters from the input schema as needed.

{
  "id": 1,
  "jsonrpc": "2.0",
  "method": "tools/call",
  "params": {
    "arguments": {},
    "name": "brain_calc_transformer_ecodesign_dga"
  }
}

Input Schema

NameRequiredDescriptionDefault
dgaNoDissolved Gas Analysis concentrations (ppm) for Duval Triangle fault classification.
p0WNoTop-level shortcut for no-load iron core loss P0 in watts (W).
pkWNoTop-level shortcut for full-load winding loss Pk in watts (W).
tcoNoTotal Cost of Ownership and CO2 lifecycle loss valuation inputs.
langNoResponse localization language code ("fr" for French or "en" for English, defaults to "fr").fr
modeNoTransformer design or dissolved-gas diagnostic mode (defaults to "audit").audit
snKvaNoTop-level shortcut for transformer rated power Sn in kVA.
presetIdNoOptional reference transformer study preset identifier (e.g. "STUDY_PACK_A_MV_LV_1000KVA_LIQUID").
acousticsNoTransformer acoustic emergence and Maekawa barrier attenuation inputs.
ecodesignNoStructured transformer no-load/load loss and PEI efficiency inputs.
dielectricNoAltitude-corrected dielectric withstand level verification inputs.

Output Schema

NameRequiredDescriptionDefault
dgaNoDuval Triangle 1 gas percentages and fault zone classification.
modeNoExecuted transformer design or dissolved-gas diagnostic mode.
acousticsNoDay/night boundary sound pressure emergence and Maekawa dB attenuation.
ecodesignNoPeak Efficiency Index (PEI), optimum load, and loss tier compliance.
tco30YearsNoNPV capitalized loss evaluation and carbon emissions over horizon.
legalNoticeNoInformational engineering compliance notice confirming SI physical scope and intellectual property rules.
overallStatusNoOverall engineering summary status ("PASS", "WARNING", or "FAIL").
calculationTraceNoTransparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.

Schema Changelog

Changes observed during successful MCP inspections.

  1. Changed124 schema fields changed
    • changedInput schema / properties / acoustics / properties / barrier / properties / barrierHeightM / description
      Previous value: -"Acoustic screen wall top height in meters."New value: +"Acoustic screen wall crest height above ground in meters (m)."
    • addedInput schema / properties / acoustics / properties / barrier / properties / barrierHeightM / minimum
      Added value: +0
    • changedInput schema / properties / acoustics / properties / barrier / properties / barrierToReceiverM / description
      Previous value: -"Horizontal distance from wall to receiver in meters."New value: +"Horizontal distance from barrier to receiver in meters (m)."
    • addedInput schema / properties / acoustics / properties / barrier / properties / barrierToReceiverM / minimum
      Added value: +0.1
    • changedInput schema / properties / acoustics / properties / barrier / properties / frequencyHz / description
      Previous value: -"Representative dominant 100/200/250 Hz magnetostriction tone in Hz."New value: +"Representative dominant magnetostriction tone frequency in Hz."
    • addedInput schema / properties / acoustics / properties / barrier / properties / frequencyHz / maximum
      Added value: +20000
    • addedInput schema / properties / acoustics / properties / barrier / properties / frequencyHz / minimum
      Added value: +16
    • changedInput schema / properties / acoustics / properties / barrier / properties / receiverHeightM / description
      Previous value: -"Boundary receiver microphone height in meters."New value: +"Boundary receiver microphone height above ground in meters (m)."
    • addedInput schema / properties / acoustics / properties / barrier / properties / receiverHeightM / minimum
      Added value: +0
    • changedInput schema / properties / acoustics / properties / barrier / properties / sourceHeightM / description
      Previous value: -"Acoustic source center height in meters."New value: +"Acoustic source center elevation above ground in meters (m)."
    • addedInput schema / properties / acoustics / properties / barrier / properties / sourceHeightM / minimum
      Added value: +0
    • changedInput schema / properties / acoustics / properties / barrier / properties / sourceToBarrierM / description
      Previous value: -"Horizontal distance from source to wall in meters."New value: +"Horizontal distance from transformer to barrier in meters (m)."
    • addedInput schema / properties / acoustics / properties / barrier / properties / sourceToBarrierM / minimum
      Added value: +0.1
    • changedInput schema / properties / acoustics / properties / directivityMode / description
      Previous value: -"Acoustic radiation factor (\"FREE_FIELD\", \"FACADE_WALL\")."New value: +"Acoustic radiation directivity factor (\"FREE_FIELD\" or \"FACADE_WALL\")."
    • changedInput schema / properties / acoustics / properties / distanceM / description
      Previous value: -"Acoustic propagation distance from transformer to property boundary in m."New value: +"Propagation distance from transformer center to boundary in meters (m)."
    • addedInput schema / properties / acoustics / properties / distanceM / minimum
      Added value: +0.1
    • addedInput schema / properties / acoustics / properties / residualDayDba / maximum
      Added value: +150
    • addedInput schema / properties / acoustics / properties / residualDayDba / minimum
      Added value: +0
    • addedInput schema / properties / acoustics / properties / residualNightDba / maximum
      Added value: +150
    • addedInput schema / properties / acoustics / properties / residualNightDba / minimum
      Added value: +0
    • addedInput schema / properties / acoustics / properties / sourceLwaDba / maximum
      Added value: +150
    • addedInput schema / properties / acoustics / properties / sourceLwaDba / minimum
      Added value: +10
    • changedInput schema / properties / acoustics / properties / transformerCount / description
      Previous value: -"Number of co-located operating transformers."New value: +"Number of co-located operating transformers on the site."
    • addedInput schema / properties / acoustics / properties / transformerCount / maximum
      Added value: +100
    • addedInput schema / properties / acoustics / properties / transformerCount / minimum
      Added value: +1
    • changedInput schema / properties / dga / properties / c2h2 / description
      Previous value: -"Dissolved acetylene C2H2 concentration in ppm."New value: +"Dissolved acetylene C2H2 concentration in oil in parts per million (ppm)."
    • addedInput schema / properties / dga / properties / c2h2 / minimum
      Added value: +0
    • changedInput schema / properties / dga / properties / c2h4 / description
      Previous value: -"Dissolved ethylene C2H4 concentration in ppm."New value: +"Dissolved ethylene C2H4 concentration in oil in parts per million (ppm)."
    • addedInput schema / properties / dga / properties / c2h4 / minimum
      Added value: +0
    • changedInput schema / properties / dga / properties / c2h6 / description
      Previous value: -"Dissolved ethane C2H6 concentration in ppm."New value: +"Dissolved ethane C2H6 concentration in oil in parts per million (ppm)."
    • addedInput schema / properties / dga / properties / c2h6 / minimum
      Added value: +0
    • changedInput schema / properties / dga / properties / ch4 / description
      Previous value: -"Dissolved methane CH4 concentration in ppm."New value: +"Dissolved methane CH4 concentration in oil in parts per million (ppm)."
    • addedInput schema / properties / dga / properties / ch4 / minimum
      Added value: +0
    • changedInput schema / properties / dga / properties / co / description
      Previous value: -"Dissolved carbon monoxide CO concentration in ppm."New value: +"Dissolved carbon monoxide CO concentration in oil in ppm."
    • addedInput schema / properties / dga / properties / co / minimum
      Added value: +0
    • changedInput schema / properties / dga / properties / co2 / description
      Previous value: -"Dissolved carbon dioxide CO2 concentration in ppm."New value: +"Dissolved carbon dioxide CO2 concentration in oil in ppm."
    • addedInput schema / properties / dga / properties / co2 / minimum
      Added value: +0
    • changedInput schema / properties / dga / properties / h2 / description
      Previous value: -"Dissolved hydrogen H2 concentration in ppm."New value: +"Dissolved hydrogen H2 concentration in oil in parts per million (ppm)."
    • addedInput schema / properties / dga / properties / h2 / minimum
      Added value: +0
    • changedInput schema / properties / dga / properties / hasCommunicatingOltc / description
      Previous value: -"True if the transformer includes a communicating diverter OLTC compartment."New value: +"True when transformer has a communicating diverter OLTC tank."
    • changedInput schema / properties / dielectric / properties / altitudeM / description
      Previous value: -"Installation site altitude above sea level in meters."New value: +"Installation site elevation above sea level in meters (m)."
    • addedInput schema / properties / dielectric / properties / altitudeM / maximum
      Added value: +6000
    • addedInput schema / properties / dielectric / properties / altitudeM / minimum
      Added value: +-100
    • addedInput schema / properties / dielectric / properties / specifiedAcsdKv / minimum
      Added value: +0.5
    • addedInput schema / properties / dielectric / properties / specifiedLiwlKv / minimum
      Added value: +1
    • changedInput schema / properties / dielectric / properties / umKv / description
      Previous value: -"Highest voltage for equipment Um in kV."New value: +"Highest voltage for equipment Um in kilovolts (kV)."
    • addedInput schema / properties / dielectric / properties / umKv / minimum
      Added value: +0.4
    • changedInput schema / properties / dielectric / properties / urKv / description
      Previous value: -"Nominal system operating voltage Ur in kV."New value: +"Nominal system operating voltage Ur in kilovolts (kV)."
    • addedInput schema / properties / dielectric / properties / urKv / minimum
      Added value: +0.4
    • changedInput schema / properties / ecodesign / properties / coolingType / description
      Previous value: -"Cooling & dielectric class (\"LIQUID\", \"DRY_CAST\")."New value: +"Transformer cooling and dielectric class (\"LIQUID\" or \"DRY_CAST\")."
    • changedInput schema / properties / ecodesign / properties / p0W / description
      Previous value: -"Guaranteed no-load core losses P0 in watts (W)."New value: +"Guaranteed no-load iron core loss P0 in watts (W)."
    • addedInput schema / properties / ecodesign / properties / p0W / minimum
      Added value: +0
    • changedInput schema / properties / ecodesign / properties / pkW / description
      Previous value: -"Guaranteed full-load winding copper/stray losses Pk in watts (W)."New value: +"Guaranteed full-load copper and stray loss Pk in watts (W)."
    • addedInput schema / properties / ecodesign / properties / pkW / minimum
      Added value: +0
    • changedInput schema / properties / ecodesign / properties / primaryUmKv / description
      Previous value: -"Primary winding highest system voltage Um in kV."New value: +"Primary winding highest system voltage Um in kilovolts (kV)."
    • addedInput schema / properties / ecodesign / properties / primaryUmKv / minimum
      Added value: +0.4
    • changedInput schema / properties / ecodesign / properties / secondaryUmKv / description
      Previous value: -"Secondary winding highest system voltage Um in kV."New value: +"Secondary winding highest system voltage Um in kilovolts (kV)."
    • addedInput schema / properties / ecodesign / properties / secondaryUmKv / minimum
      Added value: +0.1
    • changedInput schema / properties / ecodesign / properties / snKva / description
      Previous value: -"Transformer rated apparent power Sn in kVA."New value: +"Transformer rated apparent power Sn in kilovolt-amperes (kVA)."
    • addedInput schema / properties / ecodesign / properties / snKva / minimum
      Added value: +1
    • changedInput schema / properties / ecodesign / properties / tier / description
      Previous value: -"Efficiency tier target (\"TIER_1\", \"TIER_2\")."New value: +"Target loss efficiency compliance tier (\"TIER_1\" or \"TIER_2\")."
    • changedInput schema / properties / mode / description
      Previous value: -"Transformer design/diagnostic study mode (defaults to \"audit\")."New value: +"Transformer design or dissolved-gas diagnostic mode (defaults to \"audit\")."
    • changedInput schema / properties / p0W / description
      Previous value: -"Top-level shortcut for no-load loss P0 in watts."New value: +"Top-level shortcut for no-load iron core loss P0 in watts (W)."
    • addedInput schema / properties / p0W / minimum
      Added value: +0
    • changedInput schema / properties / pkW / description
      Previous value: -"Top-level shortcut for load loss Pk in watts."New value: +"Top-level shortcut for full-load winding loss Pk in watts (W)."
    • addedInput schema / properties / pkW / minimum
      Added value: +0
    • changedInput schema / properties / presetId / description
      Previous value: -"Optional reference transformer study preset ID (e.g. \"STUDY_PACK_A_MV_LV_1000KVA_LIQUID\")."New value: +"Optional reference transformer study preset identifier (e.g. \"STUDY_PACK_A_MV_LV_1000KVA_LIQUID\")."
    • addedInput schema / properties / snKva / minimum
      Added value: +1
    • changedInput schema / properties / tco / properties / capexEur / description
      Previous value: -"Initial transformer capital purchase cost in EUR."New value: +"Initial transformer capital purchase price in euros (EUR)."
    • addedInput schema / properties / tco / properties / capexEur / minimum
      Added value: +0
    • changedInput schema / properties / tco / properties / co2KgPerMwh / description
      Previous value: -"Grid carbon emission intensity in kg CO2 / MWh."New value: +"Grid carbon emission intensity factor in kg CO2 per MWh."
    • addedInput schema / properties / tco / properties / co2KgPerMwh / minimum
      Added value: +0
    • changedInput schema / properties / tco / properties / discountRate / description
      Previous value: -"Annual real discount rate (e.g. 0.04 for 4%)."New value: +"Annual real economic discount rate ratio (e.g. 0.04 for 4%)."
    • addedInput schema / properties / tco / properties / discountRate / maximum
      Added value: +1
    • addedInput schema / properties / tco / properties / discountRate / minimum
      Added value: +0
    • changedInput schema / properties / tco / properties / energyPriceEurPerMwh / description
      Previous value: -"Levelized electricity loss cost in EUR/MWh."New value: +"Levelized electrical loss valuation tariff in EUR/MWh."
    • addedInput schema / properties / tco / properties / energyPriceEurPerMwh / minimum
      Added value: +0
    • changedInput schema / properties / tco / properties / rmsLoadFactor / description
      Previous value: -"Equivalent annual RMS load factor between 0 and 1."New value: +"Equivalent annual RMS load factor ratio between 0 and 1."
    • addedInput schema / properties / tco / properties / rmsLoadFactor / maximum
      Added value: +1.5
    • addedInput schema / properties / tco / properties / rmsLoadFactor / minimum
      Added value: +0
    • changedInput schema / properties / tco / properties / years / description
      Previous value: -"Economic evaluation horizon in years (typically 30)."New value: +"Economic lifecycle evaluation horizon in years (typically 30)."
    • addedInput schema / properties / tco / properties / years / maximum
      Added value: +100
    • addedInput schema / properties / tco / properties / years / minimum
      Added value: +1
    • addedOutput schema / properties / acoustics / properties / combinedParticularLpaDba
      Added value: +{
      +  "description": "Combined receiver sound pressure level LpA in dB(A).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / acoustics / properties / overallCompliant
      Added value: +{
      +  "description": "True when daytime and nighttime emergence limits pass.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / acoustics / properties / requiredAdditionalAttenuationDb
      Added value: +{
      +  "description": "Additional attenuation needed for compliance in dB.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / acoustics / properties / totalSourceLwaDba
      Added value: +{
      +  "description": "Combined sound power level LWA across sources in dB(A).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / acoustics / properties / transformerCount
      Added value: +{
      +  "description": "Number of evaluated acoustic transformer sources.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / acoustics / properties / zerEmergence
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Daytime and nighttime property-boundary noise emergence budgets.",
      +  "properties": {
      +    "day": {
      +      "additionalProperties": true,
      +      "description": "Daytime boundary emergence evaluation summary.",
      +      "properties": {
      +        "compliantStrict": {
      +          "description": "True when daytime emergence meets strict boundary limit.",
      +          "type": "boolean"
      +        },
      +        "emergenceDb": {
      +          "description": "Daytime acoustic emergence above ambient residual in dB.",
      +          "type": "number"
      +        },
      +        "marginStrictDb": {
      +          "description": "Remaining daytime acoustic compliance margin in dB.",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "night": {
      +      "additionalProperties": true,
      +      "description": "Nighttime boundary emergence evaluation summary.",
      +      "properties": {
      +        "compliantStrict": {
      +          "description": "True when nighttime emergence meets strict boundary limit.",
      +          "type": "boolean"
      +        },
      +        "emergenceDb": {
      +          "description": "Nighttime acoustic emergence above ambient residual in dB.",
      +          "type": "number"
      +        },
      +        "marginStrictDb": {
      +          "description": "Remaining nighttime acoustic compliance margin in dB.",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / dga / properties / duvalSumPpm
      Added value: +{
      +  "description": "Sum of CH4, C2H4, and C2H2 concentrations in ppm.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / dga / properties / duvalZone
      Added value: +{
      +  "description": "Classified Duval Triangle 1 fault zone identifier.",
      +  "type": "string"
      +}
    • addedOutput schema / properties / dga / properties / effectiveDiagnosis
      Added value: +{
      +  "description": "Overall dissolved-gas diagnostic verdict label.",
      +  "type": "string"
      +}
    • addedOutput schema / properties / dga / properties / exceededGases
      Added value: +{
      +  "description": "Dissolved gases exceeding critical alarm limits.",
      +  "items": {
      +    "description": "Gas species exceeding critical alarm concentration limit.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / dga / properties / hasCommunicatingOltc
      Added value: +{
      +  "description": "True if OLTC diverter shares oil with main tank.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / dga / properties / hydrocarbonPlusH2Ppm
      Added value: +{
      +  "description": "Total dissolved combustible hydrocarbon plus H2 gas in ppm.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / dga / properties / pctC2h2
      Added value: +{
      +  "description": "Ternary Duval Triangle 1 acetylene C2H2 share in %.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / dga / properties / pctC2h4
      Added value: +{
      +  "description": "Ternary Duval Triangle 1 ethylene C2H4 share in %.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / dga / properties / pctCh4
      Added value: +{
      +  "description": "Ternary Duval Triangle 1 methane CH4 share in %.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / dga / properties / severity
      Added value: +{
      +  "description": "Diagnostic alarm severity (\"NORMAL\", \"WATCH\", or \"CRITICAL\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / dga / properties / summaryText
      Added value: +{
      +  "description": "Human-readable engineering summary of the oil gas sample.",
      +  "type": "string"
      +}
    • addedOutput schema / properties / dga / properties / tdcgWithCoPpm
      Added value: +{
      +  "description": "Total dissolved combustible gas including CO in ppm.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / dga / properties / watchGases
      Added value: +{
      +  "description": "Dissolved gases exceeding early watch thresholds.",
      +  "items": {
      +    "description": "Gas species exceeding early watch concentration limit.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • changedOutput schema / properties / ecodesign / description
      Previous value: -"Peak Efficiency Index (PEI), k_PEI optimum load, and loss compliance."New value: +"Peak Efficiency Index (PEI), optimum load, and loss tier compliance."
    • addedOutput schema / properties / ecodesign / properties / compliantTier2
      Added value: +{
      +  "description": "Boolean summary flag mirroring Tier 2 loss compliance.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / ecodesign / properties / lossLimits
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Measured vs Tier 1/2 maximum loss limits and margins in watts.",
      +  "properties": {
      +    "measured": {
      +      "additionalProperties": true,
      +      "description": "Evaluated transformer P0 and Pk loss values in watts.",
      +      "properties": {
      +        "p0W": {
      +          "description": "Evaluated no-load core loss P0 in watts (W).",
      +          "type": "number"
      +        },
      +        "pkW": {
      +          "description": "Evaluated full-load winding loss Pk in watts (W).",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "tier2Max": {
      +      "additionalProperties": true,
      +      "description": "Tier 2 ceiling limits for no-load and load losses.",
      +      "properties": {
      +        "p0W": {
      +          "description": "Maximum permissible Tier 2 no-load loss P0 in watts (W).",
      +          "type": "number"
      +        },
      +        "pkW": {
      +          "description": "Maximum permissible Tier 2 load loss Pk in watts (W).",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / ecodesign / properties / regime
      Added value: +{
      +  "description": "Applicable transformer loss compliance regime identifier.",
      +  "type": "string"
      +}
    • addedOutput schema / properties / ecodesign / properties / snKva
      Added value: +{
      +  "description": "Evaluated transformer rated apparent power Sn in kVA.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / ecodesign / properties / targetCompliant
      Added value: +{
      +  "description": "True when transformer satisfies requested targetTier.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / ecodesign / properties / targetTier
      Added value: +{
      +  "description": "Evaluated target efficiency tier (\"TIER_1\" or \"TIER_2\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / ecodesign / properties / tier1Compliant
      Added value: +{
      +  "description": "True when P0 and Pk meet Tier 1 maximum limits.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / ecodesign / properties / tier2Compliant
      Added value: +{
      +  "description": "True when P0 and Pk meet Tier 2 maximum limits.",
      +  "type": "boolean"
      +}
    • changedOutput schema / properties / mode / description
      Previous value: -"Executed transformer design or DGA diagnostic mode."New value: +"Executed transformer design or dissolved-gas diagnostic mode."
    • changedOutput schema / properties / overallStatus / description
      Previous value: -"Overall pass/warning/fail engineering summary status."New value: +"Overall engineering summary status (\"PASS\", \"WARNING\", or \"FAIL\")."
    • addedOutput schema / properties / tco30Years / properties / annualEnergyLossCostEur
      Added value: +{
      +  "description": "Annualized cost of electrical energy losses in EUR.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / tco30Years / properties / annualTotalMwh
      Added value: +{
      +  "description": "Combined annual no-load and load energy loss in MWh.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / tco30Years / properties / capexEur
      Added value: +{
      +  "description": "Initial transformer capital purchase cost in EUR.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / tco30Years / properties / discountRate
      Added value: +{
      +  "description": "Applied annual real discount rate ratio.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / tco30Years / properties / lifetimeCo2Tonnes
      Added value: +{
      +  "description": "Cumulative lifecycle CO2 emissions from losses in tonnes.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / tco30Years / properties / lossShareOfTcoPct
      Added value: +{
      +  "description": "Percentage share of total TCO attributable to energy losses.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / tco30Years / properties / npvLoadLossEur
      Added value: +{
      +  "description": "Net present value of capitalized load losses in EUR.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / tco30Years / properties / npvNoLoadLossEur
      Added value: +{
      +  "description": "Net present value of capitalized no-load losses in EUR.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / tco30Years / properties / npvTotalLossEur
      Added value: +{
      +  "description": "Combined net present value of all electrical losses in EUR.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / tco30Years / properties / tcoTotalEur
      Added value: +{
      +  "description": "Total 30-year lifecycle cost (CAPEX plus NPV losses) in EUR.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / tco30Years / properties / years
      Added value: +{
      +  "description": "Economic capitalization evaluation horizon in years.",
      +  "type": "number"
      +}
  2. Changed25 schema fields changed
    • addedInput schema / additionalProperties
      Added value: +true
    • addedInput schema / properties / acoustics / additionalProperties
      Added value: +true
    • addedInput schema / properties / acoustics / description
      Added value: +"Transformer acoustic emergence and Maekawa barrier attenuation inputs."
    • addedInput schema / properties / acoustics / properties
      Added value: +{
      +  "barrier": {
      +    "additionalProperties": true,
      +    "description": "Maekawa Fresnel acoustic diffraction screen geometry.",
      +    "properties": {
      +      "barrierHeightM": {
      +        "description": "Acoustic screen wall top height in meters.",
      +        "type": "number"
      +      },
      +      "barrierToReceiverM": {
      +        "description": "Horizontal distance from wall to receiver in meters.",
      +        "type": "number"
      +      },
      +      "frequencyHz": {
      +        "description": "Representative dominant 100/200/250 Hz magnetostriction tone in Hz.",
      +        "type": "number"
      +      },
      +      "receiverHeightM": {
      +        "description": "Boundary receiver microphone height in meters.",
      +        "type": "number"
      +      },
      +      "sourceHeightM": {
      +        "description": "Acoustic source center height in meters.",
      +        "type": "number"
      +      },
      +      "sourceToBarrierM": {
      +        "description": "Horizontal distance from source to wall in meters.",
      +        "type": "number"
      +      }
      +    },
      +    "type": "object"
      +  },
      +  "directivityMode": {
      +    "description": "Acoustic radiation factor (\"FREE_FIELD\", \"FACADE_WALL\").",
      +    "type": "string"
      +  },
      +  "distanceM": {
      +    "description": "Acoustic propagation distance from transformer to property boundary in m.",
      +    "type": "number"
      +  },
      +  "residualDayDba": {
      +    "description": "Ambient daytime background sound pressure level in dB(A).",
      +    "type": "number"
      +  },
      +  "residualNightDba": {
      +    "description": "Ambient nighttime background sound pressure level in dB(A).",
      +    "type": "number"
      +  },
      +  "sourceLwaDba": {
      +    "description": "Guaranteed transformer sound power level LWA in dB(A).",
      +    "type": "number"
      +  },
      +  "transformerCount": {
      +    "description": "Number of co-located operating transformers.",
      +    "type": "number"
      +  }
      +}
    • addedInput schema / properties / dga / additionalProperties
      Added value: +true
    • addedInput schema / properties / dga / description
      Added value: +"Dissolved Gas Analysis concentrations (ppm) for Duval Triangle fault classification."
    • addedInput schema / properties / dga / properties
      Added value: +{
      +  "c2h2": {
      +    "description": "Dissolved acetylene C2H2 concentration in ppm.",
      +    "type": "number"
      +  },
      +  "c2h4": {
      +    "description": "Dissolved ethylene C2H4 concentration in ppm.",
      +    "type": "number"
      +  },
      +  "c2h6": {
      +    "description": "Dissolved ethane C2H6 concentration in ppm.",
      +    "type": "number"
      +  },
      +  "ch4": {
      +    "description": "Dissolved methane CH4 concentration in ppm.",
      +    "type": "number"
      +  },
      +  "co": {
      +    "description": "Dissolved carbon monoxide CO concentration in ppm.",
      +    "type": "number"
      +  },
      +  "co2": {
      +    "description": "Dissolved carbon dioxide CO2 concentration in ppm.",
      +    "type": "number"
      +  },
      +  "h2": {
      +    "description": "Dissolved hydrogen H2 concentration in ppm.",
      +    "type": "number"
      +  },
      +  "hasCommunicatingOltc": {
      +    "description": "True if the transformer includes a communicating diverter OLTC compartment.",
      +    "type": "boolean"
      +  }
      +}
    • addedInput schema / properties / dielectric / additionalProperties
      Added value: +true
    • addedInput schema / properties / dielectric / description
      Added value: +"Altitude-corrected dielectric withstand level verification inputs."
    • addedInput schema / properties / dielectric / properties
      Added value: +{
      +  "altitudeM": {
      +    "description": "Installation site altitude above sea level in meters.",
      +    "type": "number"
      +  },
      +  "specifiedAcsdKv": {
      +    "description": "Specified short-duration power-frequency withstand voltage in kV RMS.",
      +    "type": "number"
      +  },
      +  "specifiedLiwlKv": {
      +    "description": "Specified lightning impulse withstand level LIWL in kV peak.",
      +    "type": "number"
      +  },
      +  "umKv": {
      +    "description": "Highest voltage for equipment Um in kV.",
      +    "type": "number"
      +  },
      +  "urKv": {
      +    "description": "Nominal system operating voltage Ur in kV.",
      +    "type": "number"
      +  }
      +}
    • addedInput schema / properties / ecodesign / additionalProperties
      Added value: +true
    • addedInput schema / properties / ecodesign / description
      Added value: +"Structured transformer no-load/load loss and PEI efficiency inputs."
    • addedInput schema / properties / ecodesign / properties
      Added value: +{
      +  "coolingType": {
      +    "description": "Cooling & dielectric class (\"LIQUID\", \"DRY_CAST\").",
      +    "type": "string"
      +  },
      +  "p0W": {
      +    "description": "Guaranteed no-load core losses P0 in watts (W).",
      +    "type": "number"
      +  },
      +  "pkW": {
      +    "description": "Guaranteed full-load winding copper/stray losses Pk in watts (W).",
      +    "type": "number"
      +  },
      +  "primaryUmKv": {
      +    "description": "Primary winding highest system voltage Um in kV.",
      +    "type": "number"
      +  },
      +  "secondaryUmKv": {
      +    "description": "Secondary winding highest system voltage Um in kV.",
      +    "type": "number"
      +  },
      +  "snKva": {
      +    "description": "Transformer rated apparent power Sn in kVA.",
      +    "type": "number"
      +  },
      +  "tier": {
      +    "description": "Efficiency tier target (\"TIER_1\", \"TIER_2\").",
      +    "type": "string"
      +  }
      +}
    • addedInput schema / properties / lang / default
      Added value: +"fr"
    • addedInput schema / properties / lang / description
      Added value: +"Response localization language code (\"fr\" for French or \"en\" for English, defaults to \"fr\")."
    • addedInput schema / properties / mode / default
      Added value: +"audit"
    • addedInput schema / properties / mode / description
      Added value: +"Transformer design/diagnostic study mode (defaults to \"audit\")."
    • addedInput schema / properties / p0W / description
      Added value: +"Top-level shortcut for no-load loss P0 in watts."
    • addedInput schema / properties / pkW / description
      Added value: +"Top-level shortcut for load loss Pk in watts."
    • addedInput schema / properties / presetId / description
      Added value: +"Optional reference transformer study preset ID (e.g. \"STUDY_PACK_A_MV_LV_1000KVA_LIQUID\")."
    • addedInput schema / properties / snKva / description
      Added value: +"Top-level shortcut for transformer rated power Sn in kVA."
    • addedInput schema / properties / tco / additionalProperties
      Added value: +true
    • addedInput schema / properties / tco / description
      Added value: +"Total Cost of Ownership and CO2 lifecycle loss valuation inputs."
    • addedInput schema / properties / tco / properties
      Added value: +{
      +  "capexEur": {
      +    "description": "Initial transformer capital purchase cost in EUR.",
      +    "type": "number"
      +  },
      +  "co2KgPerMwh": {
      +    "description": "Grid carbon emission intensity in kg CO2 / MWh.",
      +    "type": "number"
      +  },
      +  "discountRate": {
      +    "description": "Annual real discount rate (e.g. 0.04 for 4%).",
      +    "type": "number"
      +  },
      +  "energyPriceEurPerMwh": {
      +    "description": "Levelized electricity loss cost in EUR/MWh.",
      +    "type": "number"
      +  },
      +  "rmsLoadFactor": {
      +    "description": "Equivalent annual RMS load factor between 0 and 1.",
      +    "type": "number"
      +  },
      +  "years": {
      +    "description": "Economic evaluation horizon in years (typically 30).",
      +    "type": "number"
      +  }
      +}
    • changedOutput schema / (root)
      Previous value: -nullNew value: +{
      +  "additionalProperties": true,
      +  "description": "Transformer ecodesign, TCO, acoustics, and DGA analysis with calculationTrace and legalNotice.",
      +  "properties": {
      +    "acoustics": {
      +      "additionalProperties": true,
      +      "description": "Day/night boundary sound pressure emergence and Maekawa dB attenuation.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "calculationTrace": {
      +      "additionalProperties": true,
      +      "description": "Transparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.",
      +      "properties": {
      +        "defaultsApplied": {
      +          "additionalProperties": true,
      +          "description": "Default physical or engineering assumptions injected when optional inputs were omitted.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "engineeringAssumptions": {
      +          "description": "Explicit boundary assumptions required to interpret the numerical output.",
      +          "items": {
      +            "description": "Boundary condition or validity assumption for the calculation.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "formulasAndConstants": {
      +          "additionalProperties": true,
      +          "description": "Mathematical formulas and SI physical constants bound to this calculation mode.",
      +          "properties": {
      +            "constants": {
      +              "additionalProperties": true,
      +              "description": "Map of physical constants, resistivities, and design coefficients in SI units.",
      +              "properties": {},
      +              "type": "object"
      +            },
      +            "formulas": {
      +              "description": "Ordered list of physical equations evaluated by the calculation engine.",
      +              "items": {
      +                "description": "Symbolic engineering formula string used during evaluation.",
      +                "type": "string"
      +              },
      +              "type": "array"
      +            }
      +          },
      +          "type": "object"
      +        },
      +        "inputsProvided": {
      +          "additionalProperties": true,
      +          "description": "Non-empty normalized input parameters explicitly supplied by the caller.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "mode": {
      +          "description": "Normalized calculation mode executed for the current payload.",
      +          "type": "string"
      +        },
      +        "physicalPrinciples": {
      +          "description": "Key physical principles governing the computed result.",
      +          "items": {
      +            "description": "Concise statement of an underlying electrical or thermal principle.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "tool": {
      +          "description": "Resolved Brain tool identifier audited by the calculation tracer.",
      +          "type": "string"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "dga": {
      +      "additionalProperties": true,
      +      "description": "Duval Triangle 1 gas percentages and fault zone classification.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "ecodesign": {
      +      "additionalProperties": true,
      +      "description": "Peak Efficiency Index (PEI), k_PEI optimum load, and loss compliance.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "legalNotice": {
      +      "description": "Informational engineering compliance notice confirming SI physical scope and intellectual property rules.",
      +      "type": "string"
      +    },
      +    "mode": {
      +      "description": "Executed transformer design or DGA diagnostic mode.",
      +      "type": "string"
      +    },
      +    "overallStatus": {
      +      "description": "Overall pass/warning/fail engineering summary status.",
      +      "type": "string"
      +    },
      +    "tco30Years": {
      +      "additionalProperties": true,
      +      "description": "NPV capitalized loss evaluation and carbon emissions over horizon.",
      +      "properties": {},
      +      "type": "object"
      +    }
      +  },
      +  "type": "object"
      +}
  3. First observed

TDQS

A4.5/5.0
Behavior5/5

Does the description disclose side effects, auth requirements, rate limits, or destructive behavior?

Beyond the readOnly/idempotent/non-destructive annotations, it discloses statelessness, zero side effects, a 120 req/min/IP HTTP ceiling, JSON-RPC -32602 on invalid types, and the silent defaults (mode="audit", lang="fr", 1000 kVA liquid preset). Those defaults are operationally important because every parameter is optional, so a caller could otherwise invoke it with no idea what study was actually run.

Agents need to know what a tool does to the world before calling it. Descriptions should go beyond structured annotations to explain consequences.

Conciseness4/5

Is the description appropriately sized, front-loaded, and free of redundancy?

Structure is strong and front-loaded: capability sentence, then 'When to use', 'Do not use for', 'Behavior', 'Returns'. The opening sentence is an unusually long enumeration of seven computations, but each clause maps to a real mode, so nothing is genuinely wasted.

Shorter descriptions cost fewer tokens and are easier for agents to parse. Every sentence should earn its place.

Completeness4/5

Given the tool's complexity, does the description cover enough for an agent to succeed on first attempt?

For an 11-parameter, nested, multi-mode tool with an output schema, the description covers modes, defaults, error signaling, and rate limits. Since an output schema already exists, the enumerated return fields are a bonus rather than a necessity; the definition is essentially complete for correct invocation, with only mode-to-parameter mapping left implicit.

Complex tools with many parameters or behaviors need more documentation. Simple tools need less. This dimension scales expectations accordingly.

Parameters3/5

Does the description clarify parameter syntax, constraints, interactions, or defaults beyond what the schema provides?

Schema description coverage is 100% and the nested objects are thoroughly documented, so the schema carries the parameter burden. The description adds only marginal semantics beyond it: the 75 C PEI reference temperature and the default preset identity for presetId, which the schema does not state. Baseline 3 is appropriate.

Input schemas describe structure but not intent. Descriptions should explain non-obvious parameter relationships and valid value ranges.

Purpose5/5

Does the description clearly state what the tool does and how it differs from similar tools?

The description names specific computations and standards: no-load/load loss limits (P0, Pk), PEI at 75 C reference, 30-year TCO NPV and CO2, Maekawa Fresnel barrier diffraction, altitude-corrected dielectric withstand, and Duval Triangle 1 DGA. It also explicitly excludes cold-load inrush and fire bunds by naming the sibling tools that handle them, so an agent can route correctly without opening schemas.

Agents choose between tools based on descriptions. A clear purpose with a specific verb and resource helps agents select the right tool.

Usage Guidelines5/5

Does the description explain when to use this tool, when not to, or what alternatives exist?

It provides an explicit 'When to use' list (efficiency compliance, lifecycle TCO, boundary noise, dielectric levels, oil gas ratios) and a 'Do not use for' clause that redirects to sodural_calc_transformer_inrush and brain_calc_fm_global_fire_smoke_gis. Both the positive and negative selection conditions are stated outright.

Agents often have multiple tools that could apply. Explicit usage guidance like "use X instead of Y when Z" prevents misuse.