HV Substation (63-400 kV) Clearances & Grid Calculator

brain_calc_hv_substation_grid_compliance
Read-onlyIdempotent

Evaluate 63-400 kV high-voltage substation physics: altitude air-density scaling, phase/ground clearances (Dm, Dp, Dms), insulator USCD creepage, ZnO arrester margins, U/f/Q grid-code envelopes, Biot-Savart busbar dynamics, two-layer soil mesh, toroidal CT conduits, and 48/125 Vdc auxiliaries. When to use: Use for 63-400 kV HV substation clearances, grid-code audits, busbar forces, and soil mesh design; do NOT use for MV delivery bays (<= 33 kV), earth-split rf / adiabatic straps / breaker TRV / lightning risk, or concrete foundations -- call brain_calc_mv_delivery_physics, brain_calc_earthing_lightning_trv, or brain_calc_civil_concrete_foundation instead. Behavior: Runs stateless, read-only SI audits across five modes with zero side effects; non-object payloads raise JSON-RPC -32602, while omitted arguments default to mode="insulation_and_clearances" at 225 kV AIS. Returns: mode, compliant, status, voltageTier, withstandLevelsKv, clearancesM, coronaAndPollution, compactAndArrester, alerts, warnings, calculationTrace, and legalNotice.

Tool call template

This tool declares no required parameters. Add optional parameters from the input schema as needed.

{
  "id": 1,
  "jsonrpc": "2.0",
  "method": "tools/call",
  "params": {
    "arguments": {},
    "name": "brain_calc_hv_substation_grid_compliance"
  }
}

Input Schema

NameRequiredDescriptionDefault
uPuNoNormalized bus voltage in per-unit [0.5, 1.5].
langNoResponse localization language code ("fr" for French or "en" for English, defaults to "fr").fr
modeNoSubstation engineering domain mode or full multi-section audit.insulation_and_clearances
roleNoAlias for substation grid connection role ("GENERATION" or "CONSUMER").
sMvaNoReference network base power S in MVA for short-circuit or VT burden.
unKvNoNominal system line-to-line voltage Un in kV (e.g. 63, 90, 225, 400).
ik1KaNoSingle-phase-to-earth fault current Ik1 at the substation in kA.
ik3KaNoThree-phase symmetrical short-circuit current Ik3 in kA.
loadWNoStanding DC auxiliary load power in watts (W).
simMeNoSimulated mean error ME metric for EMT model validation.
spanMNoRigid tubular busbar support span length between post insulators in meters.
tauMsNoDC fault current decay time constant tau = L/R in milliseconds.
tkSecNoShort-circuit mechanical & adiabatic thermal fault duration tk in seconds.
z0OhmNoAbsolute zero-sequence source impedance Z0 in ohms.
bf50MsNoAlias for 50BF breaker failure backup timing in ms.
pMaxMwNoMaximum active power capacity Pmax in MW (>= 0).
simMaeNoSimulated mean absolute error MAE metric for EMT model validation.
simMxeNoSimulated maximum error MXE metric for EMT model validation.
testMeNoMeasured field-test ME threshold for model acceptance.
zTrOhmNoTransformer positive-sequence impedance magnitude in ohms.
pRaccMwNoSubscribed grid connection active power Pracc in MW (>= 0).
rfgTypeNoGenerator grid-code requirement class ("A", "B", "C", "D").
testMaeNoMeasured field-test MAE threshold for model acceptance.
testMxeNoMeasured field-test MXE threshold for model acceptance.
vtClassNoMetering/protection voltage transformer accuracy class (e.g. "0.2", "3P").
zHTROhmNoZero-sequence upstream transformer grounding reactance in ohms.
zone1MsNoDistance relay Zone 1 instantaneous trip time in ms.
zone2MsNoDistance relay Zone 2 backup trip time in ms.
zone3MsNoDistance relay Zone 3 remote backup trip time in ms.
bayCountNoNumber of connected HV switchgear bays (integer >= 1).
categoryNoPlant connection power category or regulatory tier code.
ik3MaxKaNoMaximum three-phase short-circuit current Ik3_max in kA.
presetIdNoOptional reference HV substation preset identifier pre-filling geometry and grid parameters.
rodCountNoTotal count of driven vertical ground rods connected to mesh.
siteRoleNoGrid connection role ("GENERATION", "INDUSTRIAL_CONSUMER", "STORAGE").
tubeOdMmNoRigid aluminum busbar tube outer diameter in mm.
z0OverZ1NoSystem effective earthing zero-to-positive impedance ratio Z0/Z1.
zMaltOhmNoCombined substation earthing grid impedance magnitude in ohms.
altitudeMNoSubstation elevation above sea level in meters [0, 4500] for air-density correction.
busSchemeNoBusbar topology configuration (e.g. "SINGLE_BUS", "DOUBLE_BUS", "BREAKER_AND_HALF").
coreDiaCmNoInsulator core shank diameter in cm for creepage profile factor.
dcSystemVNoAlias for DC auxiliary voltage bus rating in V (e.g. 48, 110, 125).
seasonKeyNoAmbient thermal season profile ("WINTER", "INTERMEDIATE", "SUMMER").
starRaysNNoNumber of counterpoise star-ray arms when star geometry is selected.
voltageKvNoAlias for nominal HV busbar voltage in kV (>= 1).
vtDropPctNoMeasured VT secondary voltage loop drop percentage (%).
gridAreaM2NoTotal buried earthing grid footprint area in m2.
gridWidthMNoEarthing mesh rectangular width in meters.
peakSurgeANoSimultaneous breaker trip/close solenoid peak surge current in amperes.
reservePctNoBattery capacity aging & temperature design reserve margin in %.
rodLengthMNoVertical earthing rod electrode length in meters.
rodRadiusMNoVertical earthing rod equivalent radius in meters.
shedDia1CmNoMajor insulator weather shed diameter in cm.
shedDia2CmNoMinor alternating insulator shed diameter in cm.
technologyNoSubstation switchgear technology ("AIS" air-insulated or "GIS" gas-insulated).
tubeWallMmNoRigid aluminum busbar tube wall thickness in mm.
auxVoltageVNoAuxiliary DC control battery bank nominal voltage in V (e.g. 48 or 125 Vdc).
batteryTechNoAuxiliary battery chemistry ("LEAD_VRLA", "NICD", "LFP").
climateZoneNoWind/ice mechanical loading climate zone code.
commDelayMsNoTeleprotection communication channel one-way latency in ms.
conductorIdNoBusbar or overhead phase conductor profile identifier.
deepRhoOhmMNoDeep soil stratum resistivity rho2 in ohm*m.
frequencyHzNoGrid frequency at PCC in Hz [45, 55] (nominal 50.0 Hz).
gridLengthMNoEarthing mesh rectangular length in meters.
providedDmMNoDesign phase-to-earth air clearance Dm in meters.
providedDpMNoDesign phase-to-phase air clearance Dp in meters.
qAbsorbMvarNoUnder-excited reactive power absorption capability in Mvar.
qInjectMvarNoOver-excited reactive power injection capability in Mvar.
rhoDeepOhmMNoAlias for deep soil stratum resistivity rho2 in ohm*m.
rodSpacingMNoMinimum spacing between adjacent vertical ground rods in meters.
soilRhoOhmMNoEquivalent uniform surface soil resistivity rho in ohm*m.
starRayLenMNoLength per counterpoise star-ray arm in meters.
zone5DipPctNoLow-voltage ride-through deep dip threshold (% residual U).
ambientTempCNoDesign ambient outdoor air temperature in deg C.
burialDepthMNoAlias for earthing grid burial depth h in meters.
buriedDepthMNoEarthing grid burial depth h in meters.
gravelThickMNoCrushed surface insulating gravel layer thickness in meters.
hasEarthWireNoTrue when overhead shield wires protect HV substation spans.
meshSpacingMNoBuried earthing grid mesh conductor spacing D in meters.
pOperatingMwNoMeasured steady-state active power at PCC in MW.
phasorFormatNoPhasor telemetry frame representation ("POLAR", "RECTANGULAR").
providedDmsMNoDesign safety working air clearance Dms in meters.
rhoUpperOhmMNoTwo-layer upper surface soil layer resistivity rho1 in ohm*m.
uOperatingKvNoActual steady-state operating voltage at PCC in kV.
xfmrPowerMvaNoMain HV/MV power transformer rated apparent power in MVA.
autonomyHoursNoRequired backup battery autonomy duration in hours.
breaker50BfMsNoBreaker-failure backup clearing time in ms.
conductorMmMmNoLegacy alias for conductor outer diameter in mm.
fenceSetbackMNoPerimeter security fence setback distance from live HV parts in meters.
generatorTechNoPrimary generation unit type ("SYNCHRONOUS", "IBR", "HYBRID").
gravelRhoOhmMNoCrushed surface gravel wet resistivity in ohm*m.
hasRemoteShedNoTrue when remote utility load/generation shedding teleprotection is active.
lineFeedCountNoNumber of connected overhead lines sharing earth return paths.
phaseSpacingMNoCenter-to-center busbar phase spacing in meters.
rocofHzPerSecNoRate of change of frequency ROCOF withstand in Hz/s.
cableLoopDropVNoDC battery distribution cable loop voltage drop in V.
connectionTypeNoEarthing conductor joint class ("EXOTHERMIC", "COMPRESSION", "BOLTED").
faultDurationSNoStep/touch voltage fault clearing duration in seconds.
hasCompiledDllNoTrue when black-box vendor EMT simulation model DLL is supplied.
igEarthFaultKaNoGrid-injected earth fault current Ig (post split factor) in kA.
overloadWindowNoThermal overload window duration tag (e.g. "15min", "20min").
pollutionClassNoSite environmental pollution severity ("LIGHT", "MEDIUM", "HEAVY", "VERY_HEAVY").
qOperatingMvarNoActual reactive power exchange at PCC in Mvar (+ inject, - absorb).
tanPhiMeasuredNoMeasured reactive-to-active power ratio Q/P at PCC.
faultClearingMsNoTotal primary protection + breaker fault clearing time in ms.
gisCableLengthMNoEnclosed GIS solid-dielectric cable run length in meters.
zone5DurationMsNoLow-voltage ride-through hold duration in ms.
commDelayModeledNoTrue if communication latency is explicitly included in EMT study.
conductorHeightMNoHeight of live HV busbars above ground level in meters.
earthingGeometryNoEarthing electrode layout ("MESH", "ROD_BANK", "STAR").
highKeraunicZoneNoTrue for sites located in high lightning flash density zones.
meshConductorMm2NoBuried copper earthing grid conductor cross-section in mm2.
nominalVoltageKvNoSecondary alias for nominal system voltage Un in kV (>= 1).
overheadZLineOhmNoZero-sequence overhead earth-wire impedance per circuit in ohms.
overloadCurrentANoEmergency short-term overload busbar current in amperes.
protectionSchemeNoBusbar thermal/fault clearance scheme identifier.
arresterDistanceMNoAlias for electrical separation distance from surge arrester in meters.
isPowerElectronicNoTrue if connected via power-electronic inverter interface (IBR/HVDC).
operatingCurrentANoNormal continuous busbar operating current in amperes.
permanentCurrentANoContinuous standing DC control load current in amperes.
gisBlindBusLengthMNoEnclosed GIS shielded busduct segment length in meters.
insulatorMeanDiaCmNoMean porcelain/composite post insulator diameter in cm.
providedCreepageMmNoInstalled insulator surface creepage distance in mm.
conductorDiameterMmNoTubular or stranded HV conductor outer diameter in mm.
hasGenerationGe12MwNoTrue for sites embedding local generation >= 12 MW.
hasZeroSeqNeutralTrNoTrue when step-up/interconnecting transformer provides zero-sequence neutral path.
insulatorDiameterMmNoInsulator core/mean diameter in mm.
guardWireReductionKrNoOverhead earth-wire current return reduction factor kr in [0, 1].
isCriticalSubstationNoTrue for critical grid node with stricter breaker failure budget.
distanceFromArresterMNoElectrical separation distance from ZnO surge arrester to protected winding in meters.
reducedInsulationXfmrNoTrue if the power transformer specifies graded/reduced neutral-end insulation.
steelTubeAroundTcToreNoTrue if a ferromagnetic steel sleeve passes through the toroidal zero-sequence CT.
applyVoltageEquivalenceNoTrue to apply equivalent GIS-to-AIS insulation reduction factors where valid.
hasSpecificDielectricStudyNoTrue when transient switching/lightning simulation supports reduced margin.
transformerCableInToroidalCtNoBoolean flag or conduit material tag ("steel_s235" vs "fibro_100") around toroidal CT.

Output Schema

NameRequiredDescriptionDefault
modeNoExecuted HV substation calculation mode.
alertsNoBlocking engineering alerts requiring design change.
statusNoHuman-readable verdict status string.
warningsNoAdvisory non-blocking engineering observations.
compliantNoOverall physical compliance verdict for requested HV domain(s).
clearancesMNoComputed minimum phase-to-earth Dm, phase-to-phase Dp, and safety clearances in m.
legalNoticeNoInformational engineering compliance notice confirming SI physical scope and intellectual property rules.
voltageTierNoResolved system voltage tier, Um ceiling, and technology class.
calculationTraceNoTransparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.
withstandLevelsKvNoAltitude-adjusted LIWL, SIWL, and short-duration AC withstand levels in kV.
altitudeCorrectionNoAltitude air-density dielectric and linear air-clearance scaling factors.
compactAndArresterNoZnO surge arrester protective distance margin and BIL reduction checks.
coronaAndPollutionNoSurface gradient corona inception and insulator USCD creepage margin.

Schema Changelog

Changes observed during successful MCP inspections.

  1. Changed141 schema fields changed
    • changedInput schema / properties / altitudeM / description
      Previous value: -"Substation elevation above sea level in meters (m) for air-density correction."New value: +"Substation elevation above sea level in meters [0, 4500] for air-density correction."
    • addedInput schema / properties / altitudeM / maximum
      Added value: +4500
    • addedInput schema / properties / altitudeM / minimum
      Added value: +0
    • addedInput schema / properties / arresterDistanceM / minimum
      Added value: +0
    • addedInput schema / properties / autonomyHours / minimum
      Added value: +0.1
    • addedInput schema / properties / auxVoltageV / minimum
      Added value: +12
    • addedInput schema / properties / bf50Ms / minimum
      Added value: +0
    • addedInput schema / properties / breaker50BfMs / minimum
      Added value: +0
    • addedInput schema / properties / burialDepthM / minimum
      Added value: +0.1
    • addedInput schema / properties / buriedDepthM / minimum
      Added value: +0.1
    • addedInput schema / properties / cableLoopDropV / minimum
      Added value: +0
    • addedInput schema / properties / commDelayMs / minimum
      Added value: +0
    • addedInput schema / properties / conductorDiameterMm / minimum
      Added value: +1
    • addedInput schema / properties / conductorHeightM / minimum
      Added value: +1
    • addedInput schema / properties / conductorMmMm / minimum
      Added value: +1
    • addedInput schema / properties / coreDiaCm / minimum
      Added value: +1
    • addedInput schema / properties / dcSystemV / minimum
      Added value: +12
    • addedInput schema / properties / deepRhoOhmM / minimum
      Added value: +1
    • addedInput schema / properties / distanceFromArresterM / minimum
      Added value: +0
    • addedInput schema / properties / faultClearingMs / minimum
      Added value: +0
    • addedInput schema / properties / faultDurationS / minimum
      Added value: +0.01
    • addedInput schema / properties / fenceSetbackM / minimum
      Added value: +0
    • changedInput schema / properties / frequencyHz / description
      Previous value: -"Grid frequency at PCC in Hz (nominal 50.0 Hz)."New value: +"Grid frequency at PCC in Hz [45, 55] (nominal 50.0 Hz)."
    • addedInput schema / properties / frequencyHz / maximum
      Added value: +55
    • addedInput schema / properties / frequencyHz / minimum
      Added value: +45
    • addedInput schema / properties / gisBlindBusLengthM / minimum
      Added value: +0
    • addedInput schema / properties / gisCableLengthM / minimum
      Added value: +0
    • addedInput schema / properties / gravelRhoOhmM / minimum
      Added value: +1
    • addedInput schema / properties / gravelThickM / minimum
      Added value: +0
    • addedInput schema / properties / gridAreaM2 / minimum
      Added value: +1
    • addedInput schema / properties / gridLengthM / minimum
      Added value: +1
    • addedInput schema / properties / gridWidthM / minimum
      Added value: +1
    • changedInput schema / properties / guardWireReductionKr / description
      Previous value: -"Overhead earth-wire current return reduction factor kr (0..1)."New value: +"Overhead earth-wire current return reduction factor kr in [0, 1]."
    • addedInput schema / properties / guardWireReductionKr / maximum
      Added value: +1
    • addedInput schema / properties / guardWireReductionKr / minimum
      Added value: +0
    • addedInput schema / properties / igEarthFaultKa / minimum
      Added value: +0
    • addedInput schema / properties / ik1Ka / minimum
      Added value: +0
    • addedInput schema / properties / ik3Ka / minimum
      Added value: +0
    • addedInput schema / properties / ik3MaxKa / minimum
      Added value: +0
    • addedInput schema / properties / insulatorDiameterMm / minimum
      Added value: +1
    • addedInput schema / properties / insulatorMeanDiaCm / minimum
      Added value: +1
    • addedInput schema / properties / loadW / minimum
      Added value: +0
    • addedInput schema / properties / meshConductorMm2 / minimum
      Added value: +1
    • addedInput schema / properties / meshSpacingM / minimum
      Added value: +0.5
    • changedInput schema / properties / nominalVoltageKv / description
      Previous value: -"Secondary alias for nominal system voltage Un in kV."New value: +"Secondary alias for nominal system voltage Un in kV (>= 1)."
    • addedInput schema / properties / nominalVoltageKv / minimum
      Added value: +1
    • addedInput schema / properties / operatingCurrentA / minimum
      Added value: +0
    • addedInput schema / properties / overheadZLineOhm / minimum
      Added value: +0
    • addedInput schema / properties / overloadCurrentA / minimum
      Added value: +0
    • changedInput schema / properties / pMaxMw / description
      Previous value: -"Maximum active power capacity Pmax in MW."New value: +"Maximum active power capacity Pmax in MW (>= 0)."
    • addedInput schema / properties / pMaxMw / minimum
      Added value: +0
    • changedInput schema / properties / pRaccMw / description
      Previous value: -"Subscribed grid connection active power Pracc in MW."New value: +"Subscribed grid connection active power Pracc in MW (>= 0)."
    • addedInput schema / properties / pRaccMw / minimum
      Added value: +0
    • addedInput schema / properties / peakSurgeA / minimum
      Added value: +0
    • addedInput schema / properties / permanentCurrentA / minimum
      Added value: +0
    • addedInput schema / properties / phaseSpacingM / minimum
      Added value: +0.1
    • addedInput schema / properties / providedCreepageMm / minimum
      Added value: +0
    • addedInput schema / properties / providedDmM / minimum
      Added value: +0
    • addedInput schema / properties / providedDmsM / minimum
      Added value: +0
    • addedInput schema / properties / providedDpM / minimum
      Added value: +0
    • addedInput schema / properties / reservePct / minimum
      Added value: +0
    • addedInput schema / properties / rhoDeepOhmM / minimum
      Added value: +1
    • addedInput schema / properties / rhoUpperOhmM / minimum
      Added value: +1
    • addedInput schema / properties / rodLengthM / minimum
      Added value: +0.5
    • addedInput schema / properties / rodRadiusM / minimum
      Added value: +0.001
    • addedInput schema / properties / rodSpacingM / minimum
      Added value: +0.5
    • changedInput schema / properties / role / description
      Previous value: -"Alias for substation grid connection role."New value: +"Alias for substation grid connection role (\"GENERATION\" or \"CONSUMER\")."
    • addedInput schema / properties / sMva / minimum
      Added value: +0.1
    • addedInput schema / properties / shedDia1Cm / minimum
      Added value: +1
    • addedInput schema / properties / shedDia2Cm / minimum
      Added value: +1
    • addedInput schema / properties / soilRhoOhmM / minimum
      Added value: +1
    • addedInput schema / properties / spanM / minimum
      Added value: +0.1
    • addedInput schema / properties / starRayLenM / minimum
      Added value: +0
    • addedInput schema / properties / starRaysN / minimum
      Added value: +0
    • addedInput schema / properties / tauMs / minimum
      Added value: +0
    • addedInput schema / properties / tkSec / minimum
      Added value: +0.01
    • addedInput schema / properties / tubeOdMm / minimum
      Added value: +1
    • addedInput schema / properties / tubeWallMm / minimum
      Added value: +0.5
    • addedInput schema / properties / uOperatingKv / minimum
      Added value: +1
    • changedInput schema / properties / uPu / description
      Previous value: -"Normalized bus voltage in per-unit (p.u.)."New value: +"Normalized bus voltage in per-unit [0.5, 1.5]."
    • addedInput schema / properties / uPu / maximum
      Added value: +1.5
    • addedInput schema / properties / uPu / minimum
      Added value: +0.5
    • addedInput schema / properties / unKv / minimum
      Added value: +1
    • changedInput schema / properties / voltageKv / description
      Previous value: -"Alias for nominal HV busbar voltage in kV."New value: +"Alias for nominal HV busbar voltage in kV (>= 1)."
    • addedInput schema / properties / voltageKv / minimum
      Added value: +1
    • addedInput schema / properties / vtDropPct / minimum
      Added value: +0
    • changedInput schema / properties / xfmrPowerMva / description
      Previous value: -"Main HV/MV power transformer rated MVA."New value: +"Main HV/MV power transformer rated apparent power in MVA."
    • addedInput schema / properties / xfmrPowerMva / minimum
      Added value: +0.1
    • addedInput schema / properties / zone1Ms / minimum
      Added value: +0
    • addedInput schema / properties / zone2Ms / minimum
      Added value: +0
    • addedInput schema / properties / zone3Ms / minimum
      Added value: +0
    • addedInput schema / properties / zone5DipPct / maximum
      Added value: +100
    • addedInput schema / properties / zone5DipPct / minimum
      Added value: +0
    • addedInput schema / properties / zone5DurationMs / minimum
      Added value: +0
    • addedOutput schema / properties / alerts / items / additionalProperties
      Added value: +true
    • changedOutput schema / properties / alerts / items / description
      Previous value: -"Critical substation compliance violation."New value: +"Structured compliance alert or advisory warning record."
    • addedOutput schema / properties / alerts / items / properties
      Added value: +{
      +  "code": {
      +    "description": "Machine-readable finding classification code.",
      +    "type": "string"
      +  },
      +  "en": {
      +    "description": "English localized engineering diagnostic message.",
      +    "type": "string"
      +  },
      +  "fr": {
      +    "description": "French localized engineering diagnostic message.",
      +    "type": "string"
      +  },
      +  "severity": {
      +    "description": "Finding severity level (\"CRITICAL\" or \"WARNING\").",
      +    "type": "string"
      +  }
      +}
    • changedOutput schema / properties / alerts / items / type
      Previous value: -"string"New value: +"object"
    • addedOutput schema / properties / altitudeCorrection
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Altitude air-density dielectric and linear air-clearance scaling factors.",
      +  "properties": {
      +    "altitudeCorrectionRequired": {
      +      "description": "True when site elevation exceeds 1000 m.",
      +      "type": "boolean"
      +    },
      +    "altitudeM": {
      +      "description": "Evaluated site elevation above sea level in meters.",
      +      "type": "number"
      +    },
      +    "clearanceIncreasePct": {
      +      "description": "Percentage increase applied to air clearances (%).",
      +      "type": "number"
      +    },
      +    "clearanceLinearFactor": {
      +      "description": "Linear air-clearance altitude expansion multiplier.",
      +      "type": "number"
      +    },
      +    "dielectricLiPfFactor": {
      +      "description": "Lightning & 50 Hz dielectric withstand multiplier.",
      +      "type": "number"
      +    },
      +    "dielectricSiFactor": {
      +      "description": "Switching impulse dielectric withstand multiplier.",
      +      "type": "number"
      +    },
      +    "thresholdM": {
      +      "description": "Altitude threshold above which air-density derating begins (1000 m).",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / clearancesM / properties / conductorHeightAboveTrackM
      Added value: +{
      +  "description": "Minimum busbar conductor height above access track in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / d1VicinityM
      Added value: +{
      +  "description": "Outer vicinity safety boundary distance D1 in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / d3ErgonomicM
      Added value: +{
      +  "description": "Ergonomic live-zone clearance envelope D3 in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / dmPhaseEarthM
      Added value: +{
      +  "description": "Minimum phase-to-earth air clearance Dm in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / dmRodStructM
      Added value: +{
      +  "description": "Rod-to-structure phase-to-earth air clearance in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / dmaApproachM
      Added value: +{
      +  "description": "Live-work minimum approach distance Dma in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / dmacCorrectedM
      Added value: +{
      +  "description": "Altitude-corrected approach distance Dmac in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / dmsSafeHeightM
      Added value: +{
      +  "description": "Minimum safety working clearance height Dms in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / dpPhasePhaseM
      Added value: +{
      +  "description": "Minimum phase-to-phase air clearance Dp in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / dpRodCondM
      Added value: +{
      +  "description": "Rod-to-conductor phase-to-phase clearance in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / dt1WorkHorizM
      Added value: +{
      +  "description": "Horizontal live-maintenance work clearance Dt1 in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / dt4WorkVertM
      Added value: +{
      +  "description": "Vertical live-maintenance work clearance Dt4 in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / fenceMinSetbackHvM
      Added value: +{
      +  "description": "Minimum perimeter fence setback distance in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / insulatorFootMinM
      Added value: +{
      +  "description": "Minimum live-to-pedestal insulator base height in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / clearancesM / properties / trackGaugeM
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Substation equipment maintenance track envelope geometry.",
      +  "properties": {
      +    "deckHeightM": {
      +      "description": "Access vehicle deck height in meters.",
      +      "type": "number"
      +    },
      +    "lateralMarginM": {
      +      "description": "Lateral clearance margin beyond vehicle deck in meters.",
      +      "type": "number"
      +    },
      +    "widthM": {
      +      "description": "Access vehicle track gauge width in meters.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / clearancesM / properties / trackMinimumWidthM
      Added value: +{
      +  "description": "Minimum gantry handling track width in meters.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / compactAndArrester / properties / compactAltitudeAlert
      Added value: +{
      +  "description": "True when compact switchgear exceeds altitude dielectric threshold.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / compactAndArrester / properties / gisArresterEvaluation
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Enclosed GIS cable and busduct surge arrester requirement assessment.",
      +  "properties": {
      +    "applicableToCurrentTech": {
      +      "description": "True when GIS arrester distance rule applies directly.",
      +      "type": "boolean"
      +    },
      +    "blindBusLengthM": {
      +      "description": "Evaluated enclosed shielded busduct length in meters.",
      +      "type": "number"
      +    },
      +    "cableLengthM": {
      +      "description": "Evaluated enclosed solid-dielectric cable length in meters.",
      +      "type": "number"
      +    },
      +    "required": {
      +      "description": "True if ZnO arrester is mandatory under current inputs.",
      +      "type": "boolean"
      +    },
      +    "ruleScope": {
      +      "description": "Evaluated GIS cable/busduct arrester threshold tier.",
      +      "type": "string"
      +    },
      +    "wouldTriggerInGis": {
      +      "description": "True if enclosed cable/busduct lengths exceed GIS limits.",
      +      "type": "boolean"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / compactAndArrester / properties / znoArresterSpec
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Coordinated ZnO surge arrester ratings and protective separation bounds.",
      +  "properties": {
      +    "maxDistanceLineM": {
      +      "description": "Maximum protective separation from line arrester in meters.",
      +      "type": "number"
      +    },
      +    "maxDistanceXfmrM": {
      +      "description": "Maximum protective separation from transformer arrester in meters.",
      +      "type": "number"
      +    },
      +    "neutralArresterKv": {
      +      "description": "Recommended neutral-point ZnO arrester rating in kV.",
      +      "type": "number"
      +    },
      +    "neutralCoilOhm": {
      +      "description": "Recommended transformer neutral earthing impedance in ohms.",
      +      "type": "number"
      +    },
      +    "ucKv": {
      +      "description": "ZnO arrester continuous operating voltage Uc in kV.",
      +      "type": "number"
      +    },
      +    "upKv": {
      +      "description": "ZnO arrester lightning impulse residual voltage Up in kV.",
      +      "type": "number"
      +    },
      +    "urLineKv": {
      +      "description": "Line-entrance ZnO arrester rated voltage Ur in kV.",
      +      "type": "number"
      +    },
      +    "urXfmrKv": {
      +      "description": "Transformer-terminal ZnO arrester rated voltage Ur in kV.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / coronaAndPollution / properties / conductorDiameterMm
      Added value: +{
      +  "description": "Evaluated HV phase conductor outer diameter in mm.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / coronaAndPollution / properties / coronaAltitudeFactor
      Added value: +{
      +  "description": "Altitude corona inception surface gradient derating factor.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / coronaAndPollution / properties / diameterFactorK
      Added value: +{
      +  "description": "Creepage profile diameter correction factor k.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / coronaAndPollution / properties / meanInsulatorDiaCm
      Added value: +{
      +  "description": "Evaluated average post insulator diameter in cm.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / coronaAndPollution / properties / peekCriticalPeakKv
      Added value: +{
      +  "description": "Peek critical corona inception peak voltage in kV.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / coronaAndPollution / properties / pollutionLegacyLevel
      Added value: +{
      +  "description": "Legacy pollution severity index (\"I\"..\"IV\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / coronaAndPollution / properties / pollutionUnifiedClass
      Added value: +{
      +  "description": "Unified site pollution severity class (\"a\"..\"e\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / coronaAndPollution / properties / requiredCreepagePhPhMm
      Added value: +{
      +  "description": "Minimum required phase-to-phase creepage distance in mm.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / coronaAndPollution / properties / requiredUscdPhEarthMm
      Added value: +{
      +  "description": "Minimum required phase-to-earth USCD creepage in mm.",
      +  "type": "number"
      +}
    • changedOutput schema / properties / voltageTier / description
      Previous value: -"Resolved system voltage tier, altitude factor Ka, and insulation ceiling."New value: +"Resolved system voltage tier, Um ceiling, and technology class."
    • addedOutput schema / properties / voltageTier / properties / domainClass
      Added value: +{
      +  "description": "HV voltage domain tier label (e.g. \"HTB1\", \"HTB2\", \"HTB3\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / voltageTier / properties / equivalenceApplied
      Added value: +{
      +  "description": "True if GIS-to-AIS dielectric equivalence factor applied.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / voltageTier / properties / inputUnKv
      Added value: +{
      +  "description": "Requested nominal system voltage Un in kV.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / voltageTier / properties / specKv
      Added value: +{
      +  "description": "Resolved HV design voltage class in kV.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / voltageTier / properties / technology
      Added value: +{
      +  "description": "Evaluated switchgear technology (\"ais\", \"gis\", or \"compact\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / voltageTier / properties / umKv
      Added value: +{
      +  "description": "Highest equipment operating voltage Um in kV.",
      +  "type": "number"
      +}
    • changedOutput schema / properties / warnings / description
      Previous value: -"Non-blocking engineering observations."New value: +"Advisory non-blocking engineering observations."
    • addedOutput schema / properties / warnings / items / additionalProperties
      Added value: +true
    • changedOutput schema / properties / warnings / items / description
      Previous value: -"Advisory engineering warning message."New value: +"Structured compliance alert or advisory warning record."
    • addedOutput schema / properties / warnings / items / properties
      Added value: +{
      +  "code": {
      +    "description": "Machine-readable finding classification code.",
      +    "type": "string"
      +  },
      +  "en": {
      +    "description": "English localized engineering diagnostic message.",
      +    "type": "string"
      +  },
      +  "fr": {
      +    "description": "French localized engineering diagnostic message.",
      +    "type": "string"
      +  },
      +  "severity": {
      +    "description": "Finding severity level (\"CRITICAL\" or \"WARNING\").",
      +    "type": "string"
      +  }
      +}
    • changedOutput schema / properties / warnings / items / type
      Previous value: -"string"New value: +"object"
    • addedOutput schema / properties / withstandLevelsKv / properties / equipment
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Switchgear and busbar insulator dielectric withstand levels in kV.",
      +  "properties": {
      +    "liBaseKv": {
      +      "description": "Base sea-level lightning impulse withstand voltage LIWL in kV.",
      +      "type": "number"
      +    },
      +    "liCorrectedKv": {
      +      "description": "Altitude-corrected lightning impulse withstand LIWL in kV.",
      +      "type": "number"
      +    },
      +    "pf1MinBaseKv": {
      +      "description": "Base 1-minute power-frequency withstand voltage in kV.",
      +      "type": "number"
      +    },
      +    "pf1MinCorrectedKv": {
      +      "description": "Altitude-corrected 1-minute power-frequency withstand in kV.",
      +      "type": "number"
      +    },
      +    "siBaseKv": {
      +      "description": "Base sea-level switching impulse withstand SIWL in kV.",
      +      "type": "number"
      +    },
      +    "siCorrectedKv": {
      +      "description": "Altitude-corrected switching impulse withstand SIWL in kV.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / withstandLevelsKv / properties / transformer
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Power transformer dielectric withstand levels in kV.",
      +  "properties": {
      +    "liBaseKv": {
      +      "description": "Transformer base lightning impulse withstand LIWL in kV.",
      +      "type": "number"
      +    },
      +    "liCorrectedKv": {
      +      "description": "Altitude-corrected transformer LIWL in kV.",
      +      "type": "number"
      +    },
      +    "liReducedKv": {
      +      "description": "Graded/reduced winding lightning impulse withstand in kV.",
      +      "type": "number"
      +    },
      +    "pf1MinCorrectedKv": {
      +      "description": "Altitude-corrected transformer 1-minute withstand in kV.",
      +      "type": "number"
      +    },
      +    "pf1MinEnvelopeKv": {
      +      "description": "Transformer 1-minute power-frequency envelope in kV.",
      +      "type": "number"
      +    },
      +    "siBaseKv": {
      +      "description": "Transformer switching impulse withstand SIWL in kV.",
      +      "type": "number"
      +    },
      +    "siCorrectedKv": {
      +      "description": "Altitude-corrected transformer SIWL in kV.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
  2. Changed144 schema fields changed
    • addedInput schema / additionalProperties
      Added value: +true
    • addedInput schema / properties / altitudeM / description
      Added value: +"Substation elevation above sea level in meters (m) for air-density correction."
    • addedInput schema / properties / ambientTempC / description
      Added value: +"Design ambient outdoor air temperature in deg C."
    • addedInput schema / properties / applyVoltageEquivalence / description
      Added value: +"True to apply equivalent GIS-to-AIS insulation reduction factors where valid."
    • addedInput schema / properties / arresterDistanceM / description
      Added value: +"Alias for electrical separation distance from surge arrester in meters."
    • addedInput schema / properties / autonomyHours / description
      Added value: +"Required backup battery autonomy duration in hours."
    • addedInput schema / properties / auxVoltageV / description
      Added value: +"Auxiliary DC control battery bank nominal voltage in V (e.g. 48 or 125 Vdc)."
    • addedInput schema / properties / batteryTech / description
      Added value: +"Auxiliary battery chemistry (\"LEAD_VRLA\", \"NICD\", \"LFP\")."
    • addedInput schema / properties / bayCount / description
      Added value: +"Number of connected HV switchgear bays (integer >= 1)."
    • addedInput schema / properties / bayCount / minimum
      Added value: +1
    • addedInput schema / properties / bf50Ms / description
      Added value: +"Alias for 50BF breaker failure backup timing in ms."
    • addedInput schema / properties / breaker50BfMs / description
      Added value: +"Breaker-failure backup clearing time in ms."
    • addedInput schema / properties / burialDepthM / description
      Added value: +"Alias for earthing grid burial depth h in meters."
    • addedInput schema / properties / buriedDepthM / description
      Added value: +"Earthing grid burial depth h in meters."
    • addedInput schema / properties / busScheme / description
      Added value: +"Busbar topology configuration (e.g. \"SINGLE_BUS\", \"DOUBLE_BUS\", \"BREAKER_AND_HALF\")."
    • addedInput schema / properties / cableLoopDropV / description
      Added value: +"DC battery distribution cable loop voltage drop in V."
    • addedInput schema / properties / category / description
      Added value: +"Plant connection power category or regulatory tier code."
    • addedInput schema / properties / climateZone / description
      Added value: +"Wind/ice mechanical loading climate zone code."
    • addedInput schema / properties / commDelayModeled / description
      Added value: +"True if communication latency is explicitly included in EMT study."
    • addedInput schema / properties / commDelayMs / description
      Added value: +"Teleprotection communication channel one-way latency in ms."
    • addedInput schema / properties / conductorDiameterMm / description
      Added value: +"Tubular or stranded HV conductor outer diameter in mm."
    • addedInput schema / properties / conductorHeightM / description
      Added value: +"Height of live HV busbars above ground level in meters."
    • addedInput schema / properties / conductorId / description
      Added value: +"Busbar or overhead phase conductor profile identifier."
    • addedInput schema / properties / conductorMmMm / description
      Added value: +"Legacy alias for conductor outer diameter in mm."
    • addedInput schema / properties / connectionType / description
      Added value: +"Earthing conductor joint class (\"EXOTHERMIC\", \"COMPRESSION\", \"BOLTED\")."
    • addedInput schema / properties / coreDiaCm / description
      Added value: +"Insulator core shank diameter in cm for creepage profile factor."
    • addedInput schema / properties / dcSystemV / description
      Added value: +"Alias for DC auxiliary voltage bus rating in V (e.g. 48, 110, 125)."
    • addedInput schema / properties / deepRhoOhmM / description
      Added value: +"Deep soil stratum resistivity rho2 in ohm*m."
    • addedInput schema / properties / distanceFromArresterM / description
      Added value: +"Electrical separation distance from ZnO surge arrester to protected winding in meters."
    • addedInput schema / properties / earthingGeometry / description
      Added value: +"Earthing electrode layout (\"MESH\", \"ROD_BANK\", \"STAR\")."
    • addedInput schema / properties / faultClearingMs / description
      Added value: +"Total primary protection + breaker fault clearing time in ms."
    • addedInput schema / properties / faultDurationS / description
      Added value: +"Step/touch voltage fault clearing duration in seconds."
    • addedInput schema / properties / fenceSetbackM / description
      Added value: +"Perimeter security fence setback distance from live HV parts in meters."
    • addedInput schema / properties / frequencyHz / description
      Added value: +"Grid frequency at PCC in Hz (nominal 50.0 Hz)."
    • addedInput schema / properties / generatorTech / description
      Added value: +"Primary generation unit type (\"SYNCHRONOUS\", \"IBR\", \"HYBRID\")."
    • addedInput schema / properties / gisBlindBusLengthM / description
      Added value: +"Enclosed GIS shielded busduct segment length in meters."
    • addedInput schema / properties / gisCableLengthM / description
      Added value: +"Enclosed GIS solid-dielectric cable run length in meters."
    • addedInput schema / properties / gravelRhoOhmM / description
      Added value: +"Crushed surface gravel wet resistivity in ohm*m."
    • addedInput schema / properties / gravelThickM / description
      Added value: +"Crushed surface insulating gravel layer thickness in meters."
    • addedInput schema / properties / gridAreaM2 / description
      Added value: +"Total buried earthing grid footprint area in m2."
    • addedInput schema / properties / gridLengthM / description
      Added value: +"Earthing mesh rectangular length in meters."
    • addedInput schema / properties / gridWidthM / description
      Added value: +"Earthing mesh rectangular width in meters."
    • addedInput schema / properties / guardWireReductionKr / description
      Added value: +"Overhead earth-wire current return reduction factor kr (0..1)."
    • addedInput schema / properties / hasCompiledDll / description
      Added value: +"True when black-box vendor EMT simulation model DLL is supplied."
    • addedInput schema / properties / hasEarthWire / description
      Added value: +"True when overhead shield wires protect HV substation spans."
    • addedInput schema / properties / hasGenerationGe12Mw / description
      Added value: +"True for sites embedding local generation >= 12 MW."
    • addedInput schema / properties / hasRemoteShed / description
      Added value: +"True when remote utility load/generation shedding teleprotection is active."
    • addedInput schema / properties / hasSpecificDielectricStudy / description
      Added value: +"True when transient switching/lightning simulation supports reduced margin."
    • addedInput schema / properties / hasZeroSeqNeutralTr / description
      Added value: +"True when step-up/interconnecting transformer provides zero-sequence neutral path."
    • addedInput schema / properties / highKeraunicZone / description
      Added value: +"True for sites located in high lightning flash density zones."
    • addedInput schema / properties / igEarthFaultKa / description
      Added value: +"Grid-injected earth fault current Ig (post split factor) in kA."
    • addedInput schema / properties / ik1Ka / description
      Added value: +"Single-phase-to-earth fault current Ik1 at the substation in kA."
    • addedInput schema / properties / ik3Ka / description
      Added value: +"Three-phase symmetrical short-circuit current Ik3 in kA."
    • addedInput schema / properties / ik3MaxKa / description
      Added value: +"Maximum three-phase short-circuit current Ik3_max in kA."
    • addedInput schema / properties / insulatorDiameterMm / description
      Added value: +"Insulator core/mean diameter in mm."
    • addedInput schema / properties / insulatorMeanDiaCm / description
      Added value: +"Mean porcelain/composite post insulator diameter in cm."
    • addedInput schema / properties / isCriticalSubstation / description
      Added value: +"True for critical grid node with stricter breaker failure budget."
    • addedInput schema / properties / isPowerElectronic / description
      Added value: +"True if connected via power-electronic inverter interface (IBR/HVDC)."
    • addedInput schema / properties / lang / default
      Added value: +"fr"
    • addedInput schema / properties / lang / description
      Added value: +"Response localization language code (\"fr\" for French or \"en\" for English, defaults to \"fr\")."
    • addedInput schema / properties / lineFeedCount / description
      Added value: +"Number of connected overhead lines sharing earth return paths."
    • addedInput schema / properties / lineFeedCount / minimum
      Added value: +0
    • addedInput schema / properties / loadW / description
      Added value: +"Standing DC auxiliary load power in watts (W)."
    • addedInput schema / properties / meshConductorMm2 / description
      Added value: +"Buried copper earthing grid conductor cross-section in mm2."
    • addedInput schema / properties / meshSpacingM / description
      Added value: +"Buried earthing grid mesh conductor spacing D in meters."
    • addedInput schema / properties / mode / default
      Added value: +"insulation_and_clearances"
    • addedInput schema / properties / mode / description
      Added value: +"Substation engineering domain mode or full multi-section audit."
    • addedInput schema / properties / nominalVoltageKv / description
      Added value: +"Secondary alias for nominal system voltage Un in kV."
    • addedInput schema / properties / operatingCurrentA / description
      Added value: +"Normal continuous busbar operating current in amperes."
    • addedInput schema / properties / overheadZLineOhm / description
      Added value: +"Zero-sequence overhead earth-wire impedance per circuit in ohms."
    • addedInput schema / properties / overloadCurrentA / description
      Added value: +"Emergency short-term overload busbar current in amperes."
    • addedInput schema / properties / overloadWindow / description
      Added value: +"Thermal overload window duration tag (e.g. \"15min\", \"20min\")."
    • addedInput schema / properties / pMaxMw / description
      Added value: +"Maximum active power capacity Pmax in MW."
    • addedInput schema / properties / pOperatingMw / description
      Added value: +"Measured steady-state active power at PCC in MW."
    • addedInput schema / properties / pRaccMw / description
      Added value: +"Subscribed grid connection active power Pracc in MW."
    • addedInput schema / properties / peakSurgeA / description
      Added value: +"Simultaneous breaker trip/close solenoid peak surge current in amperes."
    • addedInput schema / properties / permanentCurrentA / description
      Added value: +"Continuous standing DC control load current in amperes."
    • addedInput schema / properties / phaseSpacingM / description
      Added value: +"Center-to-center busbar phase spacing in meters."
    • addedInput schema / properties / phasorFormat / description
      Added value: +"Phasor telemetry frame representation (\"POLAR\", \"RECTANGULAR\")."
    • addedInput schema / properties / pollutionClass / description
      Added value: +"Site environmental pollution severity (\"LIGHT\", \"MEDIUM\", \"HEAVY\", \"VERY_HEAVY\")."
    • addedInput schema / properties / presetId / description
      Added value: +"Optional reference HV substation preset identifier pre-filling geometry and grid parameters."
    • addedInput schema / properties / protectionScheme / description
      Added value: +"Busbar thermal/fault clearance scheme identifier."
    • addedInput schema / properties / providedCreepageMm / description
      Added value: +"Installed insulator surface creepage distance in mm."
    • addedInput schema / properties / providedDmM / description
      Added value: +"Design phase-to-earth air clearance Dm in meters."
    • addedInput schema / properties / providedDmsM / description
      Added value: +"Design safety working air clearance Dms in meters."
    • addedInput schema / properties / providedDpM / description
      Added value: +"Design phase-to-phase air clearance Dp in meters."
    • addedInput schema / properties / qAbsorbMvar / description
      Added value: +"Under-excited reactive power absorption capability in Mvar."
    • addedInput schema / properties / qInjectMvar / description
      Added value: +"Over-excited reactive power injection capability in Mvar."
    • addedInput schema / properties / qOperatingMvar / description
      Added value: +"Actual reactive power exchange at PCC in Mvar (+ inject, - absorb)."
    • addedInput schema / properties / reducedInsulationXfmr / description
      Added value: +"True if the power transformer specifies graded/reduced neutral-end insulation."
    • addedInput schema / properties / reservePct / description
      Added value: +"Battery capacity aging & temperature design reserve margin in %."
    • addedInput schema / properties / rfgType / description
      Added value: +"Generator grid-code requirement class (\"A\", \"B\", \"C\", \"D\")."
    • addedInput schema / properties / rhoDeepOhmM / description
      Added value: +"Alias for deep soil stratum resistivity rho2 in ohm*m."
    • addedInput schema / properties / rhoUpperOhmM / description
      Added value: +"Two-layer upper surface soil layer resistivity rho1 in ohm*m."
    • addedInput schema / properties / rocofHzPerSec / description
      Added value: +"Rate of change of frequency ROCOF withstand in Hz/s."
    • addedInput schema / properties / rodCount / description
      Added value: +"Total count of driven vertical ground rods connected to mesh."
    • addedInput schema / properties / rodCount / minimum
      Added value: +0
    • addedInput schema / properties / rodLengthM / description
      Added value: +"Vertical earthing rod electrode length in meters."
    • addedInput schema / properties / rodRadiusM / description
      Added value: +"Vertical earthing rod equivalent radius in meters."
    • addedInput schema / properties / rodSpacingM / description
      Added value: +"Minimum spacing between adjacent vertical ground rods in meters."
    • addedInput schema / properties / role / description
      Added value: +"Alias for substation grid connection role."
    • addedInput schema / properties / sMva / description
      Added value: +"Reference network base power S in MVA for short-circuit or VT burden."
    • addedInput schema / properties / seasonKey / description
      Added value: +"Ambient thermal season profile (\"WINTER\", \"INTERMEDIATE\", \"SUMMER\")."
    • addedInput schema / properties / shedDia1Cm / description
      Added value: +"Major insulator weather shed diameter in cm."
    • addedInput schema / properties / shedDia2Cm / description
      Added value: +"Minor alternating insulator shed diameter in cm."
    • addedInput schema / properties / simMae / description
      Added value: +"Simulated mean absolute error MAE metric for EMT model validation."
    • addedInput schema / properties / simMe / description
      Added value: +"Simulated mean error ME metric for EMT model validation."
    • addedInput schema / properties / simMxe / description
      Added value: +"Simulated maximum error MXE metric for EMT model validation."
    • addedInput schema / properties / siteRole / description
      Added value: +"Grid connection role (\"GENERATION\", \"INDUSTRIAL_CONSUMER\", \"STORAGE\")."
    • addedInput schema / properties / soilRhoOhmM / description
      Added value: +"Equivalent uniform surface soil resistivity rho in ohm*m."
    • addedInput schema / properties / spanM / description
      Added value: +"Rigid tubular busbar support span length between post insulators in meters."
    • addedInput schema / properties / starRayLenM / description
      Added value: +"Length per counterpoise star-ray arm in meters."
    • addedInput schema / properties / starRaysN / description
      Added value: +"Number of counterpoise star-ray arms when star geometry is selected."
    • changedInput schema / properties / starRaysN / type
      Previous value: -"integer"New value: +"number"
    • addedInput schema / properties / steelTubeAroundTcTore / description
      Added value: +"True if a ferromagnetic steel sleeve passes through the toroidal zero-sequence CT."
    • addedInput schema / properties / tanPhiMeasured / description
      Added value: +"Measured reactive-to-active power ratio Q/P at PCC."
    • addedInput schema / properties / tauMs / description
      Added value: +"DC fault current decay time constant tau = L/R in milliseconds."
    • addedInput schema / properties / technology / description
      Added value: +"Substation switchgear technology (\"AIS\" air-insulated or \"GIS\" gas-insulated)."
    • addedInput schema / properties / testMae / description
      Added value: +"Measured field-test MAE threshold for model acceptance."
    • addedInput schema / properties / testMe / description
      Added value: +"Measured field-test ME threshold for model acceptance."
    • addedInput schema / properties / testMxe / description
      Added value: +"Measured field-test MXE threshold for model acceptance."
    • addedInput schema / properties / tkSec / description
      Added value: +"Short-circuit mechanical & adiabatic thermal fault duration tk in seconds."
    • changedInput schema / properties / transformerCableInToroidalCt / description
      Previous value: -"Boolean or conduit string (e.g. \"steel_s235\" triggers magnetic shunting alert vs \"fibro_100\")."New value: +"Boolean flag or conduit material tag (\"steel_s235\" vs \"fibro_100\") around toroidal CT."
    • addedInput schema / properties / transformerCableInToroidalCt / oneOf
      Added value: +[
      +  {
      +    "description": "Boolean indicating whether cable screen/sheath loops correctly bypass the toroidal CT window.",
      +    "type": "boolean"
      +  },
      +  {
      +    "description": "Conduit sleeve material tag (e.g. \"steel_s235\" triggers magnetic shunting alert vs \"fibro_100\").",
      +    "type": "string"
      +  }
      +]
    • addedInput schema / properties / tubeOdMm / description
      Added value: +"Rigid aluminum busbar tube outer diameter in mm."
    • addedInput schema / properties / tubeWallMm / description
      Added value: +"Rigid aluminum busbar tube wall thickness in mm."
    • addedInput schema / properties / uOperatingKv / description
      Added value: +"Actual steady-state operating voltage at PCC in kV."
    • addedInput schema / properties / uPu / description
      Added value: +"Normalized bus voltage in per-unit (p.u.)."
    • addedInput schema / properties / unKv / description
      Added value: +"Nominal system line-to-line voltage Un in kV (e.g. 63, 90, 225, 400)."
    • addedInput schema / properties / voltageKv / description
      Added value: +"Alias for nominal HV busbar voltage in kV."
    • addedInput schema / properties / vtClass / description
      Added value: +"Metering/protection voltage transformer accuracy class (e.g. \"0.2\", \"3P\")."
    • addedInput schema / properties / vtDropPct / description
      Added value: +"Measured VT secondary voltage loop drop percentage (%)."
    • addedInput schema / properties / xfmrPowerMva / description
      Added value: +"Main HV/MV power transformer rated MVA."
    • addedInput schema / properties / z0Ohm / description
      Added value: +"Absolute zero-sequence source impedance Z0 in ohms."
    • addedInput schema / properties / z0OverZ1 / description
      Added value: +"System effective earthing zero-to-positive impedance ratio Z0/Z1."
    • addedInput schema / properties / zHTROhm / description
      Added value: +"Zero-sequence upstream transformer grounding reactance in ohms."
    • addedInput schema / properties / zMaltOhm / description
      Added value: +"Combined substation earthing grid impedance magnitude in ohms."
    • addedInput schema / properties / zTrOhm / description
      Added value: +"Transformer positive-sequence impedance magnitude in ohms."
    • addedInput schema / properties / zone1Ms / description
      Added value: +"Distance relay Zone 1 instantaneous trip time in ms."
    • addedInput schema / properties / zone2Ms / description
      Added value: +"Distance relay Zone 2 backup trip time in ms."
    • addedInput schema / properties / zone3Ms / description
      Added value: +"Distance relay Zone 3 remote backup trip time in ms."
    • addedInput schema / properties / zone5DipPct / description
      Added value: +"Low-voltage ride-through deep dip threshold (% residual U)."
    • addedInput schema / properties / zone5DurationMs / description
      Added value: +"Low-voltage ride-through hold duration in ms."
    • changedOutput schema / (root)
      Previous value: -nullNew value: +{
      +  "additionalProperties": true,
      +  "description": "HV substation insulation, grid code, electrodynamics, and earthing evaluation with calculationTrace and legalNotice.",
      +  "properties": {
      +    "alerts": {
      +      "description": "Blocking engineering alerts requiring design change.",
      +      "items": {
      +        "description": "Critical substation compliance violation.",
      +        "type": "string"
      +      },
      +      "type": "array"
      +    },
      +    "calculationTrace": {
      +      "additionalProperties": true,
      +      "description": "Transparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.",
      +      "properties": {
      +        "defaultsApplied": {
      +          "additionalProperties": true,
      +          "description": "Default physical or engineering assumptions injected when optional inputs were omitted.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "engineeringAssumptions": {
      +          "description": "Explicit boundary assumptions required to interpret the numerical output.",
      +          "items": {
      +            "description": "Boundary condition or validity assumption for the calculation.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "formulasAndConstants": {
      +          "additionalProperties": true,
      +          "description": "Mathematical formulas and SI physical constants bound to this calculation mode.",
      +          "properties": {
      +            "constants": {
      +              "additionalProperties": true,
      +              "description": "Map of physical constants, resistivities, and design coefficients in SI units.",
      +              "properties": {},
      +              "type": "object"
      +            },
      +            "formulas": {
      +              "description": "Ordered list of physical equations evaluated by the calculation engine.",
      +              "items": {
      +                "description": "Symbolic engineering formula string used during evaluation.",
      +                "type": "string"
      +              },
      +              "type": "array"
      +            }
      +          },
      +          "type": "object"
      +        },
      +        "inputsProvided": {
      +          "additionalProperties": true,
      +          "description": "Non-empty normalized input parameters explicitly supplied by the caller.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "mode": {
      +          "description": "Normalized calculation mode executed for the current payload.",
      +          "type": "string"
      +        },
      +        "physicalPrinciples": {
      +          "description": "Key physical principles governing the computed result.",
      +          "items": {
      +            "description": "Concise statement of an underlying electrical or thermal principle.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "tool": {
      +          "description": "Resolved Brain tool identifier audited by the calculation tracer.",
      +          "type": "string"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "clearancesM": {
      +      "additionalProperties": true,
      +      "description": "Computed minimum phase-to-earth Dm, phase-to-phase Dp, and safety clearances in m.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "compactAndArrester": {
      +      "additionalProperties": true,
      +      "description": "ZnO surge arrester protective distance margin and BIL reduction checks.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "compliant": {
      +      "description": "Overall physical compliance verdict for requested HV domain(s).",
      +      "type": "boolean"
      +    },
      +    "coronaAndPollution": {
      +      "additionalProperties": true,
      +      "description": "Surface gradient corona inception and insulator USCD creepage margin.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "legalNotice": {
      +      "description": "Informational engineering compliance notice confirming SI physical scope and intellectual property rules.",
      +      "type": "string"
      +    },
      +    "mode": {
      +      "description": "Executed HV substation calculation mode.",
      +      "type": "string"
      +    },
      +    "status": {
      +      "description": "Human-readable verdict status string.",
      +      "type": "string"
      +    },
      +    "voltageTier": {
      +      "additionalProperties": true,
      +      "description": "Resolved system voltage tier, altitude factor Ka, and insulation ceiling.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "warnings": {
      +      "description": "Non-blocking engineering observations.",
      +      "items": {
      +        "description": "Advisory engineering warning message.",
      +        "type": "string"
      +      },
      +      "type": "array"
      +    },
      +    "withstandLevelsKv": {
      +      "additionalProperties": true,
      +      "description": "Altitude-adjusted LIWL, SIWL, and short-duration AC withstand levels in kV.",
      +      "properties": {},
      +      "type": "object"
      +    }
      +  },
      +  "type": "object"
      +}
  3. First observed

TDQS

A4.2/5.0
Behavior4/5

Does the description disclose side effects, auth requirements, rate limits, or destructive behavior?

Annotations already declare readOnlyHint, idempotentHint, destructiveHint=false and openWorldHint=false, yet the description still adds non-obvious operational facts: non-object payloads raise JSON-RPC -32602, and omitted arguments default to mode='insulation_and_clearances' at 225 kV AIS. The 'stateless, read-only, zero side effects' sentence largely restates the annotations, which keeps it short of a 5, but the error-path and default-behavior disclosure is genuine added value.

Agents need to know what a tool does to the world before calling it. Descriptions should go beyond structured annotations to explain consequences.

Conciseness4/5

Is the description appropriately sized, front-loaded, and free of redundancy?

Front-loaded and segmented into purpose, 'When to use', and 'Behavior' blocks with no filler sentences. The opening physics enumeration is long and partially duplicated by the mode list, but every clause carries a distinct domain or routing fact.

Shorter descriptions cost fewer tokens and are easier for agents to parse. Every sentence should earn its place.

Completeness3/5

Given the tool's complexity, does the description cover enough for an agent to succeed on first attempt?

Routing, safety profile, defaults, and error behavior are complete, and an output schema exists so the return-value enumeration is redundant but harmless. The gap is mode-to-parameter guidance: a 135-parameter, all-optional tool spanning five modes gives an agent no way to know a minimal viable call per mode beyond the default.

Complex tools with many parameters or behaviors need more documentation. Simple tools need less. This dimension scales expectations accordingly.

Parameters3/5

Does the description clarify parameter syntax, constraints, interactions, or defaults beyond what the schema provides?

Schema description coverage is 100% across 135 documented parameters, so the baseline is 3 and the schema does the heavy lifting. The description adds conceptual grouping by naming the physical domains (air-density scaling, creepage, arrester margins, soil mesh) that the parameters serve, but with zero required parameters and five modes it gives no mapping of which parameter clusters belong to which mode, which is the highest-value semantics it could have supplied.

Input schemas describe structure but not intent. Descriptions should explain non-obvious parameter relationships and valid value ranges.

Purpose5/5

Does the description clearly state what the tool does and how it differs from similar tools?

Uses a concrete verb ('Evaluate') with a precisely scoped resource: 63-400 kV HV substation physics, enumerated as specific engineering quantities (Dm/Dp/Dms clearances, USCD creepage, ZnO arrester margins, U/f/Q envelopes, soil mesh, CT conduits, DC auxiliaries). It explicitly excludes sibling domains (MV delivery bays, earthing/lightning, civil foundations) by name, so an agent can discriminate it from brain_calc_mv_delivery_physics and brain_calc_earthing_lightning_trv without reading any schema.

Agents choose between tools based on descriptions. A clear purpose with a specific verb and resource helps agents select the right tool.

Usage Guidelines5/5

Does the description explain when to use this tool, when not to, or what alternatives exist?

Contains an explicit 'When to use' clause (clearances, grid-code audits, busbar forces, soil mesh design) and a 'do NOT use for' clause that names three concrete alternatives with their own domains. This is the when/when-not/alternatives pattern at full strength.

Agents often have multiple tools that could apply. Explicit usage guidance like "use X instead of Y when Z" prevents misuse.

Try in Browser