MV Underground Cable Thermal & Bonding Calculator

brain_calc_hta_cable_cyclic
Read-onlyIdempotent

Calculate buried medium-voltage power cable radial thermal resistances T1..T4, 24-hour cyclic overload multiplier M via exponential integral -Ei(-x), non-adiabatic conductor/screen short-circuit capacity, and induced sheath standing voltages with SVL surge coordination. When to use: Use for underground MV cable ampacity, cyclic soil thermal coupling, and single/cross-bonded sheath voltage studies. Do not use for: <= 1 kV low-voltage feeders or temperature-dependent branch impedance tolerance sweeps -- call brain_calc_lv_feeder_physics or brain_calc_impedance_tolerance instead. Behavior: Computes radial heat-transfer and Faraday sheath equations in a stateless, read-only SI pass with zero mutations; non-object inputs or invalid parameters raise JSON-RPC -32602, and omitted inputs default to mode="study" with the reference 20 kV 240 mm2 Al trefoil preset. Returns: mode, continuousRatingA, cyclicRatingA, thermalResistances, shortCircuitConductor, shortCircuitScreen, sheathBondingAndSvl, calculationTrace, and legalNotice.

Tool call template

This tool declares no required parameters. Add optional parameters from the input schema as needed.

{
  "id": 1,
  "jsonrpc": "2.0",
  "method": "tools/call",
  "params": {
    "arguments": {},
    "name": "brain_calc_hta_cable_cyclic"
  }
}

Input Schema

NameRequiredDescriptionDefault
modeNoThermal calculation mode: complete cable study or specific thermal/sheath sub-model.study
presetIdNoReference underground MV cable construction preset identifier (e.g. "hta_20kv_240al_trefoil").
loadFactorNoDaily cyclic load factor in [0.1, 1.0] used when 24-point hourlyRatios is omitted.
sectionMm2NoPhase conductor cross-sectional area in mm2 (e.g. 150, 240, 400).
hourlyRatiosNoOptional 24-element hourly load profile array overriding loadFactor.
bondingSchemeNoMetallic screen bonding topology ("SINGLE_POINT", "SOLID_BONDING", "CROSS_BONDING").
voltageLineKvNoPhase-to-phase operating line voltage in kV (e.g. 20 kV).
conductorMaterialNoConductor metal identifier ("CU" for copper or "AL" for aluminum).

Output Schema

NameRequiredDescriptionDefault
modeNoExecuted MV underground cable thermal calculation mode.
presetIdNoResolved underground cable preset identifier, or null for custom payloads.
legalNoticeNoInformational engineering compliance notice confirming SI physical scope and intellectual property rules.
cyclicRatingANo24-hour cyclic permissible peak current rating M*Iz in amperes (A).
calculationTraceNoTransparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.
continuousRatingANoSteady-state continuous permissible current rating Iz in amperes (A).
shortCircuitScreenNoNon-adiabatic metallic screen short-circuit thermal capacity check.
thermalResistancesNoRadial cable & soil thermal resistances T1..T4 in K*m/W.
sheathBondingAndSvlNoInduced standing sheath voltage (V) and SVL arrester sizing.
shortCircuitConductorNoNon-adiabatic core conductor short-circuit thermal withstand capacity.

Schema Changelog

Changes observed during successful MCP inspections.

  1. Changed49 schema fields changed
    • changedInput schema / properties / conductorMaterial / description
      Previous value: -"Conductor metal (\"CU\" for copper or \"AL\" for aluminum)."New value: +"Conductor metal identifier (\"CU\" for copper or \"AL\" for aluminum)."
    • addedInput schema / properties / hourlyRatios / items / maximum
      Added value: +1
    • addedInput schema / properties / hourlyRatios / items / minimum
      Added value: +0
    • changedInput schema / properties / loadFactor / description
      Previous value: -"Daily cyclic load factor between 0.1 and 1.0 used when 24-point hourlyRatios is omitted."New value: +"Daily cyclic load factor in [0.1, 1.0] used when 24-point hourlyRatios is omitted."
    • addedInput schema / properties / loadFactor / maximum
      Added value: +1
    • addedInput schema / properties / loadFactor / minimum
      Added value: +0.1
    • changedInput schema / properties / sectionMm2 / description
      Previous value: -"Phase conductor cross-section in mm2 (e.g. 150, 240, 400)."New value: +"Phase conductor cross-sectional area in mm2 (e.g. 150, 240, 400)."
    • addedInput schema / properties / sectionMm2 / minimum
      Added value: +10
    • changedInput schema / properties / voltageLineKv / description
      Previous value: -"Phase-to-phase operating line voltage in kV (e.g. 20)."New value: +"Phase-to-phase operating line voltage in kV (e.g. 20 kV)."
    • addedInput schema / properties / voltageLineKv / minimum
      Added value: +1
    • changedOutput schema / properties / continuousRatingA / description
      Previous value: -"Steady-state continuous permissible current rating Iz in A."New value: +"Steady-state continuous permissible current rating Iz in amperes (A)."
    • changedOutput schema / properties / cyclicRatingA / description
      Previous value: -"24-hour cyclic permissible peak current rating M*Iz in A."New value: +"24-hour cyclic permissible peak current rating M*Iz in amperes (A)."
    • changedOutput schema / properties / mode / description
      Previous value: -"Executed MV cable thermal calculation mode."New value: +"Executed MV underground cable thermal calculation mode."
    • addedOutput schema / properties / presetId
      Added value: +{
      +  "description": "Resolved underground cable preset identifier, or null for custom payloads.",
      +  "oneOf": [
      +    {
      +      "description": "Resolved underground cable preset identifier, or null for custom payloads.",
      +      "type": "string"
      +    },
      +    {
      +      "description": "Null when preset identifier is absent for custom inputs.",
      +      "type": "null"
      +    }
      +  ]
      +}
    • addedOutput schema / properties / sheathBondingAndSvl / properties / recommendedScheme
      Added value: +{
      +  "description": "Recommended sheath bonding arrangement (\"SINGLE_POINT\", \"BOTH_ENDS\", or \"CROSS_BONDING\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sheathBondingAndSvl / properties / standingGradientVPerKm
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Induced sheath standing voltage gradient profile in V/km.",
      +  "properties": {
      +    "centerVPerKm": {
      +      "description": "Center-phase sheath induced voltage gradient in V/km.",
      +      "type": "number"
      +    },
      +    "maxVPerKm": {
      +      "description": "Maximum sheath standing voltage gradient across phases in V/km.",
      +      "type": "number"
      +    },
      +    "outerVPerKm": {
      +      "description": "Outer-phase sheath induced voltage gradient in V/km.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sheathBondingAndSvl / properties / standingVoltageLimitV
      Added value: +{
      +  "description": "Permissible continuous sheath standing voltage limit in volts (V).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sheathBondingAndSvl / properties / svlVerification
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Sheath voltage limiter (SVL) coordination and TOV capability check.",
      +  "properties": {
      +    "minInsulationBilKv": {
      +      "description": "Minimum jacket impulse withstand level BIL in kV.",
      +      "type": "number"
      +    },
      +    "minRequiredUcKv": {
      +      "description": "Minimum required continuous SVL rating Uc in kV.",
      +      "type": "number"
      +    },
      +    "needed": {
      +      "description": "True when sheath voltage limiters (SVL) are required.",
      +      "type": "boolean"
      +    },
      +    "passesCoordination": {
      +      "description": "True when SVL residual voltage coordinates with sheath BIL.",
      +      "type": "boolean"
      +    },
      +    "protectiveMarginPct": {
      +      "description": "Impulse coordination safety margin below jacket BIL in %.",
      +      "type": "number"
      +    },
      +    "recommendedUcKv": {
      +      "description": "Selected commercial SVL continuous voltage rating Uc in kV.",
      +      "type": "number"
      +    },
      +    "residualVoltageKv": {
      +      "description": "SVL surge discharge residual voltage in kV.",
      +      "type": "number"
      +    },
      +    "standingVoltageKv": {
      +      "description": "Continuous standing sheath voltage in kV.",
      +      "type": "number"
      +    },
      +    "tovCompliant": {
      +      "description": "True when SVL temporary overvoltage capability exceeds fault stress.",
      +      "type": "boolean"
      +    }
      +  },
      +  "type": "object"
      +}
    • changedOutput schema / properties / shortCircuitConductor / description
      Previous value: -"Non-adiabatic core conductor short-circuit withstand in kA^2*s."New value: +"Non-adiabatic core conductor short-circuit thermal withstand capacity."
    • addedOutput schema / properties / shortCircuitConductor / properties / achievedFinalTempC
      Added value: +{
      +  "description": "Peak fault temperature reached in degrees Celsius (deg C).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitConductor / properties / componentType
      Added value: +{
      +  "description": "Evaluated cable element (\"CONDUCTOR\" or \"TAPE\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / shortCircuitConductor / properties / durationSec
      Added value: +{
      +  "description": "Short-circuit fault clearing duration in seconds (s).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitConductor / properties / epsilonFactor
      Added value: +{
      +  "description": "Non-adiabatic radial heat diffusion gain factor epsilon (>= 1).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitConductor / properties / iAdiabaticA
      Added value: +{
      +  "description": "Adiabatic short-circuit current withstand in amperes (A).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitConductor / properties / iNonAdiabaticA
      Added value: +{
      +  "description": "Non-adiabatic short-circuit current withstand in amperes (A).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitConductor / properties / kMaterialConstant
      Added value: +{
      +  "description": "Material thermal constant k in A*s^(1/2)/mm2.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitConductor / properties / mFactor
      Added value: +{
      +  "description": "Non-adiabatic thermal boundary factor M, or null for core conductors.",
      +  "oneOf": [
      +    {
      +      "description": "Non-adiabatic thermal boundary factor M, or null for core conductors.",
      +      "type": "number"
      +    },
      +    {
      +      "description": "Null when numeric metric is not evaluated in active mode.",
      +      "type": "null"
      +    }
      +  ]
      +}
    • addedOutput schema / properties / shortCircuitConductor / properties / nonAdiabaticGainPct
      Added value: +{
      +  "description": "Thermal withstand gain from radial heat diffusion in %.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitConductor / properties / sectionMm2
      Added value: +{
      +  "description": "Conductor or metallic screen cross-section in mm2.",
      +  "type": "number"
      +}
    • changedOutput schema / properties / shortCircuitScreen / description
      Previous value: -"Metallic screen short-circuit thermal capacity check."New value: +"Non-adiabatic metallic screen short-circuit thermal capacity check."
    • addedOutput schema / properties / shortCircuitScreen / properties / achievedFinalTempC
      Added value: +{
      +  "description": "Peak fault temperature reached in degrees Celsius (deg C).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitScreen / properties / componentType
      Added value: +{
      +  "description": "Evaluated cable element (\"CONDUCTOR\" or \"TAPE\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / shortCircuitScreen / properties / durationSec
      Added value: +{
      +  "description": "Short-circuit fault clearing duration in seconds (s).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitScreen / properties / epsilonFactor
      Added value: +{
      +  "description": "Non-adiabatic radial heat diffusion gain factor epsilon (>= 1).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitScreen / properties / iAdiabaticA
      Added value: +{
      +  "description": "Adiabatic short-circuit current withstand in amperes (A).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitScreen / properties / iNonAdiabaticA
      Added value: +{
      +  "description": "Non-adiabatic short-circuit current withstand in amperes (A).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitScreen / properties / kMaterialConstant
      Added value: +{
      +  "description": "Material thermal constant k in A*s^(1/2)/mm2.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitScreen / properties / mFactor
      Added value: +{
      +  "description": "Non-adiabatic thermal boundary factor M, or null for core conductors.",
      +  "oneOf": [
      +    {
      +      "description": "Non-adiabatic thermal boundary factor M, or null for core conductors.",
      +      "type": "number"
      +    },
      +    {
      +      "description": "Null when numeric metric is not evaluated in active mode.",
      +      "type": "null"
      +    }
      +  ]
      +}
    • addedOutput schema / properties / shortCircuitScreen / properties / nonAdiabaticGainPct
      Added value: +{
      +  "description": "Thermal withstand gain from radial heat diffusion in %.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / shortCircuitScreen / properties / sectionMm2
      Added value: +{
      +  "description": "Conductor or metallic screen cross-section in mm2.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / thermalResistances / properties / formation
      Added value: +{
      +  "description": "Buried cable laying formation code (e.g. \"3_TREFOIL_TOUCHING\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / thermalResistances / properties / mutualGroupCount
      Added value: +{
      +  "description": "Count of mutually heating buried cable circuits.",
      +  "type": "integer"
      +}
    • addedOutput schema / properties / thermalResistances / properties / t1
      Added value: +{
      +  "description": "Internal insulation radial thermal resistance T1 in K*m/W.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / thermalResistances / properties / t2
      Added value: +{
      +  "description": "Bedding/armor radial thermal resistance T2 in K*m/W.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / thermalResistances / properties / t3
      Added value: +{
      +  "description": "Outer oversheath radial thermal resistance T3 in K*m/W.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / thermalResistances / properties / t4
      Added value: +{
      +  "description": "External soil/duct radial thermal resistance T4 in K*m/W.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / thermalResistances / properties / t4DuctBreakdown
      Added value: +{
      +  "description": "Duct-bank T4 resistance sub-components, or null for direct-buried cables.",
      +  "oneOf": [
      +    {
      +      "additionalProperties": true,
      +      "description": "Duct-bank T4 resistance sub-components, or null for direct-buried cables.",
      +      "properties": {
      +        "t4AirGap": {
      +          "description": "Internal duct air-gap thermal resistance component in K*m/W.",
      +          "type": "number"
      +        },
      +        "t4DuctWall": {
      +          "description": "Duct wall thermal resistance component in K*m/W.",
      +          "type": "number"
      +        },
      +        "t4ExternalMedium": {
      +          "description": "Surrounding soil thermal resistance outside duct bank in K*m/W.",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    {
      +      "description": "Null when optional block is inactive or no match exists.",
      +      "type": "null"
      +    }
      +  ]
      +}
    • addedOutput schema / properties / thermalResistances / properties / totalCableThermalResistance
      Added value: +{
      +  "description": "Sum of radial thermal resistances T1+T2+T3+T4 in K*m/W.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / thermalResistances / properties / uRatio
      Added value: +{
      +  "description": "Geometric burial depth-to-diameter ratio u = 2*L/De.",
      +  "type": "number"
      +}
  2. Changed12 schema fields changed
    • addedInput schema / additionalProperties
      Added value: +true
    • addedInput schema / properties / bondingScheme / description
      Added value: +"Metallic screen bonding topology (\"SINGLE_POINT\", \"SOLID_BONDING\", \"CROSS_BONDING\")."
    • addedInput schema / properties / conductorMaterial / description
      Added value: +"Conductor metal (\"CU\" for copper or \"AL\" for aluminum)."
    • addedInput schema / properties / hourlyRatios / description
      Added value: +"Optional 24-element hourly load profile array overriding loadFactor."
    • addedInput schema / properties / hourlyRatios / items / description
      Added value: +"Normalized hourly load ratio I(t)/I_max in [0, 1]."
    • addedInput schema / properties / loadFactor / description
      Added value: +"Daily cyclic load factor between 0.1 and 1.0 used when 24-point hourlyRatios is omitted."
    • addedInput schema / properties / mode / default
      Added value: +"study"
    • addedInput schema / properties / mode / description
      Added value: +"Thermal calculation mode: complete cable study or specific thermal/sheath sub-model."
    • addedInput schema / properties / presetId / description
      Added value: +"Reference underground MV cable construction preset identifier (e.g. \"hta_20kv_240al_trefoil\")."
    • addedInput schema / properties / sectionMm2 / description
      Added value: +"Phase conductor cross-section in mm2 (e.g. 150, 240, 400)."
    • addedInput schema / properties / voltageLineKv / description
      Added value: +"Phase-to-phase operating line voltage in kV (e.g. 20)."
    • changedOutput schema / (root)
      Previous value: -nullNew value: +{
      +  "additionalProperties": true,
      +  "description": "MV underground cable thermal & sheath bonding study with calculationTrace and legalNotice.",
      +  "properties": {
      +    "calculationTrace": {
      +      "additionalProperties": true,
      +      "description": "Transparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.",
      +      "properties": {
      +        "defaultsApplied": {
      +          "additionalProperties": true,
      +          "description": "Default physical or engineering assumptions injected when optional inputs were omitted.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "engineeringAssumptions": {
      +          "description": "Explicit boundary assumptions required to interpret the numerical output.",
      +          "items": {
      +            "description": "Boundary condition or validity assumption for the calculation.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "formulasAndConstants": {
      +          "additionalProperties": true,
      +          "description": "Mathematical formulas and SI physical constants bound to this calculation mode.",
      +          "properties": {
      +            "constants": {
      +              "additionalProperties": true,
      +              "description": "Map of physical constants, resistivities, and design coefficients in SI units.",
      +              "properties": {},
      +              "type": "object"
      +            },
      +            "formulas": {
      +              "description": "Ordered list of physical equations evaluated by the calculation engine.",
      +              "items": {
      +                "description": "Symbolic engineering formula string used during evaluation.",
      +                "type": "string"
      +              },
      +              "type": "array"
      +            }
      +          },
      +          "type": "object"
      +        },
      +        "inputsProvided": {
      +          "additionalProperties": true,
      +          "description": "Non-empty normalized input parameters explicitly supplied by the caller.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "mode": {
      +          "description": "Normalized calculation mode executed for the current payload.",
      +          "type": "string"
      +        },
      +        "physicalPrinciples": {
      +          "description": "Key physical principles governing the computed result.",
      +          "items": {
      +            "description": "Concise statement of an underlying electrical or thermal principle.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "tool": {
      +          "description": "Resolved Brain tool identifier audited by the calculation tracer.",
      +          "type": "string"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "continuousRatingA": {
      +      "description": "Steady-state continuous permissible current rating Iz in A.",
      +      "type": "number"
      +    },
      +    "cyclicRatingA": {
      +      "description": "24-hour cyclic permissible peak current rating M*Iz in A.",
      +      "type": "number"
      +    },
      +    "legalNotice": {
      +      "description": "Informational engineering compliance notice confirming SI physical scope and intellectual property rules.",
      +      "type": "string"
      +    },
      +    "mode": {
      +      "description": "Executed MV cable thermal calculation mode.",
      +      "type": "string"
      +    },
      +    "sheathBondingAndSvl": {
      +      "additionalProperties": true,
      +      "description": "Induced standing sheath voltage (V) and SVL arrester sizing.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "shortCircuitConductor": {
      +      "additionalProperties": true,
      +      "description": "Non-adiabatic core conductor short-circuit withstand in kA^2*s.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "shortCircuitScreen": {
      +      "additionalProperties": true,
      +      "description": "Metallic screen short-circuit thermal capacity check.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "thermalResistances": {
      +      "additionalProperties": true,
      +      "description": "Radial cable & soil thermal resistances T1..T4 in K*m/W.",
      +      "properties": {},
      +      "type": "object"
      +    }
      +  },
      +  "type": "object"
      +}
  3. First observed

TDQS

A4.6/5.0
Behavior4/5

Does the description disclose side effects, auth requirements, rate limits, or destructive behavior?

Beyond the supplied annotations (readOnlyHint, idempotentHint, destructiveHint=false), the description adds stateless single-pass SI-unit computation, the JSON-RPC -32602 failure behavior for non-object or invalid inputs, and the silent defaulting of omitted inputs to mode="study" with the reference 20 kV 240 mm2 Al trefoil preset — a real trap for an agent expecting an error. The 'zero mutations' phrasing partly restates the annotations, which keeps this just short of the top mark.

Agents need to know what a tool does to the world before calling it. Descriptions should go beyond structured annotations to explain consequences.

Conciseness5/5

Is the description appropriately sized, front-loaded, and free of redundancy?

Dense but deliberately labelled (When to use / Do not use for / Behavior / Returns) so an agent can parse scope and routing first and behavioral detail second. Every clause carries technical content — no filler, no restating of the title.

Shorter descriptions cost fewer tokens and are easier for agents to parse. Every sentence should earn its place.

Completeness4/5

Given the tool's complexity, does the description cover enough for an agent to succeed on first attempt?

For a seven-mode engineering calculator with no required parameters, this covers defaults, error semantics, and routing adequately, and an output schema exists so the 'Returns' enumeration is not strictly necessary. Governing standard/edition for the thermal and short-circuit methods is the one notable omission for an agent judging result acceptability.

Complex tools with many parameters or behaviors need more documentation. Simple tools need less. This dimension scales expectations accordingly.

Parameters4/5

Does the description clarify parameter syntax, constraints, interactions, or defaults beyond what the schema provides?

Schema description coverage is 100%, so the baseline is 3; the description still earns a bump by disclosing behavior the schema does not — that omitted inputs fall back to mode="study" plus a 20 kV 240 mm2 Al trefoil preset, which explains how mode, presetId, and the unset physical parameters interact at call time.

Input schemas describe structure but not intent. Descriptions should explain non-obvious parameter relationships and valid value ranges.

Purpose5/5

Does the description clearly state what the tool does and how it differs from similar tools?

The description names a specific verb ('Calculate') and a tightly scoped resource set: buried MV cable radial thermal resistances T1..T4, 24-hour cyclic overload multiplier M via -Ei(-x), non-adiabatic conductor/screen short-circuit capacity, and induced sheath standing voltages with SVL coordination. That specificity lets an agent separate it from generic thermal or impedance siblings without opening the schema.

Agents choose between tools based on descriptions. A clear purpose with a specific verb and resource helps agents select the right tool.

Usage Guidelines5/5

Does the description explain when to use this tool, when not to, or what alternatives exist?

It supplies an explicit 'When to use' clause (underground MV ampacity, cyclic soil thermal coupling, single/cross-bonded sheath voltage studies) and an explicit 'Do not use for' clause naming two alternatives, brain_calc_lv_feeder_physics and brain_calc_impedance_tolerance, with the disambiguating condition (<=1 kV LV feeders, temperature-dependent branch impedance tolerance sweeps).

Agents often have multiple tools that could apply. Explicit usage guidance like "use X instead of Y when Z" prevents misuse.

Try in Browser

Glama MCP Gateway

Add one secure layer between your agents and this server.

Resources