changedInput schema / properties / busId / description
Previous value: -"Target MV switchboard bus identifier (defaults to \"BUS_MV_A\")."New value: +"Target MV switchboard busbar identifier (defaults to \"BUS_MV_A\")."
changedInput schema / properties / feeders / items / properties / id / description
Previous value: -"MV feeder bay identifier (e.g. \"FEEDER_1\")."New value: +"MV feeder bay identifier string (e.g. \"FEEDER_1\")."
changedInput schema / properties / feeders / items / properties / isDirectional67N / description
Previous value: -"True when directional 67N element is enabled on the feeder."New value: +"True when directional 67N earth-fault element is enabled on feeder."
changedInput schema / properties / feeders / items / properties / lengthM / description
Previous value: -"Cable route length in meters used to estimate 3Ic0 when omitted."New value: +"Cable route length in meters (m) used to estimate 3Ic0 when omitted."
addedInput schema / properties / feeders / items / properties / lengthM / minimum
Added value: +0
changedInput schema / properties / feeders / items / properties / rcaAngleDeg / description
Previous value: -"Directional 67N Relay Characteristic Angle RCA in degrees (default -45 deg)."New value: +"Directional 67N Relay Characteristic Angle RCA in degrees (default -45)."
changedInput schema / properties / feeders / items / properties / threeI0MinAmp / description
Previous value: -"Minimum earth-fault current seen on feeder in A."New value: +"Minimum earth-fault current seen on feeder in amperes (A)."
addedInput schema / properties / feeders / items / properties / threeI0MinAmp / minimum
Added value: +0
changedInput schema / properties / feeders / items / properties / threeIc0Amp / description
Previous value: -"Explicit measured/calculated feeder capacitive current 3Ic0 in A."New value: +"Explicit measured or calculated feeder capacitive current 3Ic0 in A."
addedInput schema / properties / feeders / items / properties / threeIc0Amp / minimum
Added value: +0
changedInput schema / properties / feeders / items / properties / voltageKv / description
Previous value: -"Line-to-line MV feeder voltage in kV."New value: +"Line-to-line MV feeder nominal voltage in kilovolts (kV)."
addedInput schema / properties / feeders / items / properties / voltageKv / minimum
Added value: +0.4
changedInput schema / properties / groundingInfo / properties / busbarCount / description
Previous value: -"Number of coupled MV busbar sections."New value: +"Number of coupled MV switchboard busbar sections."
addedInput schema / properties / groundingInfo / properties / busbarCount / minimum
Added value: +1
changedInput schema / properties / groundingInfo / properties / ctPrimaryA / description
Previous value: -"Phase or toroidal CT primary rating in A."New value: +"Phase or toroidal zero-sequence CT primary rating in amperes (A)."
addedInput schema / properties / groundingInfo / properties / ctPrimaryA / minimum
Added value: +1
changedInput schema / properties / groundingInfo / properties / earthMeasurementMode / description
Previous value: -"Zero-sequence sensing type (\"TOROID\", \"RESIDUAL_3CT\")."New value: +"Zero-sequence current sensing mode (\"TOROID\" or \"RESIDUAL_3CT\")."
changedInput schema / properties / groundingInfo / properties / neutralLimitA / description
Previous value: -"Neutral resistor/reactor earth-fault current limit in A (e.g. 300 or 1000)."New value: +"Neutral resistor or reactor earth-fault limit current in A (e.g. 300)."
addedInput schema / properties / groundingInfo / properties / neutralLimitA / minimum
Added value: +0
changedInput schema / properties / groundingInfo / properties / type / description
Previous value: -"Neutral grounding method (\"bpn\", \"compensated\", \"isolated\", \"solid\")."New value: +"Neutral grounding method (\"bpn\", \"compensated\", \"isolated\", or \"solid\")."
changedOutput schema / properties / busId / description
Previous value: -"Evaluated MV busbar identifier."New value: +"Evaluated MV switchboard busbar identifier."
addedOutput schema / properties / capacitiveCeilingLimitA
Added value: +{
+ "description": "Maximum permissible network capacitive current ceiling in A.",
+ "type": "number"
+}
changedOutput schema / properties / capacitiveCeilingUtilizationPct / description
Previous value: -"Percentage utilization against BPN capacitive trip threshold."New value: +"Percentage utilization against BPN capacitive trip threshold (%)."
addedOutput schema / properties / feederAudits / items / properties / feederId
Added value: +{
+ "description": "Evaluated MV feeder bay identifier string.",
+ "type": "string"
+}
removedOutput schema / properties / feederAudits / items / properties / id
Removed value: -{
- "description": "Feeder identifier.",
- "type": "string"
-}
addedOutput schema / properties / feederAudits / items / properties / is51nPossible
Added value: +{
+ "description": "True when a valid non-directional 51N setting corridor exists.",
+ "type": "boolean"
+}
addedOutput schema / properties / feederAudits / items / properties / is67nMandatory
Added value: +{
+ "description": "True when directional 67N element is required for selectivity.",
+ "type": "boolean"
+}
addedOutput schema / properties / feederAudits / items / properties / maxPickupSensitivityA
Added value: +{
+ "description": "Maximum 51N pickup preserving fault sensitivity (0.8 * 3I0min) in A.",
+ "type": "number"
+}
addedOutput schema / properties / feederAudits / items / properties / minPickupSympathyA
Added value: +{
+ "description": "Minimum 51N pickup avoiding sympathy trips (1.3 * 3Ic0) in A.",
+ "type": "number"
+}
addedOutput schema / properties / feederAudits / items / properties / proposedDelayS
Added value: +{
+ "description": "Recommended earth-fault tripping delay in seconds (s).",
+ "type": "number"
+}
addedOutput schema / properties / feederAudits / items / properties / proposedI0PickupA
Added value: +{
+ "description": "Recommended zero-sequence current pickup threshold I0> in A.",
+ "type": "number"
+}
addedOutput schema / properties / feederAudits / items / properties / rcaAngleDeg
Added value: +{
+ "description": "Applied directional 67N Relay Characteristic Angle RCA in degrees.",
+ "type": "number"
+}
removedOutput schema / properties / feederAudits / items / properties / status
Removed value: -{
- "description": "Coordination status.",
- "type": "string"
-}
addedOutput schema / properties / feederAudits / items / properties / sympathyCurrentA
Added value: +{
+ "description": "Maximum capacitive sympathy return seen during external fault in A.",
+ "type": "number"
+}
addedOutput schema / properties / feederAudits / items / properties / threeI0FaultA
Added value: +{
+ "description": "Minimum earth-fault current available on feeder in amperes (A).",
+ "type": "number"
+}
addedOutput schema / properties / feederAudits / items / properties / threeIc0Amp
Added value: +{
+ "description": "Feeder zero-sequence capacitive charging current 3Ic0 in A.",
+ "type": "number"
+}
changedOutput schema / properties / feedersCount / description
Previous value: -"Number of evaluated feeders."New value: +"Total count of evaluated MV feeders on the busbar."
changedOutput schema / properties / feedersCount / type
Previous value: -"number"New value: +"integer"
addedOutput schema / properties / feedersWith67nMandatory
Added value: +{
+ "description": "Count of feeders requiring directional 67N to avoid sympathy trips.",
+ "type": "integer"
+}
addedOutput schema / properties / isCapacitiveCeilingExceeded
Added value: +{
+ "description": "True when total 3Ic0 exceeds neutral capacitive ceiling.",
+ "type": "boolean"
+}
addedOutput schema / properties / isCapacitiveExpansionAtRisk
Added value: +{
+ "description": "True when 3Ic0 approaches capacitive ceiling margin.",
+ "type": "boolean"
+}
changedOutput schema / properties / mode / description
Previous value: -"Executed homopolar earth-fault mode."New value: +"Executed homopolar earth-fault study mode."
addedOutput schema / properties / totalNetwork3Ic0Amp
Added value: +{
+ "description": "Aggregate network zero-sequence capacitive current in amperes (A).",
+ "type": "number"
+}