Transformer Fire, Oil Bund & Smoke Extraction Calculator

brain_calc_fm_global_fire_smoke_gis
Read-onlyIdempotent

Evaluate transformer fire separation clearances, deluge spray hydraulics (10.2 / 6.1 L/min/m2), oil and fire-water retention bund volume, HVAC thermal cooling (m3/h, Pa), smoke extraction SUE (m2), and coupled substation site safety. When to use: Use for transformer oil-fire protection, bund containment, HVAC smoke extraction, and coupled site audits. Do not use for: Standalone indoor GIS or MV SF6 room airflow, stratification, and O2 asphyxiation audits without transformers -- call brain_audit_gis_mv_room_air_sf6 instead. Behavior: Runs up to three coupled thermal-hydraulic solvers in a stateless, deterministic SI pass with zero mutations; invalid payload types raise JSON-RPC -32602, while omitted inputs default to mode="full_audit", lang="fr", and presetId="gis_225_20kv_reference_2x85mva". Returns: mode, overallStatus, complianceScore, recommendations, sections, calculationTrace, and legalNotice.

Tool call template

This tool declares no required parameters. Add optional parameters from the input schema as needed.

{
  "id": 1,
  "jsonrpc": "2.0",
  "method": "tools/call",
  "params": {
    "arguments": {},
    "name": "brain_calc_fm_global_fire_smoke_gis"
  }
}

Input Schema

NameRequiredDescriptionDefault
langNoResponse localization language code ("fr" for French or "en" for English, defaults to "fr").fr
modeNoFire safety, surge/lightning separation, or cable-tray physics mode (defaults to "full_audit").full_audit
presetIdNoReference fire-safety & substation preset identifier (defaults to "gis_225_20kv_reference_2x85mva").
smokeHvacNoStructured room thermal HVAC and smoke extraction geometry overrides.
transformerNoStructured transformer fire separation, deluge hydraulics, and oil containment inputs.
surgeAndTraysNoOptional rolling-sphere lightning, arrester separation, and cable-tray spacing inputs for "surge_and_cable_trays" mode.

Output Schema

NameRequiredDescriptionDefault
modeNoExecuted fire-safety, smoke extraction, or coupled site audit mode.
presetIdNoResolved substation fire-safety preset identifier, or null for custom payloads.
sectionsNoPer-section calculation detail maps in full_audit mode.
legalNoticeNoInformational engineering compliance notice confirming SI physical scope and intellectual property rules.
overallStatusNoAggregated pass/warning/non-compliant safety verdict.
complianceScoreNoComposite numerical safety compliance score (0..100).
recommendationsNoPrioritized engineering fire-safety and HVAC recommendations.
calculationTraceNoTransparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.

Schema Changelog

Changes observed during successful MCP inspections.

  1. Changed3 schema fields changed
    • changedInput schema / properties / mode / description
      Previous value: -"Fire safety domain mode or coupled three-section substation audit (defaults to \"full_audit\")."New value: +"Fire safety, surge/lightning separation, or cable-tray physics mode (defaults to \"full_audit\")."
    • changedInput schema / properties / mode / enum
      Previous value: -[
      -  "full_audit",
      -  "transformer_fm5_4",
      -  "smoke_extraction_it246",
      -  "gis_mv_sf6_room_air"
      -]New value: +[
      +  "full_audit",
      +  "transformer_fm5_4",
      +  "smoke_extraction_it246",
      +  "gis_mv_sf6_room_air",
      +  "surge_and_cable_trays"
      +]
    • addedInput schema / properties / surgeAndTrays
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Optional rolling-sphere lightning, arrester separation, and cable-tray spacing inputs for \"surge_and_cable_trays\" mode.",
      +  "properties": {
      +    "earthGridOhm": {
      +      "description": "Measured substation earth-grid resistance in ohms.",
      +      "minimum": 0,
      +      "type": "number"
      +    },
      +    "equipmentHeightM": {
      +      "description": "Protected outdoor equipment height in meters.",
      +      "minimum": 0,
      +      "type": "number"
      +    },
      +    "hasNeutralImpedance": {
      +      "description": "True when transformer HV neutrals are grounded through a neutral earthing reactor.",
      +      "type": "boolean"
      +    },
      +    "mastHeightM": {
      +      "description": "Lightning mast or shield wire height in meters.",
      +      "minimum": 1,
      +      "type": "number"
      +    },
      +    "trayWidthMm": {
      +      "description": "Cable tray width in millimeters for vertical/horizontal clearance lookup.",
      +      "minimum": 50,
      +      "type": "number"
      +    },
      +    "unKv": {
      +      "description": "Nominal HV system line-to-line voltage in kV (1..500 kV).",
      +      "maximum": 500,
      +      "minimum": 1,
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
  2. Changed133 schema fields changed
    • removedInput schema / properties / activeProtectionSystem
      Removed value: -{
      -  "description": "Top-level override for active deluge or water-mist protection.",
      -  "type": "string"
      -}
    • removedInput schema / properties / buildingClassification
      Removed value: -{
      -  "description": "Fire safety building occupancy regime (e.g. \"industrial_code_travail\").",
      -  "type": "string"
      -}
    • removedInput schema / properties / bundAreaM2
      Removed value: -{
      -  "description": "Top-level override for retention catch basin area in m2.",
      -  "type": "number"
      -}
    • removedInput schema / properties / deltaTMaxK
      Removed value: -{
      -  "description": "Maximum permissible room air temperature rise Delta-T in Kelvin.",
      -  "type": "number"
      -}
    • removedInput schema / properties / dielectricFluid
      Removed value: -{
      -  "description": "Top-level override for fluid chemistry (\"mineral_oil_class_o\" or ester).",
      -  "type": "string"
      -}
    • removedInput schema / properties / distanceToAdjacentTxM
      Removed value: -{
      -  "description": "Top-level override for inter-transformer spacing in meters.",
      -  "type": "number"
      -}
    • removedInput schema / properties / distanceToBuildingM
      Removed value: -{
      -  "description": "Top-level override for building setback distance in meters.",
      -  "type": "number"
      -}
    • removedInput schema / properties / drainPipeLengthM
      Removed value: -{
      -  "description": "Top-level override for retention drain pipe length in meters.",
      -  "type": "number"
      -}
    • removedInput schema / properties / emergencyExhaustAch
      Removed value: -{
      -  "description": "Emergency post-leak mechanical purge extraction rate in vol/h.",
      -  "type": "number"
      -}
    • removedInput schema / properties / equipmentFootprintM2
      Removed value: -{
      -  "description": "Total plan floor footprint occupied by switchgear bays in m2.",
      -  "type": "number"
      -}
    • removedInput schema / properties / equipmentVolumeM3
      Removed value: -{
      -  "description": "Displaced solid enclosure equipment volume deducted from free air in m3.",
      -  "type": "number"
      -}
    • removedInput schema / properties / exhaustPressureDropPa
      Removed value: -{
      -  "description": "Exhaust duct and damper aerodynamic pressure loss in Pa.",
      -  "type": "number"
      -}
    • removedInput schema / properties / exposedFacadeType
      Removed value: -{
      -  "description": "Top-level override for exposed building facade fire classification.",
      -  "type": "string"
      -}
    • removedInput schema / properties / fireDoorOrDamperRating
      Removed value: -{
      -  "description": "Compartment fire barrier rating (\"EI60\", \"EI120\", \"EI180\").",
      -  "type": "string"
      -}
    • removedInput schema / properties / frontAisleM
      Removed value: -{
      -  "description": "Clear front operator & breaker withdrawal aisle width in meters.",
      -  "type": "number"
      -}
    • removedInput schema / properties / gisRoom
      Removed value: -{
      -  "additionalProperties": true,
      -  "description": "Structured GIS / MV SF6 switchgear room geometry and gas inventory overrides.",
      -  "properties": {
      -    "emergencyExhaustAch": {
      -      "description": "Emergency post-leak mechanical purge extraction rate in vol/h.",
      -      "type": "number"
      -    },
      -    "equipmentFootprintM2": {
      -      "description": "Total plan floor footprint occupied by switchgear bays in m2.",
      -      "type": "number"
      -    },
      -    "equipmentVolumeM3": {
      -      "description": "Displaced solid enclosure equipment volume deducted from free air in m3.",
      -      "type": "number"
      -    },
      -    "frontAisleM": {
      -      "description": "Clear front operator & breaker withdrawal aisle width in meters.",
      -      "type": "number"
      -    },
      -    "hasGasDuctOrAbsorber": {
      -      "description": "True when internal arc relief vents through an external pressure duct or absorber.",
      -      "type": "boolean"
      -    },
      -    "heightM": {
      -      "description": "Enclosure interior ceiling clear height in meters.",
      -      "type": "number"
      -    },
      -    "installationType": {
      -      "description": "Gas-insulated switchgear tier (\"gis_hv\" or \"mv_sf6_switchgear\").",
      -      "enum": [
      -        "gis_hv",
      -        "mv_sf6_switchgear"
      -      ],
      -      "type": "string"
      -    },
      -    "internalArcDurationS": {
      -      "description": "Internal arc fault clearing duration in seconds.",
      -      "type": "number"
      -    },
      -    "internalArcKa": {
      -      "description": "Rated switchgear internal arc fault current magnitude in kA.",
      -      "type": "number"
      -    },
      -    "lengthM": {
      -      "description": "Enclosure interior room length in meters.",
      -      "type": "number"
      -    },
      -    "maxCompartmentSf6Kg": {
      -      "description": "Largest single pressurized gas compartment SF6 mass release in kg.",
      -      "type": "number"
      -    },
      -    "normalAch": {
      -      "description": "Continuous normal-operation air change rate in volumes/hour (vol/h).",
      -      "type": "number"
      -    },
      -    "rearAisleM": {
      -      "description": "Clear rear maintenance and gas-sampling aisle width in meters.",
      -      "type": "number"
      -    },
      -    "sideAisleM": {
      -      "description": "Clear lateral access corridor width in meters.",
      -      "type": "number"
      -    },
      -    "totalSf6Kg": {
      -      "description": "Total substation inventory mass of SF6 insulating gas in kg.",
      -      "type": "number"
      -    },
      -    "trenchVolumeM3": {
      -      "description": "Communicating below-floor cable trench air volume in m3 where dense gas pools.",
      -      "type": "number"
      -    },
      -    "wallAllowableOverpressureKpa": {
      -      "description": "Building wall/roof structural allowable transient overpressure in kPa.",
      -      "type": "number"
      -    },
      -    "widthM": {
      -      "description": "Enclosure interior room width in meters.",
      -      "type": "number"
      -    }
      -  },
      -  "type": "object"
      -}
    • removedInput schema / properties / hasFirewallRated2hOr3h
      Removed value: -{
      -  "description": "Top-level override confirming 2h/3h firewall presence.",
      -  "type": "boolean"
      -}
    • removedInput schema / properties / hasGasDuctOrAbsorber
      Removed value: -{
      -  "description": "True when internal arc relief vents through an external pressure duct or absorber.",
      -  "type": "boolean"
      -}
    • removedInput schema / properties / hasSiphon
      Removed value: -{
      -  "description": "Top-level override indicating liquid flame-trap siphon fitting.",
      -  "type": "boolean"
      -}
    • removedInput schema / properties / heightM
      Removed value: -{
      -  "description": "Enclosure interior ceiling clear height in meters.",
      -  "type": "number"
      -}
    • removedInput schema / properties / installation
      Removed value: -{
      -  "description": "Top-level override for placement (\"indoor\" or \"outdoor\").",
      -  "type": "string"
      -}
    • removedInput schema / properties / installationType
      Removed value: -{
      -  "description": "Gas-insulated switchgear tier (\"gis_hv\" or \"mv_sf6_switchgear\").",
      -  "enum": [
      -    "gis_hv",
      -    "mv_sf6_switchgear"
      -  ],
      -  "type": "string"
      -}
    • removedInput schema / properties / installedExhaustM3H
      Removed value: -{
      -  "description": "Installed mechanical smoke/heat exhaust volumetric flow rate in m3/h.",
      -  "type": "number"
      -}
    • removedInput schema / properties / installedSueM2
      Removed value: -{
      -  "description": "Installed effective natural geometric smoke vent free area SUE in m2.",
      -  "type": "number"
      -}
    • removedInput schema / properties / intakePressureDropPa
      Removed value: -{
      -  "description": "Supply intake louver/filter aerodynamic pressure loss in Pa.",
      -  "type": "number"
      -}
    • removedInput schema / properties / internalArcDurationS
      Removed value: -{
      -  "description": "Internal arc fault clearing duration in seconds.",
      -  "type": "number"
      -}
    • removedInput schema / properties / internalArcKa
      Removed value: -{
      -  "description": "Rated switchgear internal arc fault current magnitude in kA.",
      -  "type": "number"
      -}
    • removedInput schema / properties / isFm3990Approved
      Removed value: -{
      -  "description": "Top-level override indicating listed less-flammable dielectric fluid.",
      -  "type": "boolean"
      -}
    • removedInput schema / properties / lengthM
      Removed value: -{
      -  "description": "Enclosure interior room length in meters.",
      -  "type": "number"
      -}
    • removedInput schema / properties / maxCompartmentSf6Kg
      Removed value: -{
      -  "description": "Largest single pressurized gas compartment SF6 mass release in kg.",
      -  "type": "number"
      -}
    • removedInput schema / properties / nominalVoltageKv
      Removed value: -{
      -  "description": "Nominal switchgear operating voltage in kV.",
      -  "type": "number"
      -}
    • removedInput schema / properties / normalAch
      Removed value: -{
      -  "description": "Continuous normal-operation air change rate in volumes/hour (vol/h).",
      -  "type": "number"
      -}
    • removedInput schema / properties / oilVolumeLiters
      Removed value: -{
      -  "description": "Top-level override for transformer liquid volume in liters.",
      -  "type": "number"
      -}
    • changedInput schema / properties / presetId / description
      Previous value: -"Reference fire-safety & GIS substation preset identifier (e.g. \"gis_225_20kv_reference_2x85mva\")."New value: +"Reference fire-safety & substation preset identifier (defaults to \"gis_225_20kv_reference_2x85mva\")."
    • removedInput schema / properties / pressureDropMarginFactor
      Removed value: -{
      -  "description": "Fan static pressure design safety multiplier (>= 1.0).",
      -  "type": "number"
      -}
    • removedInput schema / properties / protectedBuildingAreaM2
      Removed value: -{
      -  "description": "Top-level override for protected smoke-detection room area in m2.",
      -  "type": "number"
      -}
    • removedInput schema / properties / radiatorEnvelopeAreaM2
      Removed value: -{
      -  "description": "Top-level override for spray envelope surface area in m2.",
      -  "type": "number"
      -}
    • removedInput schema / properties / rearAisleM
      Removed value: -{
      -  "description": "Clear rear maintenance and gas-sampling aisle width in meters.",
      -  "type": "number"
      -}
    • removedInput schema / properties / requiredDurationMin
      Removed value: -{
      -  "description": "Top-level override for deluge water discharge duration in minutes.",
      -  "type": "number"
      -}
    • removedInput schema / properties / retentionType
      Removed value: -{
      -  "description": "Top-level override for oil/fire-water retention pit architecture.",
      -  "type": "string"
      -}
    • removedInput schema / properties / roomType
      Removed value: -{
      -  "description": "Enclosure room role (\"transformer_vault\", \"gis_hall\", \"mv_switchroom\", \"control_room\").",
      -  "type": "string"
      -}
    • removedInput schema / properties / sideAisleM
      Removed value: -{
      -  "description": "Clear lateral access corridor width in meters.",
      -  "type": "number"
      -}
    • removedInput schema / properties / smokeExtractionMode
      Removed value: -{
      -  "description": "Smoke extraction ventilation mechanism (\"natural\" vents or \"mechanical\" fans).",
      -  "enum": [
      -    "natural",
      -    "mechanical"
      -  ],
      -  "type": "string"
      -}
    • changedInput schema / properties / smokeHvac / properties / buildingClassification / description
      Previous value: -"Fire safety building occupancy regime (e.g. \"industrial_code_travail\")."New value: +"Fire safety building occupancy class (\"erp\" for public assembly or industrial default)."
    • changedInput schema / properties / smokeHvac / properties / deltaTMaxK / description
      Previous value: -"Maximum permissible room air temperature rise Delta-T in Kelvin."New value: +"Maximum permissible room air temperature rise Delta-T in Kelvin (K)."
    • addedInput schema / properties / smokeHvac / properties / deltaTMaxK / minimum
      Added value: +1
    • changedInput schema / properties / smokeHvac / properties / exhaustPressureDropPa / description
      Previous value: -"Exhaust duct and damper aerodynamic pressure loss in Pa."New value: +"Exhaust duct and damper aerodynamic pressure loss in pascals (Pa)."
    • addedInput schema / properties / smokeHvac / properties / exhaustPressureDropPa / minimum
      Added value: +0
    • changedInput schema / properties / smokeHvac / properties / fireDoorOrDamperRating / description
      Previous value: -"Compartment fire barrier rating (\"EI60\", \"EI120\", \"EI180\")."New value: +"Compartment fire barrier resistance rating (\"EI60\", \"EI120\", \"EI180\")."
    • changedInput schema / properties / smokeHvac / properties / heightM / description
      Previous value: -"Enclosure interior ceiling clear height in meters."New value: +"Enclosure interior ceiling clear height in meters (m)."
    • addedInput schema / properties / smokeHvac / properties / heightM / minimum
      Added value: +1
    • addedInput schema / properties / smokeHvac / properties / installedExhaustM3H / minimum
      Added value: +0
    • addedInput schema / properties / smokeHvac / properties / installedSueM2 / minimum
      Added value: +0
    • changedInput schema / properties / smokeHvac / properties / intakePressureDropPa / description
      Previous value: -"Supply intake louver/filter aerodynamic pressure loss in Pa."New value: +"Supply intake louver and filter aerodynamic pressure loss in pascals (Pa)."
    • addedInput schema / properties / smokeHvac / properties / intakePressureDropPa / minimum
      Added value: +0
    • changedInput schema / properties / smokeHvac / properties / lengthM / description
      Previous value: -"Enclosure interior room length in meters."New value: +"Enclosure interior room clear length in meters (m)."
    • addedInput schema / properties / smokeHvac / properties / lengthM / minimum
      Added value: +0.5
    • addedInput schema / properties / smokeHvac / properties / normalAch / minimum
      Added value: +0
    • addedInput schema / properties / smokeHvac / properties / pressureDropMarginFactor / minimum
      Added value: +1
    • changedInput schema / properties / smokeHvac / properties / smokeExtractionMode / description
      Previous value: -"Smoke extraction ventilation mechanism (\"natural\" vents or \"mechanical\" fans)."New value: +"Smoke extraction mechanism (\"natural\" vents or \"mechanical\" fans)."
    • changedInput schema / properties / smokeHvac / properties / thermalLossesKw / description
      Previous value: -"Total continuous equipment heat rejection losses in kW."New value: +"Total continuous equipment heat rejection losses in kW (>= 0 kW)."
    • addedInput schema / properties / smokeHvac / properties / thermalLossesKw / minimum
      Added value: +0
    • changedInput schema / properties / smokeHvac / properties / widthM / description
      Previous value: -"Enclosure interior room width in meters."New value: +"Enclosure interior room clear width in meters (m)."
    • addedInput schema / properties / smokeHvac / properties / widthM / minimum
      Added value: +0.5
    • removedInput schema / properties / tankHeightM
      Removed value: -{
      -  "description": "Top-level override for tank height in meters.",
      -  "type": "number"
      -}
    • removedInput schema / properties / tankLengthM
      Removed value: -{
      -  "description": "Top-level override for tank length in meters.",
      -  "type": "number"
      -}
    • removedInput schema / properties / tankWidthM
      Removed value: -{
      -  "description": "Top-level override for tank width in meters.",
      -  "type": "number"
      -}
    • removedInput schema / properties / thermalLossesKw
      Removed value: -{
      -  "description": "Total continuous equipment heat rejection losses in kW.",
      -  "type": "number"
      -}
    • removedInput schema / properties / totalSf6Kg
      Removed value: -{
      -  "description": "Total substation inventory mass of SF6 insulating gas in kg.",
      -  "type": "number"
      -}
    • changedInput schema / properties / transformer / description
      Previous value: -"Structured transformer fire separation, deluge hydraulics, and containment inputs."New value: +"Structured transformer fire separation, deluge hydraulics, and oil containment inputs."
    • addedInput schema / properties / transformer / properties / bundAreaM2 / minimum
      Added value: +0
    • changedInput schema / properties / transformer / properties / dielectricFluid / description
      Previous value: -"Insulating fluid flammability (\"mineral_oil_class_o\", \"less_flammable_ester\")."New value: +"Insulating fluid class (\"mineral_oil_class_o\" or \"natural_ester_class_k\")."
    • changedInput schema / properties / transformer / properties / distanceToAdjacentTxM / description
      Previous value: -"Clear horizontal separation distance between adjacent transformers in meters."New value: +"Clear horizontal separation distance between adjacent transformers in meters (m)."
    • addedInput schema / properties / transformer / properties / distanceToAdjacentTxM / minimum
      Added value: +0
    • changedInput schema / properties / transformer / properties / distanceToBuildingM / description
      Previous value: -"Clear horizontal separation distance to exposed building wall in meters."New value: +"Clear horizontal separation distance to exposed building wall in meters (m)."
    • addedInput schema / properties / transformer / properties / distanceToBuildingM / minimum
      Added value: +0
    • changedInput schema / properties / transformer / properties / drainPipeLengthM / description
      Previous value: -"Gravity drain pipe length to remote separator tank in meters."New value: +"Gravity drain pipe length to remote separator tank in meters (m)."
    • addedInput schema / properties / transformer / properties / drainPipeLengthM / minimum
      Added value: +0
    • changedInput schema / properties / transformer / properties / installation / description
      Previous value: -"Physical placement (\"indoor\", \"outdoor\")."New value: +"Physical placement environment (\"indoor\" or \"outdoor\")."
    • changedInput schema / properties / transformer / properties / oilVolumeLiters / description
      Previous value: -"Total transformer dielectric liquid volume in liters."New value: +"Total transformer dielectric liquid inventory volume in liters (L)."
    • addedInput schema / properties / transformer / properties / oilVolumeLiters / minimum
      Added value: +0
    • changedInput schema / properties / transformer / properties / protectedBuildingAreaM2 / description
      Previous value: -"Protected indoor bay area covered by high-sensitivity aspirating smoke detection in m2."New value: +"Protected indoor bay area covered by aspirating smoke detection in m2."
    • addedInput schema / properties / transformer / properties / protectedBuildingAreaM2 / minimum
      Added value: +0
    • changedInput schema / properties / transformer / properties / radiatorEnvelopeAreaM2 / description
      Previous value: -"Projected spray protection envelope area incl. radiators in m2."New value: +"Projected spray protection envelope area including radiators in m2."
    • addedInput schema / properties / transformer / properties / radiatorEnvelopeAreaM2 / minimum
      Added value: +0
    • changedInput schema / properties / transformer / properties / requiredDurationMin / description
      Previous value: -"Required continuous fire-water deluge duration in minutes."New value: +"Required continuous fire-water deluge duration in minutes (min)."
    • addedInput schema / properties / transformer / properties / requiredDurationMin / minimum
      Added value: +0
    • changedInput schema / properties / transformer / properties / tankHeightM / description
      Previous value: -"Transformer tank cover height in meters."New value: +"Transformer main steel tank cover height in meters (m)."
    • addedInput schema / properties / transformer / properties / tankHeightM / minimum
      Added value: +0.1
    • changedInput schema / properties / transformer / properties / tankLengthM / description
      Previous value: -"Transformer main steel tank length in meters."New value: +"Transformer main steel tank length in meters (m)."
    • addedInput schema / properties / transformer / properties / tankLengthM / minimum
      Added value: +0.1
    • changedInput schema / properties / transformer / properties / tankWidthM / description
      Previous value: -"Transformer main steel tank width in meters."New value: +"Transformer main steel tank width in meters (m)."
    • addedInput schema / properties / transformer / properties / tankWidthM / minimum
      Added value: +0.1
    • removedInput schema / properties / transformerType
      Removed value: -{
      -  "description": "Top-level override for transformer type (\"power_transformer\", \"distribution_transformer\").",
      -  "type": "string"
      -}
    • removedInput schema / properties / trenchVolumeM3
      Removed value: -{
      -  "description": "Communicating below-floor cable trench air volume in m3 where dense gas pools.",
      -  "type": "number"
      -}
    • removedInput schema / properties / wallAllowableOverpressureKpa
      Removed value: -{
      -  "description": "Building wall/roof structural allowable transient overpressure in kPa.",
      -  "type": "number"
      -}
    • removedInput schema / properties / widthM
      Removed value: -{
      -  "description": "Enclosure interior room width in meters.",
      -  "type": "number"
      -}
    • changedOutput schema / properties / mode / description
      Previous value: -"Executed fire-safety / smoke / GIS audit mode."New value: +"Executed fire-safety, smoke extraction, or coupled site audit mode."
    • addedOutput schema / properties / presetId
      Added value: +{
      +  "description": "Resolved substation fire-safety preset identifier, or null for custom payloads.",
      +  "oneOf": [
      +    {
      +      "description": "Resolved substation fire-safety preset identifier, or null for custom payloads.",
      +      "type": "string"
      +    },
      +    {
      +      "description": "Null when no named reference preset identifier was supplied.",
      +      "type": "null"
      +    }
      +  ]
      +}
    • changedOutput schema / properties / recommendations / description
      Previous value: -"Prioritized engineering recommendations."New value: +"Prioritized engineering fire-safety and HVAC recommendations."
    • addedOutput schema / properties / recommendations / items / additionalProperties
      Added value: +true
    • changedOutput schema / properties / recommendations / items / description
      Previous value: -"Actionable fire-safety or HVAC remediation measure."New value: +"Prioritized fire, smoke, or switchgear room air safety recommendation."
    • addedOutput schema / properties / recommendations / items / properties
      Added value: +{
      +  "code": {
      +    "description": "Machine-readable recommendation finding identifier code.",
      +    "type": "string"
      +  },
      +  "detailFr": {
      +    "description": "Detailed remediation measure and physical threshold text.",
      +    "type": "string"
      +  },
      +  "domain": {
      +    "description": "Engineering subsystem domain identifier slug.",
      +    "type": "string"
      +  },
      +  "priority": {
      +    "description": "Recommendation urgency tier (\"HIGH\", \"MEDIUM\", or \"INFO\").",
      +    "type": "string"
      +  },
      +  "titleFr": {
      +    "description": "Localized concise recommendation headline summary text.",
      +    "type": "string"
      +  }
      +}
    • changedOutput schema / properties / recommendations / items / type
      Previous value: -"string"New value: +"object"
    • changedOutput schema / properties / sections / description
      Previous value: -"Per-section calculation detail maps."New value: +"Per-section calculation detail maps in full_audit mode."
    • addedOutput schema / properties / sections / properties / gisMvSf6RoomAir / properties / domain
      Added value: +{
      +  "description": "Sub-audit engineering domain identifier (\"gis_mv_sf6_room_air\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / gisMvSf6RoomAir / properties / internalArcAndFgas
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Internal-arc transient wall overpressure (kPa) and tCO2e inventory.",
      +  "properties": {
      +    "estimatedArcEnergyMj": {
      +      "description": "Estimated internal arc thermal energy released in MJ.",
      +      "type": "number"
      +    },
      +    "estimatedRoomOverpressureKpa": {
      +      "description": "Net enclosure peak overpressure after duct/absorber relief in kPa.",
      +      "type": "number"
      +    },
      +    "exceeds500tCo2eThreshold": {
      +      "description": "True when inventory exceeds 500 tCO2e leak-check reporting threshold.",
      +      "type": "boolean"
      +    },
      +    "hasGasDuctOrAbsorber": {
      +      "description": "True when switchgear vents through an external pressure duct or absorber.",
      +      "type": "boolean"
      +    },
      +    "internalArcDurationS": {
      +      "description": "Evaluated internal arc fault clearing duration in seconds (s).",
      +      "type": "number"
      +    },
      +    "internalArcKa": {
      +      "description": "Evaluated internal arc fault current magnitude in kA.",
      +      "type": "number"
      +    },
      +    "overpressureCompliant": {
      +      "description": "True when room overpressure remains below structural wall capacity.",
      +      "type": "boolean"
      +    },
      +    "totalCo2EquivalentTonnes": {
      +      "description": "Total installed SF6 greenhouse inventory in tonnes CO2 equivalent (tCO2e).",
      +      "type": "number"
      +    },
      +    "wallAllowableOverpressureKpa": {
      +      "description": "Allowable building wall/roof transient pressure limit in kPa.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / gisMvSf6RoomAir / properties / metrology
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Room dimensions, aisle clearances, and free net air volume breakdown.",
      +  "properties": {
      +    "aisleClearancesM": {
      +      "additionalProperties": true,
      +      "description": "Switchgear operating aisle clearances and compliance verdict.",
      +      "properties": {
      +        "aislesCompliant": {
      +          "description": "True when all operator and maintenance aisle widths pass.",
      +          "type": "boolean"
      +        },
      +        "frontAisleM": {
      +          "description": "Installed front operating aisle width in meters (m).",
      +          "type": "number"
      +        },
      +        "rearAisleM": {
      +          "description": "Installed rear maintenance corridor width in meters (m).",
      +          "type": "number"
      +        },
      +        "sideAisleM": {
      +          "description": "Installed lateral access aisle width in meters (m).",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "freeAirVolumeM3": {
      +      "description": "Net free mixing air volume in cubic meters (m3).",
      +      "type": "number"
      +    },
      +    "grossAreaM2": {
      +      "description": "Gross switchgear hall floor area in square meters (m2).",
      +      "type": "number"
      +    },
      +    "grossVolumeM3": {
      +      "description": "Gross switchgear hall enclosure volume in cubic meters (m3).",
      +      "type": "number"
      +    },
      +    "heightCompliant": {
      +      "description": "True when ceiling clear height meets minimum switchgear clearance.",
      +      "type": "boolean"
      +    },
      +    "installationType": {
      +      "description": "Evaluated switchgear tier (\"gis_hv\" or \"mv_sf6_switchgear\").",
      +      "type": "string"
      +    },
      +    "netOperatingAreaM2": {
      +      "description": "Net free operator floor area around bays in m2.",
      +      "type": "number"
      +    },
      +    "trenchVolumeM3": {
      +      "description": "Communicating below-floor cable trench air volume in m3.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / gisMvSf6RoomAir / properties / recommendations
      Added value: +{
      +  "description": "GIS / MV SF6 room air safety recommendations.",
      +  "items": {
      +    "additionalProperties": true,
      +    "description": "Prioritized fire, smoke, or switchgear room air safety recommendation.",
      +    "properties": {
      +      "code": {
      +        "description": "Machine-readable recommendation finding identifier code.",
      +        "type": "string"
      +      },
      +      "detailFr": {
      +        "description": "Detailed remediation measure and physical threshold text.",
      +        "type": "string"
      +      },
      +      "domain": {
      +        "description": "Engineering subsystem domain identifier slug.",
      +        "type": "string"
      +      },
      +      "priority": {
      +        "description": "Recommendation urgency tier (\"HIGH\", \"MEDIUM\", or \"INFO\").",
      +        "type": "string"
      +      },
      +      "titleFr": {
      +        "description": "Localized concise recommendation headline summary text.",
      +        "type": "string"
      +      }
      +    },
      +    "type": "object"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / gisMvSf6RoomAir / properties / score
      Added value: +{
      +  "description": "Section numerical room air safety compliance score (0..100).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / gisMvSf6RoomAir / properties / sf6DispersionAndO2
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Homogeneous vs stratified low-layer and trench SF6 ppm and O2 %.",
      +  "properties": {
      +    "homogeneousSf6Ppmv": {
      +      "description": "Well-mixed room SF6 concentration in ppmv.",
      +      "type": "number"
      +    },
      +    "maxCompartmentSf6Kg": {
      +      "description": "Largest single pressurized gas compartment SF6 mass in kg.",
      +      "type": "number"
      +    },
      +    "minSafeRoomVolumeO2M3": {
      +      "description": "Minimum free room air volume keeping O2 >= 19.5% in m3.",
      +      "type": "number"
      +    },
      +    "releasedSf6M3": {
      +      "description": "Expanded SF6 gas release volume at atmospheric pressure in m3.",
      +      "type": "number"
      +    },
      +    "residualO2HomogeneousPct": {
      +      "description": "Well-mixed residual oxygen volume concentration in % O2.",
      +      "type": "number"
      +    },
      +    "residualO2LowLayerPct": {
      +      "description": "Stratified low-layer (z <= 1.0 m) residual O2 in % O2.",
      +      "type": "number"
      +    },
      +    "residualO2TrenchPct": {
      +      "description": "Cable-trench residual oxygen concentration in % O2.",
      +      "type": "number"
      +    },
      +    "rhoSf6KgM3": {
      +      "description": "SF6 heavy gas density at ambient conditions in kg/m3 (6.17 kg/m3).",
      +      "type": "number"
      +    },
      +    "thresholdsPct": {
      +      "additionalProperties": true,
      +      "description": "Occupational oxygen depletion threshold percentages.",
      +      "properties": {
      +        "alarmN1": {
      +          "description": "First-level hypoxia alarm oxygen threshold in % (19.5%).",
      +          "type": "number"
      +        },
      +        "criticalN2": {
      +          "description": "Critical asphyxiation evacuation oxygen threshold in % (17.0%).",
      +          "type": "number"
      +        },
      +        "normal": {
      +          "description": "Normal ambient atmospheric oxygen percentage (20.9%).",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "totalSf6Kg": {
      +      "description": "Total installed SF6 inventory mass across all bays in kg.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / gisMvSf6RoomAir / properties / status
      Added value: +{
      +  "description": "GIS / MV SF6 room air verdict (\"COMPLIANT\", \"WARNING\", or \"NON_COMPLIANT\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / gisMvSf6RoomAir / properties / ventilationAndPurge
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Normal ACH, emergency low-point flow, and t_95% purge duration.",
      +  "properties": {
      +    "dualO2Sf6DetectionRequired": {
      +      "description": "True when combined O2 depletion and SF6 gas sensing is required.",
      +      "type": "boolean"
      +    },
      +    "emergencyExhaustAch": {
      +      "description": "Emergency post-leak low-point purge rate in vol/h.",
      +      "type": "number"
      +    },
      +    "emergencyFlowM3h": {
      +      "description": "Emergency purge exhaust volumetric flow in m3/h.",
      +      "type": "number"
      +    },
      +    "exposureLimitsPpm": {
      +      "additionalProperties": true,
      +      "description": "Occupational gas and arc-decomposition byproduct limits in ppmv.",
      +      "properties": {
      +        "hfNewMax": {
      +          "description": "Arc-byproduct hydrogen fluoride HF ceiling in ppmv.",
      +          "type": "number"
      +        },
      +        "sf6Vme": {
      +          "description": "Occupational SF6 exposure limit in ppmv.",
      +          "type": "number"
      +        },
      +        "sof2Vme": {
      +          "description": "Arc-byproduct thionyl fluoride SOF2 limit in ppmv.",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "lowPointExtractionMaxHeightM": {
      +      "description": "Maximum floor elevation of low-point SF6 exhaust pickup in m (0.30 m).",
      +      "type": "number"
      +    },
      +    "normalAch": {
      +      "description": "Continuous normal-operation room air change rate in vol/h.",
      +      "type": "number"
      +    },
      +    "normalFlowM3h": {
      +      "description": "Continuous normal fresh-air ventilation flow in m3/h.",
      +      "type": "number"
      +    },
      +    "purgeTime95PctMin": {
      +      "description": "Exponential 95%-dilution purge time t_95% in minutes (min).",
      +      "type": "number"
      +    },
      +    "purgeTime95PctSec": {
      +      "description": "Exponential 95%-dilution purge time t_95% in seconds (s).",
      +      "type": "number"
      +    },
      +    "zeroRecirculationRequired": {
      +      "description": "True when 100% outside-air once-through ventilation is mandatory.",
      +      "type": "boolean"
      +    }
      +  },
      +  "type": "object"
      +}
    • changedOutput schema / properties / sections / properties / smokeExtractionIt246 / description
      Previous value: -"Thermal cooling flow, SUE area, and fan delta-P output."New value: +"Thermal cooling airflow, SUE vent area, fan pressure loss, and detection output."
    • addedOutput schema / properties / sections / properties / smokeExtractionIt246 / properties / detectionAndSsiInterlocks
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Air-dilution detector spacing, aspirating detection, and fire damper interlocks.",
      +  "properties": {
      +    "damperCompliant": {
      +      "description": "True when installed fire dampers meet compartmentation rating.",
      +      "type": "boolean"
      +    },
      +    "detectorCoverageM2": {
      +      "description": "Maximum point smoke detector coverage area in m2/detector.",
      +      "type": "number"
      +    },
      +    "effectiveAch": {
      +      "description": "Effective room air change rate in volumes/hour (vol/h).",
      +      "type": "number"
      +    },
      +    "fireDoorOrDamperRating": {
      +      "description": "Evaluated fire barrier / damper resistance rating.",
      +      "type": "string"
      +    },
      +    "minPointSmokeDetectors": {
      +      "description": "Minimum required point smoke detectors for ceiling area.",
      +      "type": "integer"
      +    },
      +    "vewfdAspirationMandatory": {
      +      "description": "True when high air-change rate mandates aspirating detection.",
      +      "type": "boolean"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / smokeExtractionIt246 / properties / domain
      Added value: +{
      +  "description": "Sub-audit engineering domain identifier (\"smoke_extraction_it246\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / smokeExtractionIt246 / properties / geometry
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Enclosure geometry and smoke-layer height outputs.",
      +  "properties": {
      +    "cantonCount": {
      +      "description": "Required smoke-reservoir canton partition count.",
      +      "type": "integer"
      +    },
      +    "grossAreaM2": {
      +      "description": "Gross enclosure floor area in square meters (m2).",
      +      "type": "number"
      +    },
      +    "minClearHeightBelowSmokeM": {
      +      "description": "Minimum smoke-free clear height above floor in meters (m).",
      +      "type": "number"
      +    },
      +    "roomType": {
      +      "description": "Evaluated enclosure room role identifier.",
      +      "type": "string"
      +    },
      +    "roomVolumeM3": {
      +      "description": "Gross enclosure air volume in cubic meters (m3).",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / smokeExtractionIt246 / properties / hvacThermalAndPressureDrop
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Sensible-heat HVAC airflow, pressure loss (Pa), and fan power balance.",
      +  "properties": {
      +    "deltaTMaxK": {
      +      "description": "Maximum allowable room air temperature rise in Kelvin (K).",
      +      "type": "number"
      +    },
      +    "estimatedFanPowerKw": {
      +      "description": "Estimated absorbed aerodynamic fan shaft power in kW.",
      +      "type": "number"
      +    },
      +    "evaluatedExhaustM3h": {
      +      "description": "Evaluated fan exhaust volumetric flow rate in m3/h.",
      +      "type": "number"
      +    },
      +    "smokeExtractionMode": {
      +      "description": "Evaluated extraction mechanism (\"natural\" or \"mechanical\").",
      +      "type": "string"
      +    },
      +    "thermalFlowCompliant": {
      +      "description": "True when cooling airflow holds temperature rise within Delta-T.",
      +      "type": "boolean"
      +    },
      +    "thermalLossesKw": {
      +      "description": "Continuous equipment sensible heat dissipation in kW.",
      +      "type": "number"
      +    },
      +    "thermalVentFlowM3h": {
      +      "description": "Thermodynamic sensible cooling ventilation airflow in m3/h.",
      +      "type": "number"
      +    },
      +    "totalPressureDropPa": {
      +      "description": "Design total aerodynamic duct and louver pressure drop in Pa.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / smokeExtractionIt246 / properties / mechanicalSmokeExtraction
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Mechanical smoke exhaust fan capacity and thermal rating outputs.",
      +  "properties": {
      +    "fanRating": {
      +      "description": "Required high-temperature smoke exhaust fan thermal rating.",
      +      "type": "string"
      +    },
      +    "installedExhaustM3H": {
      +      "description": "Installed mechanical exhaust flow in m3/h, or null when omitted.",
      +      "oneOf": [
      +        {
      +          "description": "Installed mechanical exhaust flow in m3/h, or null when omitted.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is omitted or inapplicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "mechFlowCompliant": {
      +      "description": "True when mechanical smoke exhaust meets volumetric targets.",
      +      "type": "boolean"
      +    },
      +    "recommendedMakeupAirM3h": {
      +      "description": "Recommended fresh makeup airflow rate in m3/h.",
      +      "type": "number"
      +    },
      +    "requiredMechExhaustM3h": {
      +      "description": "Minimum required mechanical smoke exhaust rate in m3/h.",
      +      "type": "number"
      +    },
      +    "requiredMechExhaustM3s": {
      +      "description": "Minimum required mechanical smoke exhaust rate in m3/s.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / smokeExtractionIt246 / properties / naturalSmokeExtraction
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Natural buoyancy smoke extraction vent area requirements.",
      +  "properties": {
      +    "buildingClassification": {
      +      "description": "Applied occupancy fire-safety regime identifier.",
      +      "type": "string"
      +    },
      +    "exutorCount": {
      +      "description": "Recommended number of distributed natural smoke vents.",
      +      "type": "integer"
      +    },
      +    "installedSueM2": {
      +      "description": "Installed effective SUE vent area in m2, or null when omitted.",
      +      "oneOf": [
      +        {
      +          "description": "Installed effective SUE vent area in m2, or null when omitted.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is omitted or inapplicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "requiredGeometricAreaM2": {
      +      "description": "Minimum required geometric roof/facade vent area in m2.",
      +      "type": "number"
      +    },
      +    "requiredSueM2": {
      +      "description": "Minimum required aerodynamic smoke vent area SUE in m2.",
      +      "type": "number"
      +    },
      +    "sueCompliant": {
      +      "description": "True when installed natural smoke venting satisfies SUE rules.",
      +      "type": "boolean"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / smokeExtractionIt246 / properties / recommendations
      Added value: +{
      +  "description": "HVAC and smoke extraction recommendations.",
      +  "items": {
      +    "additionalProperties": true,
      +    "description": "Prioritized fire, smoke, or switchgear room air safety recommendation.",
      +    "properties": {
      +      "code": {
      +        "description": "Machine-readable recommendation finding identifier code.",
      +        "type": "string"
      +      },
      +      "detailFr": {
      +        "description": "Detailed remediation measure and physical threshold text.",
      +        "type": "string"
      +      },
      +      "domain": {
      +        "description": "Engineering subsystem domain identifier slug.",
      +        "type": "string"
      +      },
      +      "priority": {
      +        "description": "Recommendation urgency tier (\"HIGH\", \"MEDIUM\", or \"INFO\").",
      +        "type": "string"
      +      },
      +      "titleFr": {
      +        "description": "Localized concise recommendation headline summary text.",
      +        "type": "string"
      +      }
      +    },
      +    "type": "object"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / smokeExtractionIt246 / properties / score
      Added value: +{
      +  "description": "Section numerical HVAC and smoke-extraction compliance score (0..100).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / smokeExtractionIt246 / properties / status
      Added value: +{
      +  "description": "Smoke extraction and HVAC verdict (\"COMPLIANT\", \"WARNING\", or \"NON_COMPLIANT\").",
      +  "type": "string"
      +}
    • changedOutput schema / properties / sections / properties / transformerFm54 / description
      Previous value: -"Separation clearances, deluge spray L/min flow, and bund capacity output."New value: +"Separation clearances, deluge spray L/min flow, and oil bund capacity output."
    • addedOutput schema / properties / sections / properties / transformerFm54 / properties / delugeHydraulics
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Water deluge spray density, flow rate, and storage reserve outputs.",
      +  "properties": {
      +    "activeSystem": {
      +      "description": "Selected active fire-suppression system identifier.",
      +      "type": "string"
      +    },
      +    "bundDensityLpmM2": {
      +      "description": "Retention bund floor spray density in L/min/m2 (6.1).",
      +      "type": "number"
      +    },
      +    "delugeWaterReserveM3": {
      +      "description": "Required fire-water storage reserve volume in m3.",
      +      "type": "number"
      +    },
      +    "requiredDurationMin": {
      +      "description": "Design fire-water continuous discharge duration in minutes (min).",
      +      "type": "number"
      +    },
      +    "tankDensityLpmM2": {
      +      "description": "Transformer tank spray density in L/min/m2 (10.2).",
      +      "type": "number"
      +    },
      +    "totalDelugeFlowLpm": {
      +      "description": "Total required deluge spray flow rate in L/min.",
      +      "type": "number"
      +    },
      +    "totalDelugeFlowM3h": {
      +      "description": "Total required deluge spray flow rate in m3/h.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / transformerFm54 / properties / domain
      Added value: +{
      +  "description": "Sub-audit engineering domain identifier (\"transformer_fm5_4\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / transformerFm54 / properties / firewallDiagnostic
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Fire-barrier wall rating and overhang diagnostic summary.",
      +  "properties": {
      +    "firewallRequiredBetweenTx": {
      +      "description": "True when a fire-rated barrier is required between transformers.",
      +      "type": "boolean"
      +    },
      +    "firewallRequiredForBuilding": {
      +      "description": "True when a fire-rated barrier is required toward the building.",
      +      "type": "boolean"
      +    },
      +    "hasFirewallRated2hOr3h": {
      +      "description": "True when an installed 2h/3h fire-rated barrier is present.",
      +      "type": "boolean"
      +    },
      +    "requiredWallRating": {
      +      "description": "Required fire-resistance wall rating and deluge summary.",
      +      "type": "string"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / transformerFm54 / properties / fm54Table17
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Building facade fire-separation clearance thresholds and deficit.",
      +  "properties": {
      +    "buildingGapDeficitM": {
      +      "description": "Horizontal setback clearance shortfall to facade in meters (m).",
      +      "type": "number"
      +    },
      +    "requiredBuildingDistM": {
      +      "description": "Minimum required horizontal setback to building wall in meters (m).",
      +      "type": "number"
      +    },
      +    "tierId": {
      +      "description": "Oil volume separation tier classification identifier.",
      +      "type": "string"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / transformerFm54 / properties / fm54Table18
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Adjacent transformer fire-separation clearance thresholds and deficit.",
      +  "properties": {
      +    "requiredMinTxToTxM": {
      +      "description": "Minimum required horizontal spacing between adjacent transformers in m.",
      +      "type": "number"
      +    },
      +    "txGapDeficitM": {
      +      "description": "Inter-transformer separation distance shortfall in meters (m).",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / transformerFm54 / properties / recommendations
      Added value: +{
      +  "description": "Transformer fire-safety engineering recommendations.",
      +  "items": {
      +    "additionalProperties": true,
      +    "description": "Prioritized fire, smoke, or switchgear room air safety recommendation.",
      +    "properties": {
      +      "code": {
      +        "description": "Machine-readable recommendation finding identifier code.",
      +        "type": "string"
      +      },
      +      "detailFr": {
      +        "description": "Detailed remediation measure and physical threshold text.",
      +        "type": "string"
      +      },
      +      "domain": {
      +        "description": "Engineering subsystem domain identifier slug.",
      +        "type": "string"
      +      },
      +      "priority": {
      +        "description": "Recommendation urgency tier (\"HIGH\", \"MEDIUM\", or \"INFO\").",
      +        "type": "string"
      +      },
      +      "titleFr": {
      +        "description": "Localized concise recommendation headline summary text.",
      +        "type": "string"
      +      }
      +    },
      +    "type": "object"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / transformerFm54 / properties / retentionAndFtdt
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Oil and fire-water retention bund volume and drainage safety outputs.",
      +  "properties": {
      +    "fireWaterRetentionM3": {
      +      "description": "Fire-water volume requiring retention containment in m3.",
      +      "type": "number"
      +    },
      +    "hasSiphon": {
      +      "description": "True when a liquid flame-trap siphon is installed.",
      +      "type": "boolean"
      +    },
      +    "oilVolumeM3": {
      +      "description": "Transformer dielectric liquid inventory volume in m3.",
      +      "type": "number"
      +    },
      +    "retentionType": {
      +      "description": "Selected oil and fire-water containment system identifier.",
      +      "type": "string"
      +    },
      +    "siphonCompliant": {
      +      "description": "True when drainage flame-trap and pipe-length rules pass.",
      +      "type": "boolean"
      +    },
      +    "siphonRequired": {
      +      "description": "True when a liquid flame-trap siphon is required on gravity drains.",
      +      "type": "boolean"
      +    },
      +    "totalRetentionRequiredM3": {
      +      "description": "Combined dielectric oil and fire-water retention volume in m3.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / transformerFm54 / properties / score
      Added value: +{
      +  "description": "Section numerical fire-safety compliance score (0..100).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / transformerFm54 / properties / status
      Added value: +{
      +  "description": "Transformer fire protection verdict (\"COMPLIANT\", \"WARNING\", or \"NON_COMPLIANT\").",
      +  "type": "string"
      +}
  3. Changed68 schema fields changed
    • addedInput schema / additionalProperties
      Added value: +true
    • addedInput schema / properties / activeProtectionSystem / description
      Added value: +"Top-level override for active deluge or water-mist protection."
    • addedInput schema / properties / buildingClassification / description
      Added value: +"Fire safety building occupancy regime (e.g. \"industrial_code_travail\")."
    • addedInput schema / properties / bundAreaM2 / description
      Added value: +"Top-level override for retention catch basin area in m2."
    • addedInput schema / properties / deltaTMaxK / description
      Added value: +"Maximum permissible room air temperature rise Delta-T in Kelvin."
    • addedInput schema / properties / dielectricFluid / description
      Added value: +"Top-level override for fluid chemistry (\"mineral_oil_class_o\" or ester)."
    • addedInput schema / properties / distanceToAdjacentTxM / description
      Added value: +"Top-level override for inter-transformer spacing in meters."
    • addedInput schema / properties / distanceToBuildingM / description
      Added value: +"Top-level override for building setback distance in meters."
    • addedInput schema / properties / drainPipeLengthM / description
      Added value: +"Top-level override for retention drain pipe length in meters."
    • addedInput schema / properties / emergencyExhaustAch / description
      Added value: +"Emergency post-leak mechanical purge extraction rate in vol/h."
    • addedInput schema / properties / equipmentFootprintM2 / description
      Added value: +"Total plan floor footprint occupied by switchgear bays in m2."
    • addedInput schema / properties / equipmentVolumeM3 / description
      Added value: +"Displaced solid enclosure equipment volume deducted from free air in m3."
    • addedInput schema / properties / exhaustPressureDropPa / description
      Added value: +"Exhaust duct and damper aerodynamic pressure loss in Pa."
    • addedInput schema / properties / exposedFacadeType / description
      Added value: +"Top-level override for exposed building facade fire classification."
    • addedInput schema / properties / fireDoorOrDamperRating / description
      Added value: +"Compartment fire barrier rating (\"EI60\", \"EI120\", \"EI180\")."
    • addedInput schema / properties / frontAisleM / description
      Added value: +"Clear front operator & breaker withdrawal aisle width in meters."
    • addedInput schema / properties / gisRoom / additionalProperties
      Added value: +true
    • addedInput schema / properties / gisRoom / description
      Added value: +"Structured GIS / MV SF6 switchgear room geometry and gas inventory overrides."
    • addedInput schema / properties / gisRoom / properties
      Added value: +{
      +  "emergencyExhaustAch": {
      +    "description": "Emergency post-leak mechanical purge extraction rate in vol/h.",
      +    "type": "number"
      +  },
      +  "equipmentFootprintM2": {
      +    "description": "Total plan floor footprint occupied by switchgear bays in m2.",
      +    "type": "number"
      +  },
      +  "equipmentVolumeM3": {
      +    "description": "Displaced solid enclosure equipment volume deducted from free air in m3.",
      +    "type": "number"
      +  },
      +  "frontAisleM": {
      +    "description": "Clear front operator & breaker withdrawal aisle width in meters.",
      +    "type": "number"
      +  },
      +  "hasGasDuctOrAbsorber": {
      +    "description": "True when internal arc relief vents through an external pressure duct or absorber.",
      +    "type": "boolean"
      +  },
      +  "heightM": {
      +    "description": "Enclosure interior ceiling clear height in meters.",
      +    "type": "number"
      +  },
      +  "installationType": {
      +    "description": "Gas-insulated switchgear tier (\"gis_hv\" or \"mv_sf6_switchgear\").",
      +    "enum": [
      +      "gis_hv",
      +      "mv_sf6_switchgear"
      +    ],
      +    "type": "string"
      +  },
      +  "internalArcDurationS": {
      +    "description": "Internal arc fault clearing duration in seconds.",
      +    "type": "number"
      +  },
      +  "internalArcKa": {
      +    "description": "Rated switchgear internal arc fault current magnitude in kA.",
      +    "type": "number"
      +  },
      +  "lengthM": {
      +    "description": "Enclosure interior room length in meters.",
      +    "type": "number"
      +  },
      +  "maxCompartmentSf6Kg": {
      +    "description": "Largest single pressurized gas compartment SF6 mass release in kg.",
      +    "type": "number"
      +  },
      +  "normalAch": {
      +    "description": "Continuous normal-operation air change rate in volumes/hour (vol/h).",
      +    "type": "number"
      +  },
      +  "rearAisleM": {
      +    "description": "Clear rear maintenance and gas-sampling aisle width in meters.",
      +    "type": "number"
      +  },
      +  "sideAisleM": {
      +    "description": "Clear lateral access corridor width in meters.",
      +    "type": "number"
      +  },
      +  "totalSf6Kg": {
      +    "description": "Total substation inventory mass of SF6 insulating gas in kg.",
      +    "type": "number"
      +  },
      +  "trenchVolumeM3": {
      +    "description": "Communicating below-floor cable trench air volume in m3 where dense gas pools.",
      +    "type": "number"
      +  },
      +  "wallAllowableOverpressureKpa": {
      +    "description": "Building wall/roof structural allowable transient overpressure in kPa.",
      +    "type": "number"
      +  },
      +  "widthM": {
      +    "description": "Enclosure interior room width in meters.",
      +    "type": "number"
      +  }
      +}
    • addedInput schema / properties / hasFirewallRated2hOr3h / description
      Added value: +"Top-level override confirming 2h/3h firewall presence."
    • addedInput schema / properties / hasGasDuctOrAbsorber / description
      Added value: +"True when internal arc relief vents through an external pressure duct or absorber."
    • addedInput schema / properties / hasSiphon / description
      Added value: +"Top-level override indicating liquid flame-trap siphon fitting."
    • addedInput schema / properties / heightM / description
      Added value: +"Enclosure interior ceiling clear height in meters."
    • addedInput schema / properties / installation / description
      Added value: +"Top-level override for placement (\"indoor\" or \"outdoor\")."
    • addedInput schema / properties / installationType / description
      Added value: +"Gas-insulated switchgear tier (\"gis_hv\" or \"mv_sf6_switchgear\")."
    • addedInput schema / properties / installationType / enum
      Added value: +[
      +  "gis_hv",
      +  "mv_sf6_switchgear"
      +]
    • addedInput schema / properties / installedExhaustM3H / description
      Added value: +"Installed mechanical smoke/heat exhaust volumetric flow rate in m3/h."
    • addedInput schema / properties / installedSueM2 / description
      Added value: +"Installed effective natural geometric smoke vent free area SUE in m2."
    • addedInput schema / properties / intakePressureDropPa / description
      Added value: +"Supply intake louver/filter aerodynamic pressure loss in Pa."
    • addedInput schema / properties / internalArcDurationS / description
      Added value: +"Internal arc fault clearing duration in seconds."
    • addedInput schema / properties / internalArcKa / description
      Added value: +"Rated switchgear internal arc fault current magnitude in kA."
    • addedInput schema / properties / isFm3990Approved / description
      Added value: +"Top-level override indicating listed less-flammable dielectric fluid."
    • addedInput schema / properties / lang / default
      Added value: +"fr"
    • addedInput schema / properties / lang / description
      Added value: +"Response localization language code (\"fr\" for French or \"en\" for English, defaults to \"fr\")."
    • addedInput schema / properties / lengthM / description
      Added value: +"Enclosure interior room length in meters."
    • addedInput schema / properties / maxCompartmentSf6Kg / description
      Added value: +"Largest single pressurized gas compartment SF6 mass release in kg."
    • addedInput schema / properties / mode / default
      Added value: +"full_audit"
    • addedInput schema / properties / mode / description
      Added value: +"Fire safety domain mode or coupled three-section substation audit (defaults to \"full_audit\")."
    • addedInput schema / properties / nominalVoltageKv / description
      Added value: +"Nominal switchgear operating voltage in kV."
    • addedInput schema / properties / normalAch / description
      Added value: +"Continuous normal-operation air change rate in volumes/hour (vol/h)."
    • addedInput schema / properties / oilVolumeLiters / description
      Added value: +"Top-level override for transformer liquid volume in liters."
    • addedInput schema / properties / presetId / description
      Added value: +"Reference fire-safety & GIS substation preset identifier (e.g. \"gis_225_20kv_reference_2x85mva\")."
    • addedInput schema / properties / pressureDropMarginFactor / description
      Added value: +"Fan static pressure design safety multiplier (>= 1.0)."
    • addedInput schema / properties / protectedBuildingAreaM2 / description
      Added value: +"Top-level override for protected smoke-detection room area in m2."
    • addedInput schema / properties / radiatorEnvelopeAreaM2 / description
      Added value: +"Top-level override for spray envelope surface area in m2."
    • addedInput schema / properties / rearAisleM / description
      Added value: +"Clear rear maintenance and gas-sampling aisle width in meters."
    • addedInput schema / properties / requiredDurationMin / description
      Added value: +"Top-level override for deluge water discharge duration in minutes."
    • addedInput schema / properties / retentionType / description
      Added value: +"Top-level override for oil/fire-water retention pit architecture."
    • addedInput schema / properties / roomType / description
      Added value: +"Enclosure room role (\"transformer_vault\", \"gis_hall\", \"mv_switchroom\", \"control_room\")."
    • addedInput schema / properties / sideAisleM / description
      Added value: +"Clear lateral access corridor width in meters."
    • addedInput schema / properties / smokeExtractionMode / description
      Added value: +"Smoke extraction ventilation mechanism (\"natural\" vents or \"mechanical\" fans)."
    • addedInput schema / properties / smokeExtractionMode / enum
      Added value: +[
      +  "natural",
      +  "mechanical"
      +]
    • addedInput schema / properties / smokeHvac / additionalProperties
      Added value: +true
    • addedInput schema / properties / smokeHvac / description
      Added value: +"Structured room thermal HVAC and smoke extraction geometry overrides."
    • addedInput schema / properties / smokeHvac / properties
      Added value: +{
      +  "buildingClassification": {
      +    "description": "Fire safety building occupancy regime (e.g. \"industrial_code_travail\").",
      +    "type": "string"
      +  },
      +  "deltaTMaxK": {
      +    "description": "Maximum permissible room air temperature rise Delta-T in Kelvin.",
      +    "type": "number"
      +  },
      +  "exhaustPressureDropPa": {
      +    "description": "Exhaust duct and damper aerodynamic pressure loss in Pa.",
      +    "type": "number"
      +  },
      +  "fireDoorOrDamperRating": {
      +    "description": "Compartment fire barrier rating (\"EI60\", \"EI120\", \"EI180\").",
      +    "type": "string"
      +  },
      +  "heightM": {
      +    "description": "Enclosure interior ceiling clear height in meters.",
      +    "type": "number"
      +  },
      +  "installedExhaustM3H": {
      +    "description": "Installed mechanical smoke/heat exhaust volumetric flow rate in m3/h.",
      +    "type": "number"
      +  },
      +  "installedSueM2": {
      +    "description": "Installed effective natural geometric smoke vent free area SUE in m2.",
      +    "type": "number"
      +  },
      +  "intakePressureDropPa": {
      +    "description": "Supply intake louver/filter aerodynamic pressure loss in Pa.",
      +    "type": "number"
      +  },
      +  "lengthM": {
      +    "description": "Enclosure interior room length in meters.",
      +    "type": "number"
      +  },
      +  "normalAch": {
      +    "description": "Continuous normal-operation air change rate in volumes/hour (vol/h).",
      +    "type": "number"
      +  },
      +  "pressureDropMarginFactor": {
      +    "description": "Fan static pressure design safety multiplier (>= 1.0).",
      +    "type": "number"
      +  },
      +  "roomType": {
      +    "description": "Enclosure room role (\"transformer_vault\", \"gis_hall\", \"mv_switchroom\", \"control_room\").",
      +    "type": "string"
      +  },
      +  "smokeExtractionMode": {
      +    "description": "Smoke extraction ventilation mechanism (\"natural\" vents or \"mechanical\" fans).",
      +    "enum": [
      +      "natural",
      +      "mechanical"
      +    ],
      +    "type": "string"
      +  },
      +  "thermalLossesKw": {
      +    "description": "Total continuous equipment heat rejection losses in kW.",
      +    "type": "number"
      +  },
      +  "widthM": {
      +    "description": "Enclosure interior room width in meters.",
      +    "type": "number"
      +  }
      +}
    • addedInput schema / properties / tankHeightM / description
      Added value: +"Top-level override for tank height in meters."
    • addedInput schema / properties / tankLengthM / description
      Added value: +"Top-level override for tank length in meters."
    • addedInput schema / properties / tankWidthM / description
      Added value: +"Top-level override for tank width in meters."
    • addedInput schema / properties / thermalLossesKw / description
      Added value: +"Total continuous equipment heat rejection losses in kW."
    • addedInput schema / properties / totalSf6Kg / description
      Added value: +"Total substation inventory mass of SF6 insulating gas in kg."
    • addedInput schema / properties / transformer / additionalProperties
      Added value: +true
    • addedInput schema / properties / transformer / description
      Added value: +"Structured transformer fire separation, deluge hydraulics, and containment inputs."
    • addedInput schema / properties / transformer / properties
      Added value: +{
      +  "activeProtectionSystem": {
      +    "description": "Active fire suppression (\"deluge_water_spray\", \"water_mist\", \"none\").",
      +    "type": "string"
      +  },
      +  "bundAreaM2": {
      +    "description": "Open retention bund catch-basin surface area in m2.",
      +    "type": "number"
      +  },
      +  "dielectricFluid": {
      +    "description": "Insulating fluid flammability (\"mineral_oil_class_o\", \"less_flammable_ester\").",
      +    "type": "string"
      +  },
      +  "distanceToAdjacentTxM": {
      +    "description": "Clear horizontal separation distance between adjacent transformers in meters.",
      +    "type": "number"
      +  },
      +  "distanceToBuildingM": {
      +    "description": "Clear horizontal separation distance to exposed building wall in meters.",
      +    "type": "number"
      +  },
      +  "drainPipeLengthM": {
      +    "description": "Gravity drain pipe length to remote separator tank in meters.",
      +    "type": "number"
      +  },
      +  "exposedFacadeType": {
      +    "description": "Wall construction facing transformer (\"combustible\", \"non_combustible\", \"fire_rated_2h_3h\").",
      +    "type": "string"
      +  },
      +  "hasFirewallRated2hOr3h": {
      +    "description": "True if a certified 2h/3h fire-rated barrier separates the transformer.",
      +    "type": "boolean"
      +  },
      +  "hasSiphon": {
      +    "description": "True when a liquid flame-trap siphon seals the drainage discharge.",
      +    "type": "boolean"
      +  },
      +  "installation": {
      +    "description": "Physical placement (\"indoor\", \"outdoor\").",
      +    "type": "string"
      +  },
      +  "isFm3990Approved": {
      +    "description": "True if filled with a listed less-flammable high-fire-point fluid.",
      +    "type": "boolean"
      +  },
      +  "oilVolumeLiters": {
      +    "description": "Total transformer dielectric liquid volume in liters.",
      +    "type": "number"
      +  },
      +  "protectedBuildingAreaM2": {
      +    "description": "Protected indoor bay area covered by high-sensitivity aspirating smoke detection in m2.",
      +    "type": "number"
      +  },
      +  "radiatorEnvelopeAreaM2": {
      +    "description": "Projected spray protection envelope area incl. radiators in m2.",
      +    "type": "number"
      +  },
      +  "requiredDurationMin": {
      +    "description": "Required continuous fire-water deluge duration in minutes.",
      +    "type": "number"
      +  },
      +  "retentionType": {
      +    "description": "Containment system (\"baffle_extinguishing_bund\", \"remote_impounding\", \"open_pit\").",
      +    "type": "string"
      +  },
      +  "tankHeightM": {
      +    "description": "Transformer tank cover height in meters.",
      +    "type": "number"
      +  },
      +  "tankLengthM": {
      +    "description": "Transformer main steel tank length in meters.",
      +    "type": "number"
      +  },
      +  "tankWidthM": {
      +    "description": "Transformer main steel tank width in meters.",
      +    "type": "number"
      +  },
      +  "transformerType": {
      +    "description": "Transformer class (\"power_transformer\", \"distribution_transformer\").",
      +    "type": "string"
      +  }
      +}
    • addedInput schema / properties / transformerType / description
      Added value: +"Top-level override for transformer type (\"power_transformer\", \"distribution_transformer\")."
    • addedInput schema / properties / trenchVolumeM3 / description
      Added value: +"Communicating below-floor cable trench air volume in m3 where dense gas pools."
    • addedInput schema / properties / wallAllowableOverpressureKpa / description
      Added value: +"Building wall/roof structural allowable transient overpressure in kPa."
    • addedInput schema / properties / widthM / description
      Added value: +"Enclosure interior room width in meters."
    • changedOutput schema / (root)
      Previous value: -nullNew value: +{
      +  "additionalProperties": true,
      +  "description": "Substation fire separation, retention bund, smoke extraction, and GIS safety audit with calculationTrace and legalNotice.",
      +  "properties": {
      +    "calculationTrace": {
      +      "additionalProperties": true,
      +      "description": "Transparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.",
      +      "properties": {
      +        "defaultsApplied": {
      +          "additionalProperties": true,
      +          "description": "Default physical or engineering assumptions injected when optional inputs were omitted.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "engineeringAssumptions": {
      +          "description": "Explicit boundary assumptions required to interpret the numerical output.",
      +          "items": {
      +            "description": "Boundary condition or validity assumption for the calculation.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "formulasAndConstants": {
      +          "additionalProperties": true,
      +          "description": "Mathematical formulas and SI physical constants bound to this calculation mode.",
      +          "properties": {
      +            "constants": {
      +              "additionalProperties": true,
      +              "description": "Map of physical constants, resistivities, and design coefficients in SI units.",
      +              "properties": {},
      +              "type": "object"
      +            },
      +            "formulas": {
      +              "description": "Ordered list of physical equations evaluated by the calculation engine.",
      +              "items": {
      +                "description": "Symbolic engineering formula string used during evaluation.",
      +                "type": "string"
      +              },
      +              "type": "array"
      +            }
      +          },
      +          "type": "object"
      +        },
      +        "inputsProvided": {
      +          "additionalProperties": true,
      +          "description": "Non-empty normalized input parameters explicitly supplied by the caller.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "mode": {
      +          "description": "Normalized calculation mode executed for the current payload.",
      +          "type": "string"
      +        },
      +        "physicalPrinciples": {
      +          "description": "Key physical principles governing the computed result.",
      +          "items": {
      +            "description": "Concise statement of an underlying electrical or thermal principle.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "tool": {
      +          "description": "Resolved Brain tool identifier audited by the calculation tracer.",
      +          "type": "string"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "complianceScore": {
      +      "description": "Composite numerical safety compliance score (0..100).",
      +      "type": "number"
      +    },
      +    "legalNotice": {
      +      "description": "Informational engineering compliance notice confirming SI physical scope and intellectual property rules.",
      +      "type": "string"
      +    },
      +    "mode": {
      +      "description": "Executed fire-safety / smoke / GIS audit mode.",
      +      "type": "string"
      +    },
      +    "overallStatus": {
      +      "description": "Aggregated pass/warning/non-compliant safety verdict.",
      +      "type": "string"
      +    },
      +    "recommendations": {
      +      "description": "Prioritized engineering recommendations.",
      +      "items": {
      +        "description": "Actionable fire-safety or HVAC remediation measure.",
      +        "type": "string"
      +      },
      +      "type": "array"
      +    },
      +    "sections": {
      +      "additionalProperties": true,
      +      "description": "Per-section calculation detail maps.",
      +      "properties": {
      +        "gisMvSf6RoomAir": {
      +          "additionalProperties": true,
      +          "description": "SF6 gas stratification, O2 %, and purge time balance output.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "smokeExtractionIt246": {
      +          "additionalProperties": true,
      +          "description": "Thermal cooling flow, SUE area, and fan delta-P output.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "transformerFm54": {
      +          "additionalProperties": true,
      +          "description": "Separation clearances, deluge spray L/min flow, and bund capacity output.",
      +          "properties": {},
      +          "type": "object"
      +        }
      +      },
      +      "type": "object"
      +    }
      +  },
      +  "type": "object"
      +}
  4. First observed

TDQS

A4.4/5.0
Behavior4/5

Does the description disclose side effects, auth requirements, rate limits, or destructive behavior?

Beyond the readOnly/idempotent/destructive annotations, it discloses statelessness, determinism, that up to three coupled solvers run in one SI pass, that invalid payload types raise JSON-RPC -32602, and the exact default values applied to omitted inputs. It does not discuss computational cost, runtime, or any limits on input size, which is the only material gap for a multi-solver tool.

Agents need to know what a tool does to the world before calling it. Descriptions should go beyond structured annotations to explain consequences.

Conciseness4/5

Is the description appropriately sized, front-loaded, and free of redundancy?

The definition is front-loaded and clearly partitioned with 'When to use', 'Do not use for', 'Behavior', and 'Returns' labels, so an agent can scan to the needed section. The first sentence is a long laundry list of domains with inline unit constants that could be tightened, but every clause still carries routing or scoping information.

Shorter descriptions cost fewer tokens and are easier for agents to parse. Every sentence should earn its place.

Completeness5/5

Given the tool's complexity, does the description cover enough for an agent to succeed on first attempt?

For a six-parameter, deeply nested, mode-switched calculator, the definition covers purpose, mode semantics, defaults, error behavior, and sibling routing. An output schema exists, and the description still names the top-level return fields (overallStatus, complianceScore, sections, calculationTrace, legalNotice), which is more than required.

Complex tools with many parameters or behaviors need more documentation. Simple tools need less. This dimension scales expectations accordingly.

Parameters3/5

Does the description clarify parameter syntax, constraints, interactions, or defaults beyond what the schema provides?

Schema description coverage is 100% with detailed per-property descriptions, defaults, units, and enums, so the schema already carries the semantic load. The description restates the three top-level defaults (mode, lang, presetId) and the mode family, but adds no new meaning for the nested transformer, smokeHvac, or surgeAndTrays fields beyond the schema.

Input schemas describe structure but not intent. Descriptions should explain non-obvious parameter relationships and valid value ranges.

Purpose5/5

Does the description clearly state what the tool does and how it differs from similar tools?

The opening sentence names specific verbs and resources: transformer fire separation clearances, deluge spray hydraulics, bund retention volume, HVAC thermal cooling, smoke extraction SUE, and coupled site safety. It also names the sibling (brain_audit_gis_mv_room_air_sf6) it is not, so an agent can distinguish it without opening either schema.

Agents choose between tools based on descriptions. A clear purpose with a specific verb and resource helps agents select the right tool.

Usage Guidelines5/5

Does the description explain when to use this tool, when not to, or what alternatives exist?

It has an explicit 'When to use' clause listing four scenario families (oil-fire protection, bund containment, HVAC smoke extraction, coupled site audits) and an explicit 'Do not use for' clause that routes standalone indoor GIS/MV SF6 airflow and O2 audits to a named alternative. Nothing is left to inference.

Agents often have multiple tools that could apply. Explicit usage guidance like "use X instead of Y when Z" prevents misuse.

Try in Browser

Glama MCP Gateway

Add one secure layer between your agents and this server.

Resources