addedInput schema / properties / decrementFactorDf / minimum
Added value: +1
addedInput schema / properties / faultCurrentKa / minimum
Added value: +0
changedInput schema / properties / faultDurationSec / description
Previous value: -"Earth fault clearing duration tk in seconds."New value: +"Earth fault clearing duration tk in seconds (>= 0.01)."
addedInput schema / properties / faultDurationSec / minimum
Added value: +0.01
changedInput schema / properties / ik1Ka / description
Previous value: -"Single-phase-to-earth fault current Ik1 in kA."New value: +"Single-phase-to-earth fault current Ik1 in kA (>= 0)."
addedInput schema / properties / ik1Ka / minimum
Added value: +0
changedInput schema / properties / mechanicalMinSectionMm2 / description
Previous value: -"Explicit minimum mechanical cross-section floor in mm2."New value: +"Explicit minimum mechanical cross-section floor in mm2 (>= 1)."
addedInput schema / properties / mechanicalMinSectionMm2 / minimum
Added value: +1
changedInput schema / properties / nominalVoltageKv / description
Previous value: -"Nominal system voltage Un in kV."New value: +"Nominal system line-to-line voltage Un in kV (positive)."
addedInput schema / properties / nominalVoltageKv / minimum
Added value: +0.1
changedInput schema / properties / proposedSectionsMm2 / items / description
Previous value: -"Candidate standard conductor cross-section in mm2."New value: +"Candidate standard conductor cross-section in mm2 (>= 1)."
addedInput schema / properties / proposedSectionsMm2 / items / minimum
Added value: +1
changedInput schema / properties / ratedVoltageUrKv / description
Previous value: -"Switchgear or surge arrester rated voltage Ur in kV."New value: +"Switchgear or surge arrester rated voltage Ur in kV (positive)."
addedInput schema / properties / ratedVoltageUrKv / minimum
Added value: +0.1
changedInput schema / properties / soilResistivityOhmM / description
Previous value: -"Equivalent site soil electrical resistivity rho in ohm*m."New value: +"Equivalent site soil electrical resistivity rho in ohm*m (>= 1)."
addedInput schema / properties / soilResistivityOhmM / minimum
Added value: +1
changedInput schema / properties / splitFactor / description
Previous value: -"Earth return current split/reduction factor rf in [0, 1]."New value: +"Earth return current split/reduction factor rf bounded in [0, 1]."
addedInput schema / properties / splitFactor / maximum
Added value: +1
addedInput schema / properties / splitFactor / minimum
Added value: +0
addedInput schema / properties / xrRatio / minimum
Added value: +0.1
changedOutput schema / properties / criticalFindings / items / description
Previous value: -"Blocking earthing or insulation violation."New value: +"Blocking earthing or insulation violation code."
addedOutput schema / properties / earthingAudit / properties / decisionStatus
Added value: +{
+ "description": "Human-readable earthing safety verdict tag.",
+ "type": "string"
+}
addedOutput schema / properties / earthingAudit / properties / earthingConductor
Added value: +{
+ "additionalProperties": true,
+ "description": "Adiabatic earthing conductor thermal and mechanical sizing audit.",
+ "properties": {
+ "actualSectionMm2": {
+ "description": "Installed or selected conductor cross-section in mm2.",
+ "type": "number"
+ },
+ "conductorCompliant": {
+ "description": "True when conductor cross-section meets limits.",
+ "type": "boolean"
+ },
+ "material": {
+ "description": "Evaluated earthing conductor material code.",
+ "type": "string"
+ },
+ "minMechanicalSectionMm2": {
+ "description": "Mechanical floor cross-section in mm2.",
+ "type": "number"
+ },
+ "minRequiredSectionMm2": {
+ "description": "Governing minimum required strap section in mm2.",
+ "type": "number"
+ },
+ "minThermalSectionMm2": {
+ "description": "Adiabatic thermal minimum cross-section in mm2.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / earthingAudit / properties / eprToUtpRatio
Added value: +{
+ "description": "Ratio of substation EPR to permissible UTp.",
+ "type": "number"
+}
addedOutput schema / properties / earthingAudit / properties / eprVolt
Added value: +{
+ "description": "Computed substation Ground Potential Rise (EPR) in volts.",
+ "type": "number"
+}
addedOutput schema / properties / earthingAudit / properties / explicitTouchSafe
Added value: +{
+ "description": "True when prospective touch voltage stays below limit.",
+ "type": "boolean"
+}
addedOutput schema / properties / earthingAudit / properties / iEarthKa
Added value: +{
+ "description": "Effective substation ground-grid fault current Ig in kA.",
+ "type": "number"
+}
addedOutput schema / properties / earthingAudit / properties / isCompliant
Added value: +{
+ "description": "True when substation earthing safety audit passes.",
+ "type": "boolean"
+}
addedOutput schema / properties / earthingAudit / properties / isGlobalEarthingSystem
Added value: +{
+ "description": "True when site qualifies as a Global Earthing System.",
+ "type": "boolean"
+}
addedOutput schema / properties / earthingAudit / properties / lvTransferAudit
Added value: +{
+ "additionalProperties": true,
+ "description": "Low-voltage neutral transfer potential verification.",
+ "properties": {
+ "limitVolt": {
+ "description": "Allowable transferred stress voltage limit in volts.",
+ "type": "number"
+ },
+ "lvSystem": {
+ "description": "Downstream LV earthing topology code.",
+ "type": "string"
+ },
+ "lvTransferSafe": {
+ "description": "True when EPR remains below LV stress transfer limit.",
+ "type": "boolean"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / earthingAudit / properties / neutralEarthing
Added value: +{
+ "description": "System neutral earthing regime classification.",
+ "type": "string"
+}
addedOutput schema / properties / earthingAudit / properties / stationEarthingResistanceOhm
Added value: +{
+ "description": "Combined substation earthing grid impedance in ohms.",
+ "type": "number"
+}
addedOutput schema / properties / earthingAudit / properties / touchAndStep
Added value: +{
+ "additionalProperties": true,
+ "description": "Human body touch and step voltage attenuation limits.",
+ "properties": {
+ "bodyCurrentLimitMa": {
+ "description": "Permissible ventricular fibrillation current limit in mA.",
+ "type": "number"
+ },
+ "bodyImpedanceZtOhm": {
+ "description": "Human body impedance Zt in ohms.",
+ "type": "number"
+ },
+ "faultDurationSec": {
+ "description": "Applied clearing duration for body current curve in seconds.",
+ "type": "number"
+ },
+ "prospectiveStepLimitUvSpVolt": {
+ "description": "Permissible prospective step voltage limit with gravel in V.",
+ "type": "number"
+ },
+ "prospectiveTouchLimitUvTpVolt": {
+ "description": "Permissible prospective touch voltage limit with gravel in V.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / earthingAudit / properties / utpVolt
Added value: +{
+ "description": "Allowable bare-contact body touch voltage threshold UTp in volts.",
+ "type": "number"
+}
addedOutput schema / properties / lightningRisk / properties / isCompliant
Added value: +{
+ "description": "True when total lightning risk R1 <= RT.",
+ "type": "boolean"
+}
addedOutput schema / properties / lightningRisk / properties / lpsClass
Added value: +{
+ "description": "Evaluated Lightning Protection System class (\"I\"..\"IV\").",
+ "type": "string"
+}
addedOutput schema / properties / lightningRisk / properties / ngFlashesPerKm2Year
Added value: +{
+ "description": "Site ground flash density Ng in flashes/km2/year.",
+ "type": "number"
+}
addedOutput schema / properties / lightningRisk / properties / r1Total
Added value: +{
+ "description": "Total annual risk R1 across direct and indirect strikes.",
+ "type": "number"
+}
addedOutput schema / properties / lightningRisk / properties / recommendedLpl
Added value: +{
+ "description": "Minimum required lightning protection level class.",
+ "type": "string"
+}
addedOutput schema / properties / lightningRisk / properties / riskRatioToRT
Added value: +{
+ "description": "Ratio of computed structural risk R1 to tolerable RT.",
+ "type": "number"
+}
addedOutput schema / properties / lightningRisk / properties / spdProtectionLevel
Added value: +{
+ "description": "Assigned Surge Protective Device coordination level.",
+ "type": "string"
+}
addedOutput schema / properties / lightningRisk / properties / tolerableRiskRT
Added value: +{
+ "description": "Tolerable annual loss-of-life risk threshold RT.",
+ "type": "number"
+}
changedOutput schema / properties / mode / description
Previous value: -"Executed earthing/lightning/TRV mode."New value: +"Executed earthing, lightning, or TRV sub-study mode."
addedOutput schema / properties / trvAudit / properties / isCompliant
Added value: +{
+ "description": "True when system TRV stays inside breaker rated envelope.",
+ "type": "boolean"
+}
addedOutput schema / properties / trvAudit / properties / limitingCriterion
Added value: +{
+ "description": "Tightest TRV stress margin parameter.",
+ "type": "string"
+}
addedOutput schema / properties / trvAudit / properties / margins
Added value: +{
+ "additionalProperties": true,
+ "description": "Breaker TRV safety margins relative to rated envelope.",
+ "properties": {
+ "peakUcMarginPct": {
+ "description": "Margin on peak TRV crest Uc (%).",
+ "type": "number"
+ },
+ "rrrvMarginPct": {
+ "description": "Margin on initial TRV slope RRRV (%).",
+ "type": "number"
+ },
+ "u1MarginPct": {
+ "description": "Margin on first reference voltage u1 (%).",
+ "type": "number"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / trvAudit / properties / minMarginPct
Added value: +{
+ "description": "Minimum margin across TRV envelope checks (%).",
+ "type": "number"
+}
addedOutput schema / properties / trvAudit / properties / ratedEnvelope
Added value: +{
+ "additionalProperties": true,
+ "description": "Switchgear rated TRV withstand envelope.",
+ "properties": {
+ "kaf": {
+ "description": "Recovery peak amplitude factor kaf (dimensionless).",
+ "type": "number"
+ },
+ "kpp": {
+ "description": "First-pole-to-clear factor kpp (dimensionless).",
+ "type": "number"
+ },
+ "parameterMode": {
+ "description": "Two-parameter or four-parameter TRV representation.",
+ "type": "string"
+ },
+ "ratedUrKv": {
+ "description": "Breaker rated voltage Ur in kV.",
+ "type": "number"
+ },
+ "rrrvKvPerUs": {
+ "description": "Rated initial rate of rise of recovery voltage in kV/us.",
+ "type": "number"
+ },
+ "t1Us": {
+ "description": "Rated knee time t1 in microseconds (us).",
+ "type": "number"
+ },
+ "t2Us": {
+ "description": "Rated peak time t2 in microseconds (us).",
+ "type": "number"
+ },
+ "testDuty": {
+ "description": "Evaluated TRV switching test duty code.",
+ "type": "string"
+ },
+ "u1Kv": {
+ "description": "Rated four-parameter knee voltage u1 in kV.",
+ "type": "number"
+ },
+ "ucKv": {
+ "description": "Rated crest recovery voltage uc in kV.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / trvAudit / properties / systemTrv
Added value: +{
+ "additionalProperties": true,
+ "description": "System transient recovery voltage stress profile.",
+ "properties": {
+ "faultCurrentKa": {
+ "description": "Evaluated fault breaking current in kA.",
+ "type": "number"
+ },
+ "faultRatioPct": {
+ "description": "Fault current ratio vs rated breaking capacity (%).",
+ "type": "number"
+ },
+ "rrrvKvPerUs": {
+ "description": "Prospective system RRRV slope in kV/us.",
+ "type": "number"
+ },
+ "u1Kv": {
+ "description": "Prospective initial recovery knee voltage u1 in kV.",
+ "type": "number"
+ },
+ "ucKv": {
+ "description": "Prospective system TRV crest voltage uc in kV.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+}