Critical Power Auxiliaries, Battery & PUE Calculator

brain_calc_critical_power_safety
Read-onlyIdempotent

Run deterministic critical-power and safety physics models: genset altitude-temperature derating and load steps, UPS autonomy and STS phase-sync transfer, Faraday electrolysis H2 battery ventilation, LV/MV EMC tray separation, pebble-bed transformer retention pits, and data center PUE/REF metrics. When to use: Use for emergency power auxiliaries, battery rooms, oil containment, and facility PUE/REF sizing. Do not use for: Markov availability trees or transformer oil DGA -- call brain_calc_system_reliability or brain_calc_transformer_ecodesign_dga instead. Behavior: Runs up to six coupled physical solvers in a stateless, read-only SI pass with zero mutations; non-object inputs raise JSON-RPC -32602, while omitted arguments default to mode="audit" with the HYPERSCALE_DC_2N_CLASS4 preset. Returns: mode, metadata, sections, summary, calculationTrace, and legalNotice.

Tool call template

This tool declares no required parameters. Add optional parameters from the input schema as needed.

{
  "id": 1,
  "jsonrpc": "2.0",
  "method": "tools/call",
  "params": {
    "arguments": {},
    "name": "brain_calc_critical_power_safety"
  }
}

Input Schema

NameRequiredDescriptionDefault
modeNoCritical power engineering sub-domain selector or full 6-section audit (defaults to "audit").audit
gensetNoEmergency generator set derating, fuel autonomy, and step-loading inputs.
presetIdNoReference critical-power facility preset ID (e.g. "HYPERSCALE_DC_2N_CLASS4").
upsAndStsNoUPS sizing, upstream source matching, and Static Transfer Switch synchronization inputs.
dataCenterNoData center PUE, Renewable Energy Factor (REF), and facility robustness inputs.
batteryRoomNoBattery room Faraday electrolysis H2 emission and dilution airflow inputs.
emcSeparationNoPower-vs-telemetry cable electromagnetic interference separation audit inputs.
transformerPitNoOil-filled transformer retention pit, pebble-bed flame arrestor, and fire-water volume inputs.

Output Schema

NameRequiredDescriptionDefault
modeNoExecuted critical power audit or single-section calculation mode.
summaryNoOverall pass/fail flags across all evaluated critical-power subsystems.
metadataNoSelected preset title and evaluation scope metadata.
sectionsNoPer-section detailed physics outputs.
legalNoticeNoInformational engineering compliance notice confirming SI physical scope and intellectual property rules.
calculationTraceNoTransparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.

Schema Changelog

Changes observed during successful MCP inspections.

  1. Changed212 schema fields changed
    • addedInput schema / properties / batteryRoom / properties / cellCount / default
      Added value: +240
    • changedInput schema / properties / batteryRoom / properties / cellCount / description
      Previous value: -"Total series-connected 2 V or 1.2 V electrochemical cells."New value: +"Total series-connected 2 V or 1.2 V electrochemical cells (defaults to 240)."
    • addedInput schema / properties / batteryRoom / properties / chargeMode / default
      Added value: +"BOOST"
    • changedInput schema / properties / batteryRoom / properties / chargeMode / description
      Previous value: -"Worst-case gassing regime (\"FLOAT\", \"BOOST\")."New value: +"Worst-case gassing regime (\"FLOAT\" or \"BOOST\", defaults to \"BOOST\")."
    • addedInput schema / properties / batteryRoom / properties / hasHydrogenDetector / default
      Added value: +false
    • changedInput schema / properties / batteryRoom / properties / hasHydrogenDetector / description
      Previous value: -"True when LEL catalytic/MOS hydrogen gas monitoring is installed."New value: +"True when LEL catalytic/MOS hydrogen gas monitoring is installed (defaults to false)."
    • changedInput schema / properties / batteryRoom / properties / installedAirflowM3H / description
      Previous value: -"Provided continuous battery room exhaust airflow in m3/h."New value: +"Provided continuous battery room exhaust airflow in m3/h (>= 0)."
    • addedInput schema / properties / batteryRoom / properties / installedAirflowM3H / minimum
      Added value: +0
    • changedInput schema / properties / batteryRoom / properties / installedInletAreaCm2 / description
      Previous value: -"Low-level fresh air intake grille net free area in cm2."New value: +"Low-level fresh air intake grille net free area in cm2 (>= 0)."
    • addedInput schema / properties / batteryRoom / properties / installedInletAreaCm2 / minimum
      Added value: +0
    • addedInput schema / properties / batteryRoom / properties / nominalCapacityAh / default
      Added value: +400
    • changedInput schema / properties / batteryRoom / properties / nominalCapacityAh / description
      Previous value: -"Battery string C10/C20 capacity per string in Ah."New value: +"Battery string C10/C20 capacity per string in Ah (defaults to 400 Ah)."
    • addedInput schema / properties / batteryRoom / properties / nominalCapacityAh / minimum
      Added value: +1
    • addedInput schema / properties / batteryRoom / properties / technology / default
      Added value: +"VRLA"
    • changedInput schema / properties / batteryRoom / properties / technology / description
      Previous value: -"Electrochemical battery type (\"VRLA\", \"FLOODED_LEAD_ACID\", \"NICD\", \"LFP\")."New value: +"Electrochemical battery type (\"VRLA\", \"FLOODED_LEAD_ACID\", \"NICD\", \"LFP\", defaults to \"VRLA\")."
    • changedInput schema / properties / dataCenter / properties / coolingEnergyMwh / description
      Previous value: -"Annual HVAC chiller & CRAH mechanical cooling energy in MWh."New value: +"Annual HVAC chiller and CRAH cooling energy in MWh (defaults to 25% of IT energy)."
    • addedInput schema / properties / dataCenter / properties / coolingEnergyMwh / minimum
      Added value: +0
    • addedInput schema / properties / dataCenter / properties / coolingRedundancy / default
      Added value: +"N"
    • changedInput schema / properties / dataCenter / properties / coolingRedundancy / description
      Previous value: -"Mechanical cooling path redundancy (\"N\", \"N+1\", \"2N\")."New value: +"Mechanical cooling path redundancy (\"N\", \"N+1\", or \"2N\", defaults to \"N\")."
    • addedInput schema / properties / dataCenter / properties / itEnergyMwh / default
      Added value: +10000
    • changedInput schema / properties / dataCenter / properties / itEnergyMwh / description
      Previous value: -"Annual IT equipment energy consumption in MWh."New value: +"Annual IT equipment energy consumption in MWh (defaults to 10000 MWh)."
    • addedInput schema / properties / dataCenter / properties / itEnergyMwh / minimum
      Added value: +0.001
    • changedInput schema / properties / dataCenter / properties / lightingAndOtherMwh / description
      Previous value: -"Annual auxiliary lighting & security energy in MWh."New value: +"Annual auxiliary lighting and security energy in MWh (defaults to 2% of IT energy)."
    • addedInput schema / properties / dataCenter / properties / lightingAndOtherMwh / minimum
      Added value: +0
    • addedInput schema / properties / dataCenter / properties / onsiteRenewableConsumedMwh / default
      Added value: +0
    • changedInput schema / properties / dataCenter / properties / onsiteRenewableConsumedMwh / description
      Previous value: -"Annual on-site renewable energy generated & consumed in MWh."New value: +"Annual on-site renewable energy generated and consumed in MWh (defaults to 0)."
    • addedInput schema / properties / dataCenter / properties / onsiteRenewableConsumedMwh / minimum
      Added value: +0
    • changedInput schema / properties / dataCenter / properties / powerDistributionLossMwh / description
      Previous value: -"Annual UPS/PDU/transformer electrical loss in MWh."New value: +"Annual UPS/PDU/transformer electrical loss in MWh (defaults to 8% of IT energy)."
    • addedInput schema / properties / dataCenter / properties / powerDistributionLossMwh / minimum
      Added value: +0
    • addedInput schema / properties / dataCenter / properties / powerRedundancy / default
      Added value: +"N"
    • changedInput schema / properties / dataCenter / properties / powerRedundancy / description
      Previous value: -"Electrical distribution path topology (\"N\", \"N+1\", \"2N\")."New value: +"Electrical distribution path topology (\"N\", \"N+1\", or \"2N\", defaults to \"N\")."
    • addedInput schema / properties / dataCenter / properties / targetAvailabilityClass / default
      Added value: +3
    • changedInput schema / properties / dataCenter / properties / targetAvailabilityClass / description
      Previous value: -"Target facility availability robustness class (1..4)."New value: +"Target facility availability robustness class (1..4, defaults to 3)."
    • addedInput schema / properties / emcSeparation / properties / barrierType / default
      Added value: +"NONE"
    • changedInput schema / properties / emcSeparation / properties / barrierType / description
      Previous value: -"Metallic tray shielding class (\"NONE\", \"PERFORATED_STEEL_TRAY\", \"SOLID_STEEL_CONDUIT\")."New value: +"Metallic tray shielding class (\"NONE\", \"PERFORATED_STEEL_TRAY\", \"SOLID_STEEL_CONDUIT\", defaults to \"NONE\")."
    • addedInput schema / properties / emcSeparation / properties / installationContext / default
      Added value: +"INDOOR_TRAY"
    • changedInput schema / properties / emcSeparation / properties / installationContext / description
      Previous value: -"Cable routing support (\"INDOOR_TRAY\", \"UNDERGROUND_DUCT\")."New value: +"Cable routing support (\"INDOOR_TRAY\" or \"UNDERGROUND_DUCT\", defaults to \"INDOOR_TRAY\")."
    • changedInput schema / properties / emcSeparation / properties / installedSeparationMm / description
      Previous value: -"Actual center-to-center or clear spacing to signal cables in mm."New value: +"Actual center-to-center or clear spacing to signal cables in mm (>= 0)."
    • addedInput schema / properties / emcSeparation / properties / installedSeparationMm / minimum
      Added value: +0
    • addedInput schema / properties / emcSeparation / properties / lowCurrentMedium / default
      Added value: +"COPPER_SCREENED_CAT5E_6"
    • changedInput schema / properties / emcSeparation / properties / lowCurrentMedium / description
      Previous value: -"Sensitive data medium (\"COPPER_UNSCREENED\", \"COPPER_SCREENED_CAT5E_6\", \"FIBER\")."New value: +"Sensitive data medium (\"COPPER_UNSCREENED\", \"COPPER_SCREENED_CAT5E_6\", \"FIBER\", defaults to \"COPPER_SCREENED_CAT5E_6\")."
    • changedInput schema / properties / emcSeparation / properties / powerSystemTier / description
      Previous value: -"Adjacent power feeder tier (\"LV\", \"HTA\")."New value: +"Adjacent power feeder tier (\"LV\", \"HTA\", or \"HTB\")."
    • changedInput schema / properties / emcSeparation / properties / powerVoltageKv / description
      Previous value: -"Power cable operating voltage in kV."New value: +"Power cable operating voltage in kV (>= 0 kV)."
    • addedInput schema / properties / emcSeparation / properties / powerVoltageKv / minimum
      Added value: +0
    • addedInput schema / properties / genset / properties / altitudeM / default
      Added value: +150
    • changedInput schema / properties / genset / properties / altitudeM / description
      Previous value: -"Site elevation above sea level in meters for air-density derating."New value: +"Site elevation above sea level in meters for air-density derating (defaults to 150 m)."
    • addedInput schema / properties / genset / properties / altitudeM / maximum
      Added value: +5000
    • addedInput schema / properties / genset / properties / altitudeM / minimum
      Added value: +0
    • addedInput schema / properties / genset / properties / ambientTempC / default
      Added value: +25
    • changedInput schema / properties / genset / properties / ambientTempC / description
      Previous value: -"Intake combustion & cooling air temperature in deg C."New value: +"Intake combustion and cooling air temperature in deg C (defaults to 25 C)."
    • addedInput schema / properties / genset / properties / ambientTempC / maximum
      Added value: +65
    • addedInput schema / properties / genset / properties / ambientTempC / minimum
      Added value: +-30
    • changedInput schema / properties / genset / properties / fuelAutonomyHours / description
      Previous value: -"On-site day/bulk fuel storage autonomy in hours."New value: +"On-site day or bulk fuel storage autonomy in hours (>= 0 h)."
    • addedInput schema / properties / genset / properties / fuelAutonomyHours / minimum
      Added value: +0
    • addedInput schema / properties / genset / properties / fuelType / default
      Added value: +"DIESEL"
    • changedInput schema / properties / genset / properties / fuelType / description
      Previous value: -"Prime mover fuel chemistry (\"DIESEL\", \"NATURAL_GAS\", \"HVO\")."New value: +"Prime mover fuel chemistry (\"DIESEL\", \"NATURAL_GAS\", or \"HVO\", defaults to \"DIESEL\")."
    • changedInput schema / properties / genset / properties / loadSteps / items / properties / id / description
      Previous value: -"Block loading step identifier."New value: +"Block loading step identifier string."
    • changedInput schema / properties / genset / properties / loadSteps / items / properties / stepKw / description
      Previous value: -"Step active load addition in kW."New value: +"Step active load addition in kW (>= 0 kW)."
    • addedInput schema / properties / genset / properties / loadSteps / items / properties / stepKw / minimum
      Added value: +0
    • changedInput schema / properties / genset / properties / loadSteps / items / properties / stepPowerFactor / description
      Previous value: -"Step load power factor cos(phi)."New value: +"Step load power factor cos(phi) in (0.1..1.0]."
    • addedInput schema / properties / genset / properties / loadSteps / items / properties / stepPowerFactor / maximum
      Added value: +1
    • addedInput schema / properties / genset / properties / loadSteps / items / properties / stepPowerFactor / minimum
      Added value: +0.1
    • addedInput schema / properties / genset / properties / nominalFrequencyHz / default
      Added value: +50
    • changedInput schema / properties / genset / properties / nominalFrequencyHz / description
      Previous value: -"Nominal electrical output frequency in Hz (50 or 60)."New value: +"Nominal electrical output frequency in Hz (50 or 60, defaults to 50 Hz)."
    • addedInput schema / properties / genset / properties / nominalFrequencyHz / maximum
      Added value: +70
    • addedInput schema / properties / genset / properties / nominalFrequencyHz / minimum
      Added value: +40
    • addedInput schema / properties / genset / properties / performanceClass / default
      Added value: +"G2"
    • changedInput schema / properties / genset / properties / performanceClass / description
      Previous value: -"Transient load-acceptance performance class (\"G1\", \"G2\", \"G3\", \"G4\")."New value: +"Transient load-acceptance performance class (\"G1\", \"G2\", \"G3\", \"G4\", defaults to \"G2\")."
    • changedInput schema / properties / genset / properties / ratedActivePowerKw / description
      Previous value: -"ISO standard nameplate active power rating in kW."New value: +"ISO standard nameplate active power rating in kW (>= 1 kW)."
    • addedInput schema / properties / genset / properties / ratedActivePowerKw / minimum
      Added value: +1
    • changedInput schema / properties / genset / properties / ratedApparentKva / description
      Previous value: -"Alternator rated apparent power in kVA."New value: +"Alternator rated apparent power in kVA (>= 1 kVA)."
    • addedInput schema / properties / genset / properties / ratedApparentKva / minimum
      Added value: +1
    • addedInput schema / properties / genset / properties / ratingType / default
      Added value: +"ESP"
    • changedInput schema / properties / genset / properties / ratingType / description
      Previous value: -"Duty rating class (\"ESP\", \"PRP\", \"COP\")."New value: +"Duty rating class (\"ESP\", \"PRP\", or \"COP\", defaults to \"ESP\")."
    • addedInput schema / properties / transformerPit / properties / pebbleBedThicknessM / default
      Added value: +0.3
    • changedInput schema / properties / transformerPit / properties / pebbleBedThicknessM / description
      Previous value: -"Quenching pebble bed gravel thickness in meters."New value: +"Quenching pebble bed gravel thickness in meters (defaults to 0.3 m)."
    • addedInput schema / properties / transformerPit / properties / pebbleBedThicknessM / minimum
      Added value: +0
    • addedInput schema / properties / transformerPit / properties / pitArchitecture / default
      Added value: +"PEBBLE_BED_INTEGRATED"
    • changedInput schema / properties / transformerPit / properties / pitArchitecture / description
      Previous value: -"Pit flame-quenching type (\"PEBBLE_BED_INTEGRATED\", \"OPEN_BUND_REMOTE_TANK\")."New value: +"Pit flame-quenching type (\"PEBBLE_BED_INTEGRATED\" or \"OPEN_BUND_REMOTE_TANK\", defaults to \"PEBBLE_BED_INTEGRATED\")."
    • addedInput schema / properties / transformerPit / properties / pitDepthM / default
      Added value: +1
    • changedInput schema / properties / transformerPit / properties / pitDepthM / description
      Previous value: -"Retention basin net clear depth in meters."New value: +"Retention basin net clear depth in meters (defaults to 1.0 m)."
    • addedInput schema / properties / transformerPit / properties / pitDepthM / minimum
      Added value: +0
    • addedInput schema / properties / transformerPit / properties / pitFootprintLengthM / default
      Added value: +10
    • changedInput schema / properties / transformerPit / properties / pitFootprintLengthM / description
      Previous value: -"Retention basin net interior length in meters."New value: +"Retention basin net interior length in meters (defaults to 10 m)."
    • addedInput schema / properties / transformerPit / properties / pitFootprintLengthM / minimum
      Added value: +0.5
    • addedInput schema / properties / transformerPit / properties / pitFootprintWidthM / default
      Added value: +7
    • changedInput schema / properties / transformerPit / properties / pitFootprintWidthM / description
      Previous value: -"Retention basin net interior width in meters."New value: +"Retention basin net interior width in meters (defaults to 7 m)."
    • addedInput schema / properties / transformerPit / properties / pitFootprintWidthM / minimum
      Added value: +0.5
    • addedInput schema / properties / transformerPit / properties / remoteTankVolumeM3 / default
      Added value: +0
    • changedInput schema / properties / transformerPit / properties / remoteTankVolumeM3 / description
      Previous value: -"Downstream remote containment tank capacity in m3."New value: +"Downstream remote containment tank capacity in m3 (defaults to 0 m3)."
    • addedInput schema / properties / transformerPit / properties / remoteTankVolumeM3 / minimum
      Added value: +0
    • addedInput schema / properties / transformerPit / properties / retentionRule / default
      Added value: +"SINGLE_PIT_100PCT"
    • changedInput schema / properties / transformerPit / properties / retentionRule / description
      Previous value: -"Containment rule (\"SINGLE_PIT_100PCT\", \"MULTI_PIT\")."New value: +"Containment rule (\"SINGLE_PIT_100PCT\" or \"MULTI_PIT\", defaults to \"SINGLE_PIT_100PCT\")."
    • changedInput schema / properties / transformerPit / properties / transformers / items / properties / dielectricOilVolumeM3 / description
      Previous value: -"Liquid dielectric oil volume in m3."New value: +"Liquid dielectric oil volume in m3 (>= 0 m3)."
    • addedInput schema / properties / transformerPit / properties / transformers / items / properties / dielectricOilVolumeM3 / minimum
      Added value: +0
    • changedInput schema / properties / transformerPit / properties / transformers / items / properties / id / description
      Previous value: -"Transformer tag inside catchment zone."New value: +"Transformer equipment tag inside catchment zone."
    • changedInput schema / properties / transformerPit / properties / transformers / items / properties / powerMva / description
      Previous value: -"Transformer rated apparent power in MVA."New value: +"Transformer rated apparent power in MVA (>= 0 MVA)."
    • addedInput schema / properties / transformerPit / properties / transformers / items / properties / powerMva / minimum
      Added value: +0
    • changedInput schema / properties / upsAndSts / properties / activeLoadKw / description
      Previous value: -"Protected critical IT/industrial active load in kW."New value: +"Protected critical IT or industrial active load in kW (>= 0.5 kW)."
    • addedInput schema / properties / upsAndSts / properties / activeLoadKw / minimum
      Added value: +0.5
    • addedInput schema / properties / upsAndSts / properties / autonomyMinutes / default
      Added value: +15
    • changedInput schema / properties / upsAndSts / properties / autonomyMinutes / description
      Previous value: -"Target full-load DC battery ride-through time in minutes."New value: +"Target full-load DC battery ride-through time in minutes (defaults to 15 min)."
    • addedInput schema / properties / upsAndSts / properties / autonomyMinutes / minimum
      Added value: +1
    • addedInput schema / properties / upsAndSts / properties / dcNominalVoltageV / default
      Added value: +480
    • changedInput schema / properties / upsAndSts / properties / dcNominalVoltageV / description
      Previous value: -"Intermediate UPS DC battery bus voltage in V."New value: +"Intermediate UPS DC battery bus voltage in V (defaults to 480 V)."
    • addedInput schema / properties / upsAndSts / properties / dcNominalVoltageV / minimum
      Added value: +24
    • addedInput schema / properties / upsAndSts / properties / redundancyMode / default
      Added value: +"N"
    • changedInput schema / properties / upsAndSts / properties / redundancyMode / description
      Previous value: -"Power train redundancy configuration (\"N\", \"N+1\", \"2N\")."New value: +"Power train redundancy configuration (\"N\", \"N+1\", or \"2N\", defaults to \"N\")."
    • addedInput schema / properties / upsAndSts / properties / stsPhaseSyncDeg / default
      Added value: +4
    • changedInput schema / properties / upsAndSts / properties / stsPhaseSyncDeg / description
      Previous value: -"Phase angle difference tolerance window between sources in degrees."New value: +"Phase angle difference tolerance window between sources in degrees (defaults to 4 deg)."
    • addedInput schema / properties / upsAndSts / properties / stsPhaseSyncDeg / maximum
      Added value: +180
    • addedInput schema / properties / upsAndSts / properties / stsPhaseSyncDeg / minimum
      Added value: +0
    • addedInput schema / properties / upsAndSts / properties / stsPresent / default
      Added value: +false
    • changedInput schema / properties / upsAndSts / properties / stsPresent / description
      Previous value: -"True when a Static Transfer Switch selects between A/B sources."New value: +"True when a Static Transfer Switch selects between A/B sources (defaults to false)."
    • addedInput schema / properties / upsAndSts / properties / stsTransferTimeMs / default
      Added value: +4
    • changedInput schema / properties / upsAndSts / properties / stsTransferTimeMs / description
      Previous value: -"STS break/make solid-state transfer duration in ms."New value: +"STS break/make solid-state transfer duration in ms (defaults to 4 ms)."
    • addedInput schema / properties / upsAndSts / properties / stsTransferTimeMs / minimum
      Added value: +0
    • addedInput schema / properties / upsAndSts / properties / upsEfficiency / default
      Added value: +0.95
    • changedInput schema / properties / upsAndSts / properties / upsEfficiency / description
      Previous value: -"Double-conversion efficiency ratio in (0, 1]."New value: +"Double-conversion efficiency ratio in (0.5..1.0] (defaults to 0.95)."
    • addedInput schema / properties / upsAndSts / properties / upsEfficiency / maximum
      Added value: +1
    • addedInput schema / properties / upsAndSts / properties / upsEfficiency / minimum
      Added value: +0.5
    • addedInput schema / properties / upsAndSts / properties / upsTopology / default
      Added value: +"ONLINE_DOUBLE_CONVERSION"
    • changedInput schema / properties / upsAndSts / properties / upsTopology / description
      Previous value: -"UPS conversion architecture (\"ONLINE_DOUBLE_CONVERSION\", \"LINE_INTERACTIVE\")."New value: +"UPS conversion architecture (\"ONLINE_DOUBLE_CONVERSION\", \"LINE_INTERACTIVE\", defaults to \"ONLINE_DOUBLE_CONVERSION\")."
    • addedOutput schema / properties / metadata / properties / presetId
      Added value: +{
      +  "description": "Resolved facility study preset identifier or \"CUSTOM_AUDIT\".",
      +  "type": "string"
      +}
    • addedOutput schema / properties / metadata / properties / standardsCovered
      Added value: +{
      +  "description": "List of analytical physics domains evaluated in this audit.",
      +  "items": {
      +    "description": "Sanitized analytical model label covered by the audit.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / metadata / properties / titleEn
      Added value: +{
      +  "description": "Localized English title describing the audited critical-power scope.",
      +  "type": "string"
      +}
    • addedOutput schema / properties / metadata / properties / titleFr
      Added value: +{
      +  "description": "Localized French title describing the audited critical-power scope.",
      +  "type": "string"
      +}
    • changedOutput schema / properties / mode / description
      Previous value: -"Executed critical power audit mode."New value: +"Executed critical power audit or single-section calculation mode."
    • addedOutput schema / properties / sections / properties / batteryRoom / properties / atexSafetyDistance
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Near-cell hydrogen dilution safety distance outputs.",
      +  "properties": {
      +    "equivalentQFactorCoeffM": {
      +      "description": "Equivalent airflow-based distance coefficient in m.",
      +      "type": "number"
      +    },
      +    "safetyDistanceCm": {
      +      "description": "Minimum explosive zone dilution distance in cm.",
      +      "type": "number"
      +    },
      +    "safetyDistanceM": {
      +      "description": "Minimum explosive zone dilution distance in m.",
      +      "type": "number"
      +    },
      +    "safetyDistanceMm": {
      +      "description": "Minimum explosive zone dilution distance in mm.",
      +      "type": "number"
      +    },
      +    "unitNote": {
      +      "description": "Dimensional equation note confirming millimeter/meter units.",
      +      "type": "string"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / batteryRoom / properties / batteryConfig
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Battery bank gassing parameter summary.",
      +  "properties": {
      +    "cellCount": {
      +      "description": "Total series electrochemical cells in room.",
      +      "type": "integer"
      +    },
      +    "cellsPerMonobloc": {
      +      "description": "Series cells packaged per battery monobloc.",
      +      "type": "number"
      +    },
      +    "chargeMode": {
      +      "description": "Evaluated charging regime (\"FLOAT\" or \"BOOST\").",
      +      "type": "string"
      +    },
      +    "igasApplied": {
      +      "description": "Applied electrolysis gassing factor in mA/Ah.",
      +      "type": "number"
      +    },
      +    "igasBoost": {
      +      "description": "Boost regime electrolysis gassing factor in mA/Ah.",
      +      "type": "number"
      +    },
      +    "igasFloat": {
      +      "description": "Float regime electrolysis gassing factor in mA/Ah.",
      +      "type": "number"
      +    },
      +    "nominalCapacityAh": {
      +      "description": "Battery string rated C10/C20 capacity in Ah.",
      +      "type": "number"
      +    },
      +    "technology": {
      +      "description": "Evaluated battery cell chemistry string.",
      +      "type": "string"
      +    },
      +    "tempDensityFactor": {
      +      "description": "Temperature-density gas volume correction factor.",
      +      "type": "number"
      +    },
      +    "ventsPerCell": {
      +      "description": "Gas relief vent openings per individual cell.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / batteryRoom / properties / compliant
      Added value: +{
      +  "description": "True when this subsystem satisfies all physical limits.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / sections / properties / batteryRoom / properties / icpe2925
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Battery charging power threshold and compartment fire rating checks.",
      +  "properties": {
      +    "applicableRubric": {
      +      "description": "Applicable environmental threshold classification code.",
      +      "type": "string"
      +    },
      +    "dcChargingPowerKw": {
      +      "description": "Total DC charging power in kW.",
      +      "type": "number"
      +    },
      +    "declarationRequired": {
      +      "description": "True when charging power exceeds regulatory threshold.",
      +      "type": "boolean"
      +    },
      +    "declarationThresholdKw": {
      +      "description": "Regulatory power declaration threshold in kW.",
      +      "type": "number"
      +    },
      +    "firewallReiMinutes": {
      +      "description": "Minimum compartment fire barrier duration in minutes.",
      +      "type": "number"
      +    },
      +    "minPropertySetbackM": {
      +      "description": "Minimum setback distance to property line in meters.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / batteryRoom / properties / recommendations
      Added value: +{
      +  "description": "List of subsystem design recommendations.",
      +  "items": {
      +    "description": "Recommended engineering mitigation action.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / batteryRoom / properties / standards
      Added value: +{
      +  "description": "Applicable analytical model scope declarations.",
      +  "items": {
      +    "description": "Physical calculation scope label in SI units.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / batteryRoom / properties / status
      Added value: +{
      +  "description": "Subsystem verdict string (\"COMPLIANT\", \"WARNING\", or \"NON_COMPLIANT\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / batteryRoom / properties / ventilation
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Faraday H2 dilution airflow and natural grille area requirements.",
      +  "properties": {
      +    "boostAirflowM3H": {
      +      "description": "Required dilution airflow under boost regime in m3/h.",
      +      "type": "number"
      +    },
      +    "floatAirflowM3H": {
      +      "description": "Required dilution airflow under float regime in m3/h.",
      +      "type": "number"
      +    },
      +    "minNaturalInletAreaCm2": {
      +      "description": "Minimum free fresh-air intake grille area in cm2.",
      +      "type": "number"
      +    },
      +    "minNaturalOutletAreaCm2": {
      +      "description": "Minimum free exhaust outlet grille area in cm2.",
      +      "type": "number"
      +    },
      +    "requiredAirflowM3H": {
      +      "description": "Required continuous H2 dilution exhaust airflow in m3/h.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / batteryRoom / properties / violations
      Added value: +{
      +  "description": "List of blocking subsystem violations.",
      +  "items": {
      +    "description": "Blocking physical limit violation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / batteryRoom / properties / warnings
      Added value: +{
      +  "description": "List of non-blocking subsystem warnings.",
      +  "items": {
      +    "description": "Advisory engineering observation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / dataCenter / properties / compliant
      Added value: +{
      +  "description": "True when this subsystem satisfies all physical limits.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / sections / properties / dataCenter / properties / en50600Audit
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Facility multi-path availability class verification results.",
      +  "properties": {
      +    "achievedAvailabilityClass": {
      +      "description": "Achieved facility availability class (1..4).",
      +      "type": "integer"
      +    },
      +    "coolingRedundancy": {
      +      "description": "Evaluated cooling redundancy string.",
      +      "type": "string"
      +    },
      +    "energyGranularityLevel": {
      +      "description": "Evaluated facility energy metering granularity level.",
      +      "type": "number"
      +    },
      +    "powerRedundancy": {
      +      "description": "Evaluated electrical power redundancy string.",
      +      "type": "string"
      +    },
      +    "protectionClass": {
      +      "description": "Evaluated physical protection class (1..4).",
      +      "type": "integer"
      +    },
      +    "targetAvailabilityClass": {
      +      "description": "Requested facility availability class (1..4).",
      +      "type": "integer"
      +    },
      +    "targetLabelEn": {
      +      "description": "English label for target availability class.",
      +      "type": "string"
      +    },
      +    "targetLabelFr": {
      +      "description": "French label for target availability class.",
      +      "type": "string"
      +    },
      +    "utilityFeedsCount": {
      +      "description": "Count of independent utility power feeds.",
      +      "type": "integer"
      +    },
      +    "utilityFeedsSeparationM": {
      +      "description": "Physical separation between utility feeds in m.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / dataCenter / properties / pueMetrics
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Power Usage Effectiveness and DCiE energy efficiency metrics.",
      +  "properties": {
      +    "category": {
      +      "description": "Power Usage Effectiveness metering granularity category (1..3).",
      +      "type": "integer"
      +    },
      +    "dciePct": {
      +      "description": "Data Center Infrastructure Efficiency in %.",
      +      "type": "number"
      +    },
      +    "designPue": {
      +      "description": "Design PUE ratio when design telemetry provided, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Design PUE ratio when design telemetry provided, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "interimPue": {
      +      "description": "Interim PUE ratio when interim telemetry provided, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Interim PUE ratio when interim telemetry provided, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "itEnergyMwh": {
      +      "description": "Annual IT equipment energy consumption in MWh.",
      +      "type": "number"
      +    },
      +    "partialPueCooling": {
      +      "description": "Partial PUE for cooling systems, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Partial PUE for cooling systems, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "partialPuePower": {
      +      "description": "Partial PUE for power conversion, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Partial PUE for power conversion, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "pue": {
      +      "description": "Computed Power Usage Effectiveness ratio (>= 1.0).",
      +      "type": "number"
      +    },
      +    "totalDcEnergyMwh": {
      +      "description": "Total annual data center facility energy in MWh.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / dataCenter / properties / recommendations
      Added value: +{
      +  "description": "List of subsystem design recommendations.",
      +  "items": {
      +    "description": "Recommended engineering mitigation action.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / dataCenter / properties / refMetrics
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Renewable Energy Factor (REF) accounting breakdown.",
      +  "properties": {
      +    "gridRenewableMwh": {
      +      "description": "Grid-supplied renewable energy fraction in MWh.",
      +      "type": "number"
      +    },
      +    "onsiteRenewableMwh": {
      +      "description": "On-site consumed renewable energy in MWh.",
      +      "type": "number"
      +    },
      +    "rawRenewableRatio": {
      +      "description": "Uncapped renewable energy share ratio.",
      +      "type": "number"
      +    },
      +    "ref": {
      +      "description": "Capped Renewable Energy Factor in [0..1].",
      +      "type": "number"
      +    },
      +    "refPct": {
      +      "description": "Renewable Energy Factor expressed as percentage (%).",
      +      "type": "number"
      +    },
      +    "retiredCertificatesMwh": {
      +      "description": "Retired renewable energy certificates in MWh.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / dataCenter / properties / standards
      Added value: +{
      +  "description": "Applicable analytical model scope declarations.",
      +  "items": {
      +    "description": "Physical calculation scope label in SI units.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / dataCenter / properties / status
      Added value: +{
      +  "description": "Subsystem verdict string (\"COMPLIANT\", \"WARNING\", or \"NON_COMPLIANT\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / dataCenter / properties / violations
      Added value: +{
      +  "description": "List of blocking subsystem violations.",
      +  "items": {
      +    "description": "Blocking physical limit violation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / dataCenter / properties / warnings
      Added value: +{
      +  "description": "List of non-blocking subsystem warnings.",
      +  "items": {
      +    "description": "Advisory engineering observation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / aluminumMaterial
      Added value: +{
      +  "description": "True when aluminum containment material applies.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / barrierAttenuationRatio
      Added value: +{
      +  "description": "Metallic tray shielding distance reduction factor.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / barrierType
      Added value: +{
      +  "description": "Metallic tray or conduit attenuation barrier type.",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / buriedMinimumMm
      Added value: +{
      +  "description": "Minimum underground trench separation floor in mm.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / compliant
      Added value: +{
      +  "description": "True when this subsystem satisfies all physical limits.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / emiSourceMinSeparationMm
      Added value: +{
      +  "description": "Minimum setback from localized EMI sources in mm.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / eprSafetyDistanceM
      Added value: +{
      +  "description": "Buried earth potential rise separation in m, or null.",
      +  "oneOf": [
      +    {
      +      "description": "Buried earth potential rise separation in m, or null.",
      +      "type": "number"
      +    },
      +    {
      +      "description": "Null when value is not applicable in active mode.",
      +      "type": "null"
      +    }
      +  ]
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / installationContext
      Added value: +{
      +  "description": "Evaluated cable routing context (\"INDOOR_TRAY\" or buried).",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / isDielectricOpticalImmune
      Added value: +{
      +  "description": "True for dielectric optical fiber immune to EMI.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / lowCurrentMedium
      Added value: +{
      +  "description": "Evaluated telemetry/control cable medium identifier.",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / powerCircuit20AEquiv
      Added value: +{
      +  "description": "Equivalent 20 A power circuit count weighting factor.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / powerFactorP
      Added value: +{
      +  "description": "Bundled power circuit loading multiplier p.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / powerSystemTier
      Added value: +{
      +  "description": "Adjacent power voltage tier (\"BT\", \"HTA\", or \"HTB\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / powerVoltageKv
      Added value: +{
      +  "description": "Adjacent power circuit operating voltage in kV.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / recommendations
      Added value: +{
      +  "description": "List of subsystem design recommendations.",
      +  "items": {
      +    "description": "Recommended engineering mitigation action.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / requiredSeparationMm
      Added value: +{
      +  "description": "Minimum required power-to-signal separation in mm.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / segregationClass
      Added value: +{
      +  "description": "Resolved EMC cable segregation class (\"a\"..\"d\" or optical).",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / standards
      Added value: +{
      +  "description": "Applicable analytical model scope declarations.",
      +  "items": {
      +    "description": "Physical calculation scope label in SI units.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / status
      Added value: +{
      +  "description": "Subsystem verdict string (\"COMPLIANT\", \"WARNING\", or \"NON_COMPLIANT\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / tierVoltageMarginMm
      Added value: +{
      +  "description": "Additional high-voltage tier separation margin in mm.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / unshieldedBaseMm
      Added value: +{
      +  "description": "Unshielded reference separation distance in mm.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / violations
      Added value: +{
      +  "description": "List of blocking subsystem violations.",
      +  "items": {
      +    "description": "Blocking physical limit violation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / emcSeparation / properties / warnings
      Added value: +{
      +  "description": "List of non-blocking subsystem warnings.",
      +  "items": {
      +    "description": "Advisory engineering observation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / bmepAndStepCapability
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "BMEP-based step load-acceptance capability thresholds.",
      +  "properties": {
      +    "pmeKpa": {
      +      "description": "Engine brake mean effective pressure BMEP in kPa.",
      +      "type": "number"
      +    },
      +    "step1MaxPct": {
      +      "description": "Maximum allowable first load-acceptance step in %.",
      +      "type": "number"
      +    },
      +    "step2MaxPct": {
      +      "description": "Maximum allowable second load-acceptance step in %.",
      +      "type": "number"
      +    },
      +    "step3MaxPct": {
      +      "description": "Maximum allowable third load-acceptance step in %.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / compliant
      Added value: +{
      +  "description": "True when this subsystem satisfies all physical limits.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / gssCompliance
      Added value: +{
      +  "description": "Safety genset autonomy and transfer audit, or null.",
      +  "oneOf": [
      +    {
      +      "additionalProperties": true,
      +      "description": "Safety genset autonomy and transfer audit, or null.",
      +      "properties": {
      +        "code": {
      +          "description": "Evaluated safety genset class code.",
      +          "type": "string"
      +        },
      +        "fuelAutonomyH": {
      +          "description": "On-site fuel autonomy in hours.",
      +          "type": "number"
      +        },
      +        "fuelAutonomyOk": {
      +          "description": "True when fuel autonomy passes limit.",
      +          "type": "boolean"
      +        },
      +        "startDelayOk": {
      +          "description": "True when start delay passes limit.",
      +          "type": "boolean"
      +        },
      +        "startDelayS": {
      +          "description": "Start and transfer delay in seconds.",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    {
      +      "description": "Null when optional sub-audit is not enabled.",
      +      "type": "null"
      +    }
      +  ]
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / performanceLimits
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Performance class and transient tolerance limits.",
      +  "properties": {
      +    "classCode": {
      +      "description": "Transient performance class (\"G1\"..\"G4\").",
      +      "type": "string"
      +    },
      +    "gssClass": {
      +      "description": "Safety genset class code (\"NONE\" or \"GSS1\"..\"GSS4\").",
      +      "type": "string"
      +    },
      +    "limits": {
      +      "additionalProperties": true,
      +      "description": "Frequency and voltage transient ceiling parameters.",
      +      "properties": {
      +        "freqBandMaxPct": {
      +          "description": "Maximum steady-state frequency band limit in %.",
      +          "type": "number"
      +        },
      +        "freqDroopMaxPct": {
      +          "description": "Maximum steady-state frequency droop limit in %.",
      +          "type": "number"
      +        },
      +        "freqDynDropMaxPct": {
      +          "description": "Maximum transient frequency drop limit in %.",
      +          "type": "number"
      +        },
      +        "freqDynDropWithDroopMaxPct": {
      +          "description": "Combined transient drop plus droop ceiling in %.",
      +          "type": "number"
      +        },
      +        "freqDynRiseMaxPct": {
      +          "description": "Maximum transient frequency overshoot limit in %.",
      +          "type": "number"
      +        },
      +        "freqRecoveryMaxS": {
      +          "description": "Maximum frequency recovery time in seconds.",
      +          "type": "number"
      +        },
      +        "voltDynDropMaxPct": {
      +          "description": "Maximum transient voltage dip limit in %.",
      +          "type": "number"
      +        },
      +        "voltDynRiseMaxPct": {
      +          "description": "Maximum transient voltage rise limit in %.",
      +          "type": "number"
      +        },
      +        "voltModulationMaxPct": {
      +          "description": "Maximum cyclic voltage modulation envelope in %.",
      +          "type": "number"
      +        },
      +        "voltRecoveryMaxS": {
      +          "description": "Maximum voltage recovery time in seconds.",
      +          "type": "number"
      +        },
      +        "voltSteadyMaxPct": {
      +          "description": "Maximum steady-state voltage deviation limit in %.",
      +          "type": "number"
      +        },
      +        "voltUnbalanceMaxPct": {
      +          "description": "Maximum steady-state phase voltage unbalance in %.",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / ratingCompliance
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Duty rating runtime and 24-hour average power compliance.",
      +  "properties": {
      +    "annualOperatingHours": {
      +      "description": "Evaluated annual runtime in hours/year.",
      +      "type": "number"
      +    },
      +    "maxAllowedHoursYr": {
      +      "description": "Permissible annual runtime ceiling in hours/year.",
      +      "type": "number"
      +    },
      +    "maxAllowedPpaRatioPct": {
      +      "description": "Maximum permissible 24-hour average load ratio in %.",
      +      "type": "number"
      +    },
      +    "ppaKw": {
      +      "description": "Computed 24-hour average active power Ppa in kW, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Computed 24-hour average active power Ppa in kW, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "ppaRatioPct": {
      +      "description": "24-hour average load ratio vs site rated kW in %, or null.",
      +      "oneOf": [
      +        {
      +          "description": "24-hour average load ratio vs site rated kW in %, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "ratingType": {
      +      "description": "Evaluated genset duty rating class (\"ESP\", \"PRP\", or \"COP\").",
      +      "type": "string"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / recommendations
      Added value: +{
      +  "description": "List of subsystem design recommendations.",
      +  "items": {
      +    "description": "Recommended engineering mitigation action.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / siteConditions
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Site ambient conditions and genset power derating outputs.",
      +  "properties": {
      +    "alternatorDeratingFactor": {
      +      "description": "Alternator cooling derating multiplier in (0..1].",
      +      "type": "number"
      +    },
      +    "altitudeM": {
      +      "description": "Evaluated site altitude above sea level in meters.",
      +      "type": "number"
      +    },
      +    "ambientTempC": {
      +      "description": "Evaluated ambient intake air temperature in deg C.",
      +      "type": "number"
      +    },
      +    "barometricPressureKpa": {
      +      "description": "Site barometric air pressure in kPa.",
      +      "type": "number"
      +    },
      +    "combinedDeratingFactor": {
      +      "description": "Effective net altitude-temperature derating multiplier.",
      +      "type": "number"
      +    },
      +    "deratingModel": {
      +      "description": "Applied derating methodology identifier (\"OEM_COMBINED\" or barometric).",
      +      "type": "string"
      +    },
      +    "engineDeratingFactor": {
      +      "description": "Prime-mover thermal and altitude derating multiplier.",
      +      "type": "number"
      +    },
      +    "iso3046BarometricFactor": {
      +      "description": "Barometric power correction multiplier.",
      +      "type": "number"
      +    },
      +    "nameplateActivePowerKw": {
      +      "description": "ISO nameplate active power rating in kW.",
      +      "type": "number"
      +    },
      +    "siteRatedActivePowerKw": {
      +      "description": "Derated continuous site active power in kW.",
      +      "type": "number"
      +    },
      +    "siteRatedApparentKva": {
      +      "description": "Derated continuous site apparent power in kVA.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / standards
      Added value: +{
      +  "description": "Applicable analytical model scope declarations.",
      +  "items": {
      +    "description": "Physical calculation scope label in SI units.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / status
      Added value: +{
      +  "description": "Subsystem verdict string (\"COMPLIANT\", \"WARNING\", or \"NON_COMPLIANT\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / stepEvaluations
      Added value: +{
      +  "description": "Evaluated load-step transient frequency and voltage results.",
      +  "items": {
      +    "additionalProperties": true,
      +    "description": "Single load-step transient evaluation record.",
      +    "properties": {
      +      "deltaFreqPct": {
      +        "description": "Transient frequency excursion in %.",
      +        "type": "number"
      +      },
      +      "deltaVoltPct": {
      +        "description": "Transient voltage excursion in %.",
      +        "type": "number"
      +      },
      +      "id": {
      +        "description": "Evaluated load step identifier.",
      +        "type": "string"
      +      },
      +      "isEstimated": {
      +        "description": "True when transient excursions were analytically estimated.",
      +        "type": "boolean"
      +      },
      +      "iso8528_5CurveMaxPct": {
      +        "description": "Allowable curve step limit at BMEP in %.",
      +        "type": "number"
      +      },
      +      "issues": {
      +        "description": "Violation descriptions detected on this step.",
      +        "items": {
      +          "description": "Step transient limit violation text.",
      +          "type": "string"
      +        },
      +        "type": "array"
      +      },
      +      "label": {
      +        "description": "Human-readable load step description.",
      +        "type": "string"
      +      },
      +      "mode": {
      +        "description": "Step direction (\"LOAD_INCREASE\" or \"LOAD_REJECTION\").",
      +        "type": "string"
      +      },
      +      "recoveryFreqS": {
      +        "description": "Frequency recovery duration in seconds.",
      +        "type": "number"
      +      },
      +      "recoveryVoltS": {
      +        "description": "Voltage recovery duration in seconds.",
      +        "type": "number"
      +      },
      +      "stageIndex": {
      +        "description": "Sequential load step stage index (1..3).",
      +        "type": "integer"
      +      },
      +      "steadyMeasurements": {
      +        "additionalProperties": true,
      +        "description": "Optional measured steady-state genset telemetry.",
      +        "properties": {
      +          "freqBandPct": {
      +            "description": "Measured steady frequency band in %, or null.",
      +            "oneOf": [
      +              {
      +                "description": "Measured steady frequency band in %, or null.",
      +                "type": "number"
      +              },
      +              {
      +                "description": "Null when value is not applicable in active mode.",
      +                "type": "null"
      +              }
      +            ]
      +          },
      +          "freqDroopPct": {
      +            "description": "Measured steady frequency droop in %, or null.",
      +            "oneOf": [
      +              {
      +                "description": "Measured steady frequency droop in %, or null.",
      +                "type": "number"
      +              },
      +              {
      +                "description": "Null when value is not applicable in active mode.",
      +                "type": "null"
      +              }
      +            ]
      +          },
      +          "voltSteadyPct": {
      +            "description": "Measured steady voltage deviation in %, or null.",
      +            "oneOf": [
      +              {
      +                "description": "Measured steady voltage deviation in %, or null.",
      +                "type": "number"
      +              },
      +              {
      +                "description": "Null when value is not applicable in active mode.",
      +                "type": "null"
      +              }
      +            ]
      +          },
      +          "voltUnbalancePct": {
      +            "description": "Measured voltage unbalance in %, or null.",
      +            "oneOf": [
      +              {
      +                "description": "Measured voltage unbalance in %, or null.",
      +                "type": "number"
      +              },
      +              {
      +                "description": "Null when value is not applicable in active mode.",
      +                "type": "null"
      +              }
      +            ]
      +          }
      +        },
      +        "type": "object"
      +      },
      +      "stepActivePct": {
      +        "description": "Step active power ratio vs site kW in %.",
      +        "type": "number"
      +      },
      +      "stepApparentPct": {
      +        "description": "Step apparent power ratio vs site kVA in %.",
      +        "type": "number"
      +      },
      +      "stepCompliant": {
      +        "description": "True when all transient limits pass for this step.",
      +        "type": "boolean"
      +      },
      +      "stepKva": {
      +        "description": "Apparent power step magnitude in kVA.",
      +        "type": "number"
      +      },
      +      "stepKvar": {
      +        "description": "Reactive power step magnitude in kvar.",
      +        "type": "number"
      +      },
      +      "stepKw": {
      +        "description": "Active power step magnitude in kW.",
      +        "type": "number"
      +      }
      +    },
      +    "type": "object"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / violations
      Added value: +{
      +  "description": "List of blocking subsystem violations.",
      +  "items": {
      +    "description": "Blocking physical limit violation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / genset / properties / warnings
      Added value: +{
      +  "description": "List of non-blocking subsystem warnings.",
      +  "items": {
      +    "description": "Advisory engineering observation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • changedOutput schema / properties / sections / properties / transformerPit / description
      Previous value: -"Net effective containment capacity vs total oil + rainwater/fire volume."New value: +"Net effective containment capacity vs total oil plus rainwater/fire volume."
    • addedOutput schema / properties / sections / properties / transformerPit / properties / apsadAudit
      Added value: +{
      +  "description": "Optional site fire-water demand and storm retention sub-audit, or null.",
      +  "oneOf": [
      +    {
      +      "additionalProperties": true,
      +      "description": "Optional site fire-water demand and storm retention sub-audit, or null.",
      +      "properties": {
      +        "d9DurationHours": {
      +          "description": "Required fire-water supply duration in hours.",
      +          "type": "number"
      +        },
      +        "d9ExtinguishingWaterM3": {
      +          "description": "Total fire-water supply volume in m3.",
      +          "type": "number"
      +        },
      +        "d9aTotalRetentionM3": {
      +          "description": "Total site liquid retention requirement in m3.",
      +          "type": "number"
      +        },
      +        "d9aWeatherRunoffM3": {
      +          "description": "Stormwater runoff containment allowance in m3.",
      +          "type": "number"
      +        },
      +        "hasSprinkler": {
      +          "description": "True when automatic sprinkler protection is credited.",
      +          "type": "boolean"
      +        },
      +        "protectedAreaM2": {
      +          "description": "Protected industrial zone surface area in m2.",
      +          "type": "number"
      +        },
      +        "requiredFlowD9M3H": {
      +          "description": "Required external fire-water flow rate in m3/h.",
      +          "type": "number"
      +        },
      +        "riskCategory": {
      +          "description": "Site fire-water risk classification tier (1..3).",
      +          "type": "integer"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    {
      +      "description": "Null when optional sub-audit is not enabled.",
      +      "type": "null"
      +    }
      +  ]
      +}
    • addedOutput schema / properties / sections / properties / transformerPit / properties / compliant
      Added value: +{
      +  "description": "True when this subsystem satisfies all physical limits.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / sections / properties / transformerPit / properties / fireExtinctionAndPit
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Pebble-bed void displacement and total liquid retention balance.",
      +  "properties": {
      +    "extinctionDurationMin": {
      +      "description": "Design fire-water discharge duration in minutes.",
      +      "type": "number"
      +    },
      +    "extinctionFlowM3H": {
      +      "description": "Total fire-suppression water flow rate in m3/h.",
      +      "type": "number"
      +    },
      +    "extinctionWaterVolumeM3": {
      +      "description": "Cumulative fire-water retention volume in m3.",
      +      "type": "number"
      +    },
      +    "gratingLoadCapacityDaNM2": {
      +      "description": "Support grating minimum load rating in daN/m2.",
      +      "type": "number"
      +    },
      +    "integratedUsefulCapacityM3": {
      +      "description": "Net useful liquid capacity inside integrated pit in m3.",
      +      "type": "number"
      +    },
      +    "pebbleBedThicknessM": {
      +      "description": "Quenching pebble bed thickness in meters.",
      +      "type": "number"
      +    },
      +    "pebbleGradingLabel": {
      +      "description": "Crushed gravel nominal aggregate grading range.",
      +      "type": "string"
      +    },
      +    "pebbleVoidFraction": {
      +      "description": "Void porosity ratio inside gravel quenching layer.",
      +      "type": "number"
      +    },
      +    "pitArchitecture": {
      +      "description": "Evaluated retention pit flame-quenching architecture.",
      +      "type": "string"
      +    },
      +    "pitFootprintAreaM2": {
      +      "description": "Catchment pit plan surface area in m2.",
      +      "type": "number"
      +    },
      +    "remoteTankVolumeM3": {
      +      "description": "Downstream remote containment tank volume in m3.",
      +      "type": "number"
      +    },
      +    "requiredGrossVolumeIfPurePebblePitM3": {
      +      "description": "Equivalent pure pebble-bed gross pit volume in m3.",
      +      "type": "number"
      +    },
      +    "requiredLiquidToContainM3": {
      +      "description": "Total combined oil plus fire-water volume in m3.",
      +      "type": "number"
      +    },
      +    "reserveMarginPct": {
      +      "description": "Available retention margin above required volume in %.",
      +      "type": "number"
      +    },
      +    "totalAvailableRetentionM3": {
      +      "description": "Total combined pit plus remote tank capacity in m3.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / transformerPit / properties / oilRetention
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Transformer dielectric oil volume containment targets.",
      +  "properties": {
      +    "aggregateOilVolumeM3": {
      +      "description": "Sum of all transformer oil volumes in m3.",
      +      "type": "number"
      +    },
      +    "maxSingleTransformerOilM3": {
      +      "description": "Largest single transformer dielectric oil volume in m3.",
      +      "type": "number"
      +    },
      +    "requiredOilVolumeM3": {
      +      "description": "Required net oil containment capacity in m3.",
      +      "type": "number"
      +    },
      +    "retentionRule": {
      +      "description": "Applied multi-unit containment sizing rule string.",
      +      "type": "string"
      +    },
      +    "transformerCount": {
      +      "description": "Count of liquid-filled transformers draining to pit.",
      +      "type": "integer"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / transformerPit / properties / recommendations
      Added value: +{
      +  "description": "List of subsystem design recommendations.",
      +  "items": {
      +    "description": "Recommended engineering mitigation action.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / transformerPit / properties / standards
      Added value: +{
      +  "description": "Applicable analytical model scope declarations.",
      +  "items": {
      +    "description": "Physical calculation scope label in SI units.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / transformerPit / properties / status
      Added value: +{
      +  "description": "Subsystem verdict string (\"COMPLIANT\", \"WARNING\", or \"NON_COMPLIANT\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / transformerPit / properties / violations
      Added value: +{
      +  "description": "List of blocking subsystem violations.",
      +  "items": {
      +    "description": "Blocking physical limit violation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / transformerPit / properties / warnings
      Added value: +{
      +  "description": "List of non-blocking subsystem warnings.",
      +  "items": {
      +    "description": "Advisory engineering observation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / upsAndSts / properties / batteryAutonomy
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "UPS DC battery autonomy and Ah sizing outputs.",
      +  "properties": {
      +    "agingFactor": {
      +      "description": "Battery end-of-life capacity aging multiplier.",
      +      "type": "number"
      +    },
      +    "autonomyMinutes": {
      +      "description": "Evaluated full-load DC backup duration in minutes.",
      +      "type": "number"
      +    },
      +    "dcDischargeCurrentA": {
      +      "description": "Nominal DC battery discharge current in A.",
      +      "type": "number"
      +    },
      +    "dcNominalVoltageV": {
      +      "description": "Nominal DC battery bus voltage in V.",
      +      "type": "number"
      +    },
      +    "dischargeCapacityFactor": {
      +      "description": "Peukert high-rate discharge capacity ratio.",
      +      "type": "number"
      +    },
      +    "estimatedRequiredC10Ah": {
      +      "description": "Estimated required C10 battery capacity in Ah.",
      +      "type": "number"
      +    },
      +    "netBatteryEnergyKwh": {
      +      "description": "Net DC energy delivered during autonomy in kWh.",
      +      "type": "number"
      +    },
      +    "requiredDcPowerKw": {
      +      "description": "Required inverter DC input power in kW.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / upsAndSts / properties / compliant
      Added value: +{
      +  "description": "True when this subsystem satisfies all physical limits.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / sections / properties / upsAndSts / properties / earthingAndProtection
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "UPS upstream/downstream earthing and RCD compatibility.",
      +  "properties": {
      +    "downstreamEarthingSystem": {
      +      "description": "Downstream protected bus earthing system.",
      +      "type": "string"
      +    },
      +    "hasGalvanicIsolationXfmr": {
      +      "description": "True when galvanic isolation transformer is present.",
      +      "type": "boolean"
      +    },
      +    "hasUpstreamRcd": {
      +      "description": "True when upstream residual current protection is fitted.",
      +      "type": "boolean"
      +    },
      +    "upstreamEarthingSystem": {
      +      "description": "Upstream AC supply earthing (\"TT\", \"TN-S\", \"IT\").",
      +      "type": "string"
      +    },
      +    "upstreamRcdType": {
      +      "description": "Upstream RCD type designation (\"NONE\", \"A\", \"B\").",
      +      "type": "string"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / upsAndSts / properties / recommendations
      Added value: +{
      +  "description": "List of subsystem design recommendations.",
      +  "items": {
      +    "description": "Recommended engineering mitigation action.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / upsAndSts / properties / sizing
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "UPS kVA sizing, module count, and upstream rectifier impact.",
      +  "properties": {
      +    "activeLoadKw": {
      +      "description": "Protected active IT/process load in kW.",
      +      "type": "number"
      +    },
      +    "activeModulesN": {
      +      "description": "Count of active parallel UPS modules carrying load.",
      +      "type": "integer"
      +    },
      +    "designActivePowerKw": {
      +      "description": "Growth-adjusted design active load in kW.",
      +      "type": "number"
      +    },
      +    "estimatedUpstreamThduPct": {
      +      "description": "Estimated upstream voltage THDu in %, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Estimated upstream voltage THDu in %, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "inverterShortCircuitLimitA": {
      +      "description": "Inverter solid-state fault current ceiling in A.",
      +      "type": "number"
      +    },
      +    "minRecommendedSourceSccMva": {
      +      "description": "Minimum upstream fault level for < 5% THDu in MVA.",
      +      "type": "number"
      +    },
      +    "moduleUtilizationPct": {
      +      "description": "Module apparent load utilization percentage (%).",
      +      "type": "number"
      +    },
      +    "rechargePowerKw": {
      +      "description": "Battery recharge active power draw in kW.",
      +      "type": "number"
      +    },
      +    "rectifierInputCurrentA": {
      +      "description": "Total upstream AC input current in A.",
      +      "type": "number"
      +    },
      +    "rectifierInputKw": {
      +      "description": "Continuous rectifier AC input active power in kW.",
      +      "type": "number"
      +    },
      +    "rectifierThdiPct": {
      +      "description": "Rectifier input current harmonic distortion in %.",
      +      "type": "number"
      +    },
      +    "rectifierType": {
      +      "description": "Evaluated upstream rectifier topology identifier.",
      +      "type": "string"
      +    },
      +    "redundancyMode": {
      +      "description": "Power train redundancy mode (\"N\", \"N+1\", or \"2N\").",
      +      "type": "string"
      +    },
      +    "requiredOutputKva": {
      +      "description": "Required UPS apparent output capacity in kVA.",
      +      "type": "number"
      +    },
      +    "selectedModuleKva": {
      +      "description": "Selected standard UPS module rating in kVA.",
      +      "type": "number"
      +    },
      +    "totalInstalledModules": {
      +      "description": "Total installed UPS modules including redundancy.",
      +      "type": "integer"
      +    },
      +    "totalUpstreamKva": {
      +      "description": "Total upstream rectifier plus recharge kVA.",
      +      "type": "number"
      +    },
      +    "upsTopology": {
      +      "description": "Evaluated UPS conversion topology string.",
      +      "type": "string"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sections / properties / upsAndSts / properties / standards
      Added value: +{
      +  "description": "Applicable analytical model scope declarations.",
      +  "items": {
      +    "description": "Physical calculation scope label in SI units.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / upsAndSts / properties / status
      Added value: +{
      +  "description": "Subsystem verdict string (\"COMPLIANT\", \"WARNING\", or \"NON_COMPLIANT\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / sections / properties / upsAndSts / properties / stsAudit
      Added value: +{
      +  "description": "Static Transfer Switch synchronization audit, or null.",
      +  "oneOf": [
      +    {
      +      "additionalProperties": true,
      +      "description": "Static Transfer Switch synchronization audit, or null.",
      +      "properties": {
      +        "freqDiffHz": {
      +          "description": "Source-to-source frequency slip in Hz.",
      +          "type": "number"
      +        },
      +        "issues": {
      +          "description": "Detected STS compliance violations.",
      +          "items": {
      +            "description": "STS synchronization or pole violation.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "phaseSyncDeg": {
      +          "description": "Source-to-source phase synchronization window in degrees.",
      +          "type": "number"
      +        },
      +        "sharedSourceRatingRatio": {
      +          "description": "Largest-to-smallest STS rating ratio, or null.",
      +          "oneOf": [
      +            {
      +              "description": "Largest-to-smallest STS rating ratio, or null.",
      +              "type": "number"
      +            },
      +            {
      +              "description": "Null when value is not applicable in active mode.",
      +              "type": "null"
      +            }
      +          ]
      +        },
      +        "stsCompliant": {
      +          "description": "True when STS synchronization and pole rules pass.",
      +          "type": "boolean"
      +        },
      +        "stsPoles": {
      +          "description": "STS switching pole configuration (\"3P\", \"4P_OVERLAP\", \"4P_NO_OVERLAP\").",
      +          "type": "string"
      +        },
      +        "transferTimeMs": {
      +          "description": "Solid-state STS transfer duration in ms.",
      +          "type": "number"
      +        },
      +        "voltDiffPct": {
      +          "description": "Source-to-source voltage difference in %.",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    {
      +      "description": "Null when optional sub-audit is not enabled.",
      +      "type": "null"
      +    }
      +  ]
      +}
    • addedOutput schema / properties / sections / properties / upsAndSts / properties / violations
      Added value: +{
      +  "description": "List of blocking subsystem violations.",
      +  "items": {
      +    "description": "Blocking physical limit violation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sections / properties / upsAndSts / properties / warnings
      Added value: +{
      +  "description": "List of non-blocking subsystem warnings.",
      +  "items": {
      +    "description": "Advisory engineering observation message.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / summary / properties / criticalBlockers
      Added value: +{
      +  "description": "Consolidated list of blocking design violations.",
      +  "items": {
      +    "description": "Section-prefixed blocking violation string.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / summary / properties / keyKpis
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Dashboard of key scalar metrics across all six subsystems.",
      +  "properties": {
      +    "batteryAirflowM3H": {
      +      "description": "Required H2 dilution m3/h, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Required H2 dilution m3/h, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "emcSeparationMm": {
      +      "description": "Required EMC separation mm, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Required EMC separation mm, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "en50600AchievedClass": {
      +      "description": "Achieved facility availability class (1..4), or null.",
      +      "oneOf": [
      +        {
      +          "description": "Achieved facility availability class (1..4), or null.",
      +          "type": "integer"
      +        },
      +        {
      +          "description": "Null when integer metric is not evaluated.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "gensetSiteRatedKw": {
      +      "description": "Derated genset active kW, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Derated genset active kW, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "pue": {
      +      "description": "Computed data center PUE, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Computed data center PUE, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "ref": {
      +      "description": "Computed REF in [0..1], or null.",
      +      "oneOf": [
      +        {
      +          "description": "Computed REF in [0..1], or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "transformerRetentionRequiredM3": {
      +      "description": "Required retention volume m3, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Required retention volume m3, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "upsSelectedKva": {
      +      "description": "Selected UPS kVA, or null.",
      +      "oneOf": [
      +        {
      +          "description": "Selected UPS kVA, or null.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is not applicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / summary / properties / overallCompliant
      Added value: +{
      +  "description": "True when every evaluated critical-power subsystem passes.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / summary / properties / overallStatus
      Added value: +{
      +  "description": "Overall aggregated status (\"COMPLIANT\", \"WARNING\", \"NON_COMPLIANT\", or \"EMPTY\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / summary / properties / recommendations
      Added value: +{
      +  "description": "Consolidated list of recommended actions.",
      +  "items": {
      +    "description": "Section-prefixed mitigation recommendation.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / summary / properties / sectionsEvaluated
      Added value: +{
      +  "description": "Number of subsystems evaluated.",
      +  "type": "integer"
      +}
    • addedOutput schema / properties / summary / properties / sectionsPassed
      Added value: +{
      +  "description": "Number of subsystems passing all checks.",
      +  "type": "integer"
      +}
    • addedOutput schema / properties / summary / properties / violationCount
      Added value: +{
      +  "description": "Total blocking compliance violations.",
      +  "type": "integer"
      +}
    • addedOutput schema / properties / summary / properties / warningCount
      Added value: +{
      +  "description": "Total non-blocking advisory warnings.",
      +  "type": "integer"
      +}
    • addedOutput schema / properties / summary / properties / warnings
      Added value: +{
      +  "description": "Consolidated list of non-blocking warnings.",
      +  "items": {
      +    "description": "Section-prefixed advisory warning string.",
      +    "type": "string"
      +  },
      +  "type": "array"
      +}
  2. Changed23 schema fields changed
    • addedInput schema / additionalProperties
      Added value: +true
    • addedInput schema / properties / batteryRoom / additionalProperties
      Added value: +true
    • addedInput schema / properties / batteryRoom / description
      Added value: +"Battery room Faraday electrolysis H2 emission and dilution airflow inputs."
    • addedInput schema / properties / batteryRoom / properties
      Added value: +{
      +  "cellCount": {
      +    "description": "Total series-connected 2 V or 1.2 V electrochemical cells.",
      +    "minimum": 1,
      +    "type": "integer"
      +  },
      +  "chargeMode": {
      +    "description": "Worst-case gassing regime (\"FLOAT\", \"BOOST\").",
      +    "type": "string"
      +  },
      +  "hasHydrogenDetector": {
      +    "description": "True when LEL catalytic/MOS hydrogen gas monitoring is installed.",
      +    "type": "boolean"
      +  },
      +  "installedAirflowM3H": {
      +    "description": "Provided continuous battery room exhaust airflow in m3/h.",
      +    "type": "number"
      +  },
      +  "installedInletAreaCm2": {
      +    "description": "Low-level fresh air intake grille net free area in cm2.",
      +    "type": "number"
      +  },
      +  "nominalCapacityAh": {
      +    "description": "Battery string C10/C20 capacity per string in Ah.",
      +    "type": "number"
      +  },
      +  "technology": {
      +    "description": "Electrochemical battery type (\"VRLA\", \"FLOODED_LEAD_ACID\", \"NICD\", \"LFP\").",
      +    "type": "string"
      +  }
      +}
    • addedInput schema / properties / dataCenter / additionalProperties
      Added value: +true
    • addedInput schema / properties / dataCenter / description
      Added value: +"Data center PUE, Renewable Energy Factor (REF), and facility robustness inputs."
    • addedInput schema / properties / dataCenter / properties
      Added value: +{
      +  "coolingEnergyMwh": {
      +    "description": "Annual HVAC chiller & CRAH mechanical cooling energy in MWh.",
      +    "type": "number"
      +  },
      +  "coolingRedundancy": {
      +    "description": "Mechanical cooling path redundancy (\"N\", \"N+1\", \"2N\").",
      +    "type": "string"
      +  },
      +  "itEnergyMwh": {
      +    "description": "Annual IT equipment energy consumption in MWh.",
      +    "type": "number"
      +  },
      +  "lightingAndOtherMwh": {
      +    "description": "Annual auxiliary lighting & security energy in MWh.",
      +    "type": "number"
      +  },
      +  "onsiteRenewableConsumedMwh": {
      +    "description": "Annual on-site renewable energy generated & consumed in MWh.",
      +    "type": "number"
      +  },
      +  "powerDistributionLossMwh": {
      +    "description": "Annual UPS/PDU/transformer electrical loss in MWh.",
      +    "type": "number"
      +  },
      +  "powerRedundancy": {
      +    "description": "Electrical distribution path topology (\"N\", \"N+1\", \"2N\").",
      +    "type": "string"
      +  },
      +  "targetAvailabilityClass": {
      +    "description": "Target facility availability robustness class (1..4).",
      +    "maximum": 4,
      +    "minimum": 1,
      +    "type": "integer"
      +  }
      +}
    • addedInput schema / properties / emcSeparation / additionalProperties
      Added value: +true
    • addedInput schema / properties / emcSeparation / description
      Added value: +"Power-vs-telemetry cable electromagnetic interference separation audit inputs."
    • addedInput schema / properties / emcSeparation / properties
      Added value: +{
      +  "barrierType": {
      +    "description": "Metallic tray shielding class (\"NONE\", \"PERFORATED_STEEL_TRAY\", \"SOLID_STEEL_CONDUIT\").",
      +    "type": "string"
      +  },
      +  "installationContext": {
      +    "description": "Cable routing support (\"INDOOR_TRAY\", \"UNDERGROUND_DUCT\").",
      +    "type": "string"
      +  },
      +  "installedSeparationMm": {
      +    "description": "Actual center-to-center or clear spacing to signal cables in mm.",
      +    "type": "number"
      +  },
      +  "lowCurrentMedium": {
      +    "description": "Sensitive data medium (\"COPPER_UNSCREENED\", \"COPPER_SCREENED_CAT5E_6\", \"FIBER\").",
      +    "type": "string"
      +  },
      +  "powerSystemTier": {
      +    "description": "Adjacent power feeder tier (\"LV\", \"HTA\").",
      +    "type": "string"
      +  },
      +  "powerVoltageKv": {
      +    "description": "Power cable operating voltage in kV.",
      +    "type": "number"
      +  }
      +}
    • addedInput schema / properties / genset / additionalProperties
      Added value: +true
    • addedInput schema / properties / genset / description
      Added value: +"Emergency generator set derating, fuel autonomy, and step-loading inputs."
    • addedInput schema / properties / genset / properties
      Added value: +{
      +  "altitudeM": {
      +    "description": "Site elevation above sea level in meters for air-density derating.",
      +    "type": "number"
      +  },
      +  "ambientTempC": {
      +    "description": "Intake combustion & cooling air temperature in deg C.",
      +    "type": "number"
      +  },
      +  "fuelAutonomyHours": {
      +    "description": "On-site day/bulk fuel storage autonomy in hours.",
      +    "type": "number"
      +  },
      +  "fuelType": {
      +    "description": "Prime mover fuel chemistry (\"DIESEL\", \"NATURAL_GAS\", \"HVO\").",
      +    "type": "string"
      +  },
      +  "loadSteps": {
      +    "description": "Ordered sequence of block-loading steps for frequency/voltage dip assessment.",
      +    "items": {
      +      "additionalProperties": true,
      +      "description": "Single transient genset step-load block.",
      +      "properties": {
      +        "id": {
      +          "description": "Block loading step identifier.",
      +          "type": "string"
      +        },
      +        "stepKw": {
      +          "description": "Step active load addition in kW.",
      +          "type": "number"
      +        },
      +        "stepPowerFactor": {
      +          "description": "Step load power factor cos(phi).",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "type": "array"
      +  },
      +  "nominalFrequencyHz": {
      +    "description": "Nominal electrical output frequency in Hz (50 or 60).",
      +    "type": "number"
      +  },
      +  "performanceClass": {
      +    "description": "Transient load-acceptance performance class (\"G1\", \"G2\", \"G3\", \"G4\").",
      +    "type": "string"
      +  },
      +  "ratedActivePowerKw": {
      +    "description": "ISO standard nameplate active power rating in kW.",
      +    "type": "number"
      +  },
      +  "ratedApparentKva": {
      +    "description": "Alternator rated apparent power in kVA.",
      +    "type": "number"
      +  },
      +  "ratingType": {
      +    "description": "Duty rating class (\"ESP\", \"PRP\", \"COP\").",
      +    "type": "string"
      +  }
      +}
    • addedInput schema / properties / mode / default
      Added value: +"audit"
    • addedInput schema / properties / mode / description
      Added value: +"Critical power engineering sub-domain selector or full 6-section audit (defaults to \"audit\")."
    • addedInput schema / properties / presetId / description
      Added value: +"Reference critical-power facility preset ID (e.g. \"HYPERSCALE_DC_2N_CLASS4\")."
    • addedInput schema / properties / transformerPit / additionalProperties
      Added value: +true
    • addedInput schema / properties / transformerPit / description
      Added value: +"Oil-filled transformer retention pit, pebble-bed flame arrestor, and fire-water volume inputs."
    • addedInput schema / properties / transformerPit / properties
      Added value: +{
      +  "pebbleBedThicknessM": {
      +    "description": "Quenching pebble bed gravel thickness in meters.",
      +    "type": "number"
      +  },
      +  "pitArchitecture": {
      +    "description": "Pit flame-quenching type (\"PEBBLE_BED_INTEGRATED\", \"OPEN_BUND_REMOTE_TANK\").",
      +    "type": "string"
      +  },
      +  "pitDepthM": {
      +    "description": "Retention basin net clear depth in meters.",
      +    "type": "number"
      +  },
      +  "pitFootprintLengthM": {
      +    "description": "Retention basin net interior length in meters.",
      +    "type": "number"
      +  },
      +  "pitFootprintWidthM": {
      +    "description": "Retention basin net interior width in meters.",
      +    "type": "number"
      +  },
      +  "remoteTankVolumeM3": {
      +    "description": "Downstream remote containment tank capacity in m3.",
      +    "type": "number"
      +  },
      +  "retentionRule": {
      +    "description": "Containment rule (\"SINGLE_PIT_100PCT\", \"MULTI_PIT\").",
      +    "type": "string"
      +  },
      +  "transformers": {
      +    "description": "Transformers draining into the analyzed oil retention pit.",
      +    "items": {
      +      "additionalProperties": true,
      +      "description": "Transformer liquid inventory record.",
      +      "properties": {
      +        "dielectricOilVolumeM3": {
      +          "description": "Liquid dielectric oil volume in m3.",
      +          "type": "number"
      +        },
      +        "id": {
      +          "description": "Transformer tag inside catchment zone.",
      +          "type": "string"
      +        },
      +        "powerMva": {
      +          "description": "Transformer rated apparent power in MVA.",
      +          "type": "number"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "type": "array"
      +  }
      +}
    • addedInput schema / properties / upsAndSts / additionalProperties
      Added value: +true
    • addedInput schema / properties / upsAndSts / description
      Added value: +"UPS sizing, upstream source matching, and Static Transfer Switch synchronization inputs."
    • addedInput schema / properties / upsAndSts / properties
      Added value: +{
      +  "activeLoadKw": {
      +    "description": "Protected critical IT/industrial active load in kW.",
      +    "type": "number"
      +  },
      +  "autonomyMinutes": {
      +    "description": "Target full-load DC battery ride-through time in minutes.",
      +    "type": "number"
      +  },
      +  "dcNominalVoltageV": {
      +    "description": "Intermediate UPS DC battery bus voltage in V.",
      +    "type": "number"
      +  },
      +  "redundancyMode": {
      +    "description": "Power train redundancy configuration (\"N\", \"N+1\", \"2N\").",
      +    "type": "string"
      +  },
      +  "stsPhaseSyncDeg": {
      +    "description": "Phase angle difference tolerance window between sources in degrees.",
      +    "type": "number"
      +  },
      +  "stsPresent": {
      +    "description": "True when a Static Transfer Switch selects between A/B sources.",
      +    "type": "boolean"
      +  },
      +  "stsTransferTimeMs": {
      +    "description": "STS break/make solid-state transfer duration in ms.",
      +    "type": "number"
      +  },
      +  "upsEfficiency": {
      +    "description": "Double-conversion efficiency ratio in (0, 1].",
      +    "type": "number"
      +  },
      +  "upsTopology": {
      +    "description": "UPS conversion architecture (\"ONLINE_DOUBLE_CONVERSION\", \"LINE_INTERACTIVE\").",
      +    "type": "string"
      +  }
      +}
    • changedOutput schema / (root)
      Previous value: -nullNew value: +{
      +  "additionalProperties": true,
      +  "description": "Critical power auxiliaries and safety evaluation with calculationTrace and legalNotice.",
      +  "properties": {
      +    "calculationTrace": {
      +      "additionalProperties": true,
      +      "description": "Transparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.",
      +      "properties": {
      +        "defaultsApplied": {
      +          "additionalProperties": true,
      +          "description": "Default physical or engineering assumptions injected when optional inputs were omitted.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "engineeringAssumptions": {
      +          "description": "Explicit boundary assumptions required to interpret the numerical output.",
      +          "items": {
      +            "description": "Boundary condition or validity assumption for the calculation.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "formulasAndConstants": {
      +          "additionalProperties": true,
      +          "description": "Mathematical formulas and SI physical constants bound to this calculation mode.",
      +          "properties": {
      +            "constants": {
      +              "additionalProperties": true,
      +              "description": "Map of physical constants, resistivities, and design coefficients in SI units.",
      +              "properties": {},
      +              "type": "object"
      +            },
      +            "formulas": {
      +              "description": "Ordered list of physical equations evaluated by the calculation engine.",
      +              "items": {
      +                "description": "Symbolic engineering formula string used during evaluation.",
      +                "type": "string"
      +              },
      +              "type": "array"
      +            }
      +          },
      +          "type": "object"
      +        },
      +        "inputsProvided": {
      +          "additionalProperties": true,
      +          "description": "Non-empty normalized input parameters explicitly supplied by the caller.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "mode": {
      +          "description": "Normalized calculation mode executed for the current payload.",
      +          "type": "string"
      +        },
      +        "physicalPrinciples": {
      +          "description": "Key physical principles governing the computed result.",
      +          "items": {
      +            "description": "Concise statement of an underlying electrical or thermal principle.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "tool": {
      +          "description": "Resolved Brain tool identifier audited by the calculation tracer.",
      +          "type": "string"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "legalNotice": {
      +      "description": "Informational engineering compliance notice confirming SI physical scope and intellectual property rules.",
      +      "type": "string"
      +    },
      +    "metadata": {
      +      "additionalProperties": true,
      +      "description": "Selected preset title and evaluation scope metadata.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "mode": {
      +      "description": "Executed critical power audit mode.",
      +      "type": "string"
      +    },
      +    "sections": {
      +      "additionalProperties": true,
      +      "description": "Per-section detailed physics outputs.",
      +      "properties": {
      +        "batteryRoom": {
      +          "additionalProperties": true,
      +          "description": "H2 emission Q (m3/h), required ventilation airflow, and grille area checks.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "dataCenter": {
      +          "additionalProperties": true,
      +          "description": "Computed PUE, Renewable Energy Factor REF, and availability class compliance.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "emcSeparation": {
      +          "additionalProperties": true,
      +          "description": "Minimum required vs installed power/signal separation distance (mm).",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "genset": {
      +          "additionalProperties": true,
      +          "description": "Derated genset continuous/prime rating and step-load margins.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "transformerPit": {
      +          "additionalProperties": true,
      +          "description": "Net effective containment capacity vs total oil + rainwater/fire volume.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "upsAndSts": {
      +          "additionalProperties": true,
      +          "description": "UPS kVA capacity, upstream fault compatibility, and STS sync checks.",
      +          "properties": {},
      +          "type": "object"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "summary": {
      +      "additionalProperties": true,
      +      "description": "Overall pass/fail flags across all evaluated critical-power subsystems.",
      +      "properties": {},
      +      "type": "object"
      +    }
      +  },
      +  "type": "object"
      +}
  3. First observed

TDQS

A4.4/5.0
Behavior4/5

Does the description disclose side effects, auth requirements, rate limits, or destructive behavior?

Annotations already declare readOnlyHint, idempotentHint, destructiveHint=false and openWorldHint=false, yet the description adds genuinely new behavior: up to six coupled solvers in a stateless SI pass, JSON-RPC -32602 on non-object inputs, and default mode='audit' with the HYPERSCALE_DC_2N_CLASS4 preset. The 'read-only / zero mutations' phrasing partly restates the annotations, keeping it just under a 5.

Agents need to know what a tool does to the world before calling it. Descriptions should go beyond structured annotations to explain consequences.

Conciseness4/5

Is the description appropriately sized, front-loaded, and free of redundancy?

Dense but well front-loaded: purpose first, then When to use / Do not use / Behavior / Returns in labeled segments. The 'Returns:' sentence lists fields the output schema already documents, a minor redundancy, but otherwise every clause earns its place.

Shorter descriptions cost fewer tokens and are easier for agents to parse. Every sentence should earn its place.

Completeness5/5

Given the tool's complexity, does the description cover enough for an agent to succeed on first attempt?

For a complex tool with 8 top-level params, deeply nested objects, and an output schema, the description covers domain scope, routing to alternatives, error semantics, and defaulting behavior — everything an agent needs to call it correctly without restating the return shape in detail.

Complex tools with many parameters or behaviors need more documentation. Simple tools need less. This dimension scales expectations accordingly.

Parameters3/5

Does the description clarify parameter syntax, constraints, interactions, or defaults beyond what the schema provides?

Schema description coverage is 100% and every nested field is documented in-schema, so the description's only parameter-adjacent content — the mode='audit' default and the preset fallback — is already present in the schema. Baseline 3 applies since the schema carries the parameter burden.

Input schemas describe structure but not intent. Descriptions should explain non-obvious parameter relationships and valid value ranges.

Purpose5/5

Does the description clearly state what the tool does and how it differs from similar tools?

States a specific verb ('Run deterministic critical-power and safety physics models') and then enumerates all six sub-domains it covers — genset derating, UPS/STS, H2 battery ventilation, EMC separation, retention pits, and PUE/REF — so an agent can match its request to the tool without opening the schema.

Agents choose between tools based on descriptions. A clear purpose with a specific verb and resource helps agents select the right tool.

Usage Guidelines5/5

Does the description explain when to use this tool, when not to, or what alternatives exist?

Explicit 'When to use' names the target domains (emergency power auxiliaries, battery rooms, oil containment, PUE/REF sizing) and an explicit 'Do not use for' clause routes Markov availability trees and transformer oil DGA to the named siblings brain_calc_system_reliability and brain_calc_transformer_ecodesign_dga.

Agents often have multiple tools that could apply. Explicit usage guidance like "use X instead of Y when Z" prevents misuse.