GIS & MV SF6 Room Airflow & O2 Auditor

brain_audit_gis_mv_room_air_sf6
Read-onlyIdempotent

Audit indoor GIS and MV SF6 switchgear halls in SI units: free air volume (m3), low-layer (z <= 1.0 m) and trench SF6 stratification (6.17 kg/m3), residual O2 % (19.5% / 17.0%), 95% purge time (min), smoke extraction, arc overpressure (kPa), and tCO2e inventory. When to use: Use for dedicated indoor GIS or MV SF6 switchgear airflow, heavy-gas stratification, and O2 asphyxiation audits without transformers. Do not use for: Transformer oil-fire separation clearances, water deluge hydraulics, or outdoor oil retention bunds -- call brain_calc_fm_global_fire_smoke_gis instead. Behavior: Evaluates heavy-gas dilution and aerodynamics in a stateless, read-only SI pass with zero mutations; invalid argument types raise JSON-RPC -32602, while omitted inputs default to reference GIS hall parameters (lang="fr"). Returns: mode, installationType, overallStatus, complianceScore, metrology, sf6DispersionAndO2, ventilationAndPurge, smokeExtractionAndHvac, internalArcAndFgas, calculationTrace, and legalNotice.

Tool call template

This tool declares no required parameters. Add optional parameters from the input schema as needed.

{
  "id": 1,
  "jsonrpc": "2.0",
  "method": "tools/call",
  "params": {
    "arguments": {},
    "name": "brain_audit_gis_mv_room_air_sf6"
  }
}

Input Schema

NameRequiredDescriptionDefault
langNoResponse localization language code ("fr" for French or "en" for English, defaults to "fr").fr
widthMNoEnclosure interior room clear width in meters (m).
gisRoomNoStructured GIS / MV SF6 switchgear room geometry and gas inventory overrides.
heightMNoEnclosure interior ceiling clear height in meters (m).
lengthMNoEnclosure interior room clear length in meters (m).
presetIdNoReference GIS or MV switchgear room preset identifier (e.g. "gis_225_20kv_reference_2x85mva").
roomTypeNoEnclosure room role ("transformer_vault", "gis_hall", "mv_switchroom", "control_room").
normalAchNoContinuous normal-operation air change rate in volumes/hour (vol/h).
smokeHvacNoStructured room thermal HVAC and smoke extraction geometry overrides.
deltaTMaxKNoMaximum permissible room air temperature rise Delta-T in Kelvin (K).
rearAisleMNoClear rear maintenance and gas-sampling corridor width in meters (m).
sideAisleMNoClear lateral switchgear access corridor width in meters (m).
totalSf6KgNoTotal substation inventory mass of SF6 insulating gas in kg.
frontAisleMNoClear front operator and circuit-breaker withdrawal aisle width in meters (m).
internalArcKaNoRated switchgear internal arc fault current magnitude in kA.
installedSueM2NoInstalled effective natural geometric smoke vent free area SUE in m2.
trenchVolumeM3NoCommunicating below-floor cable trench air volume in m3 where heavy gas pools.
thermalLossesKwNoTotal continuous equipment heat rejection losses in kW (>= 0 kW).
installationTypeNoGas-insulated switchgear tier ("gis_hv" or "mv_sf6_switchgear").
nominalVoltageKvNoNominal switchgear operating phase-to-phase voltage in kV.
equipmentVolumeM3NoDisplaced solid switchgear enclosure volume deducted from free air in m3.
emergencyExhaustAchNoEmergency post-leak mechanical purge extraction rate in vol/h.
installedExhaustM3HNoInstalled mechanical smoke/heat exhaust volumetric flow rate in m3/h.
maxCompartmentSf6KgNoLargest single pressurized gas compartment SF6 mass release in kg.
smokeExtractionModeNoSmoke extraction mechanism ("natural" vents or "mechanical" fans).
equipmentFootprintM2NoTotal plan floor footprint occupied by switchgear bays in m2.
hasGasDuctOrAbsorberNoTrue when internal arc relief vents via an external pressure duct or absorber.
intakePressureDropPaNoSupply intake louver and filter aerodynamic pressure loss in pascals (Pa).
internalArcDurationSNoInternal arc fault clearing duration in seconds (s).
exhaustPressureDropPaNoExhaust duct and damper aerodynamic pressure loss in pascals (Pa).
buildingClassificationNoFire safety building occupancy class ("erp" for public assembly or industrial default).
fireDoorOrDamperRatingNoCompartment fire barrier resistance rating ("EI60", "EI120", "EI180").
pressureDropMarginFactorNoFan static pressure design safety multiplier (>= 1.0).
wallAllowableOverpressureKpaNoBuilding wall/roof structural allowable transient overpressure in kPa.

Output Schema

NameRequiredDescriptionDefault
modeNoExecuted GIS / MV SF6 room air audit mode ("gis_mv_room_air_audit").
presetIdNoResolved GIS/MV room preset identifier, or null for custom dimensions.
metrologyNoFloor area, aisle clearances, and free net air volume breakdown.
legalNoticeNoInformational engineering compliance notice confirming SI physical scope and intellectual property rules.
overallStatusNoOverall switchgear room air safety compliance verdict.
complianceScoreNoComposite room air & arc-safety compliance score (0..100).
recommendationsNoPrioritized room ventilation, gas detection, and overpressure recommendations.
calculationTraceNoTransparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.
installationTypeNoEvaluated switchgear tier ("gis_hv" or "mv_sf6_switchgear").
internalArcAndFgasNoInternal-arc transient wall overpressure (kPa) and SF6 tCO2e greenhouse inventory.
sf6DispersionAndO2NoWorst-case homogeneous vs stratified z <= 1.0 m / trench SF6 ppm and residual O2 %.
ventilationAndPurgeNoNormal ACH, emergency low-point exhaust flow, and exponential t_95% purge duration.
smokeExtractionAndHvacNoSmoke extraction vent area, aerodynamic pressure drops, and cooling airflow balance.

Schema Changelog

Changes observed during successful MCP inspections.

  1. Changed137 schema fields changed
    • changedInput schema / properties / buildingClassification / description
      Previous value: -"Fire safety building occupancy regime (e.g. \"industrial_code_travail\")."New value: +"Fire safety building occupancy class (\"erp\" for public assembly or industrial default)."
    • changedInput schema / properties / deltaTMaxK / description
      Previous value: -"Maximum permissible room air temperature rise Delta-T in Kelvin."New value: +"Maximum permissible room air temperature rise Delta-T in Kelvin (K)."
    • addedInput schema / properties / deltaTMaxK / minimum
      Added value: +1
    • addedInput schema / properties / emergencyExhaustAch / minimum
      Added value: +0
    • addedInput schema / properties / equipmentFootprintM2 / minimum
      Added value: +0
    • changedInput schema / properties / equipmentVolumeM3 / description
      Previous value: -"Displaced solid enclosure equipment volume deducted from free air in m3."New value: +"Displaced solid switchgear enclosure volume deducted from free air in m3."
    • addedInput schema / properties / equipmentVolumeM3 / minimum
      Added value: +0
    • changedInput schema / properties / exhaustPressureDropPa / description
      Previous value: -"Exhaust duct and damper aerodynamic pressure loss in Pa."New value: +"Exhaust duct and damper aerodynamic pressure loss in pascals (Pa)."
    • addedInput schema / properties / exhaustPressureDropPa / minimum
      Added value: +0
    • changedInput schema / properties / fireDoorOrDamperRating / description
      Previous value: -"Compartment fire barrier rating (\"EI60\", \"EI120\", \"EI180\")."New value: +"Compartment fire barrier resistance rating (\"EI60\", \"EI120\", \"EI180\")."
    • changedInput schema / properties / frontAisleM / description
      Previous value: -"Clear front operator & breaker withdrawal aisle width in meters."New value: +"Clear front operator and circuit-breaker withdrawal aisle width in meters (m)."
    • addedInput schema / properties / frontAisleM / minimum
      Added value: +0
    • addedInput schema / properties / gisRoom / properties / emergencyExhaustAch / minimum
      Added value: +0
    • addedInput schema / properties / gisRoom / properties / equipmentFootprintM2 / minimum
      Added value: +0
    • changedInput schema / properties / gisRoom / properties / equipmentVolumeM3 / description
      Previous value: -"Displaced solid enclosure equipment volume deducted from free air in m3."New value: +"Displaced solid switchgear enclosure volume deducted from free air in m3."
    • addedInput schema / properties / gisRoom / properties / equipmentVolumeM3 / minimum
      Added value: +0
    • changedInput schema / properties / gisRoom / properties / frontAisleM / description
      Previous value: -"Clear front operator & breaker withdrawal aisle width in meters."New value: +"Clear front operator and circuit-breaker withdrawal aisle width in meters (m)."
    • addedInput schema / properties / gisRoom / properties / frontAisleM / minimum
      Added value: +0
    • changedInput schema / properties / gisRoom / properties / hasGasDuctOrAbsorber / description
      Previous value: -"True when internal arc relief vents through an external pressure duct or absorber."New value: +"True when internal arc relief vents via an external pressure duct or absorber."
    • changedInput schema / properties / gisRoom / properties / heightM / description
      Previous value: -"Enclosure interior ceiling clear height in meters."New value: +"Enclosure interior ceiling clear height in meters (m)."
    • addedInput schema / properties / gisRoom / properties / heightM / minimum
      Added value: +1
    • changedInput schema / properties / gisRoom / properties / internalArcDurationS / description
      Previous value: -"Internal arc fault clearing duration in seconds."New value: +"Internal arc fault clearing duration in seconds (s)."
    • addedInput schema / properties / gisRoom / properties / internalArcDurationS / minimum
      Added value: +0
    • addedInput schema / properties / gisRoom / properties / internalArcKa / minimum
      Added value: +0
    • changedInput schema / properties / gisRoom / properties / lengthM / description
      Previous value: -"Enclosure interior room length in meters."New value: +"Enclosure interior room clear length in meters (m)."
    • addedInput schema / properties / gisRoom / properties / lengthM / minimum
      Added value: +0.5
    • addedInput schema / properties / gisRoom / properties / maxCompartmentSf6Kg / minimum
      Added value: +0
    • addedInput schema / properties / gisRoom / properties / normalAch / minimum
      Added value: +0
    • changedInput schema / properties / gisRoom / properties / rearAisleM / description
      Previous value: -"Clear rear maintenance and gas-sampling aisle width in meters."New value: +"Clear rear maintenance and gas-sampling corridor width in meters (m)."
    • addedInput schema / properties / gisRoom / properties / rearAisleM / minimum
      Added value: +0
    • changedInput schema / properties / gisRoom / properties / sideAisleM / description
      Previous value: -"Clear lateral access corridor width in meters."New value: +"Clear lateral switchgear access corridor width in meters (m)."
    • addedInput schema / properties / gisRoom / properties / sideAisleM / minimum
      Added value: +0
    • addedInput schema / properties / gisRoom / properties / totalSf6Kg / minimum
      Added value: +0
    • changedInput schema / properties / gisRoom / properties / trenchVolumeM3 / description
      Previous value: -"Communicating below-floor cable trench air volume in m3 where dense gas pools."New value: +"Communicating below-floor cable trench air volume in m3 where heavy gas pools."
    • addedInput schema / properties / gisRoom / properties / trenchVolumeM3 / minimum
      Added value: +0
    • addedInput schema / properties / gisRoom / properties / wallAllowableOverpressureKpa / minimum
      Added value: +0.1
    • changedInput schema / properties / gisRoom / properties / widthM / description
      Previous value: -"Enclosure interior room width in meters."New value: +"Enclosure interior room clear width in meters (m)."
    • addedInput schema / properties / gisRoom / properties / widthM / minimum
      Added value: +0.5
    • changedInput schema / properties / hasGasDuctOrAbsorber / description
      Previous value: -"True when internal arc relief vents through an external pressure duct or absorber."New value: +"True when internal arc relief vents via an external pressure duct or absorber."
    • changedInput schema / properties / heightM / description
      Previous value: -"Enclosure interior ceiling clear height in meters."New value: +"Enclosure interior ceiling clear height in meters (m)."
    • addedInput schema / properties / heightM / minimum
      Added value: +1
    • addedInput schema / properties / installedExhaustM3H / minimum
      Added value: +0
    • addedInput schema / properties / installedSueM2 / minimum
      Added value: +0
    • changedInput schema / properties / intakePressureDropPa / description
      Previous value: -"Supply intake louver/filter aerodynamic pressure loss in Pa."New value: +"Supply intake louver and filter aerodynamic pressure loss in pascals (Pa)."
    • addedInput schema / properties / intakePressureDropPa / minimum
      Added value: +0
    • changedInput schema / properties / internalArcDurationS / description
      Previous value: -"Internal arc fault clearing duration in seconds."New value: +"Internal arc fault clearing duration in seconds (s)."
    • addedInput schema / properties / internalArcDurationS / minimum
      Added value: +0
    • addedInput schema / properties / internalArcKa / minimum
      Added value: +0
    • changedInput schema / properties / lengthM / description
      Previous value: -"Enclosure interior room length in meters."New value: +"Enclosure interior room clear length in meters (m)."
    • addedInput schema / properties / lengthM / minimum
      Added value: +0.5
    • addedInput schema / properties / maxCompartmentSf6Kg / minimum
      Added value: +0
    • changedInput schema / properties / nominalVoltageKv / description
      Previous value: -"Nominal switchgear operating voltage in kV."New value: +"Nominal switchgear operating phase-to-phase voltage in kV."
    • addedInput schema / properties / nominalVoltageKv / minimum
      Added value: +0.4
    • addedInput schema / properties / normalAch / minimum
      Added value: +0
    • addedInput schema / properties / pressureDropMarginFactor / minimum
      Added value: +1
    • changedInput schema / properties / rearAisleM / description
      Previous value: -"Clear rear maintenance and gas-sampling aisle width in meters."New value: +"Clear rear maintenance and gas-sampling corridor width in meters (m)."
    • addedInput schema / properties / rearAisleM / minimum
      Added value: +0
    • changedInput schema / properties / sideAisleM / description
      Previous value: -"Clear lateral access corridor width in meters."New value: +"Clear lateral switchgear access corridor width in meters (m)."
    • addedInput schema / properties / sideAisleM / minimum
      Added value: +0
    • changedInput schema / properties / smokeExtractionMode / description
      Previous value: -"Smoke extraction ventilation mechanism (\"natural\" vents or \"mechanical\" fans)."New value: +"Smoke extraction mechanism (\"natural\" vents or \"mechanical\" fans)."
    • changedInput schema / properties / smokeHvac / properties / buildingClassification / description
      Previous value: -"Fire safety building occupancy regime (e.g. \"industrial_code_travail\")."New value: +"Fire safety building occupancy class (\"erp\" for public assembly or industrial default)."
    • changedInput schema / properties / smokeHvac / properties / deltaTMaxK / description
      Previous value: -"Maximum permissible room air temperature rise Delta-T in Kelvin."New value: +"Maximum permissible room air temperature rise Delta-T in Kelvin (K)."
    • addedInput schema / properties / smokeHvac / properties / deltaTMaxK / minimum
      Added value: +1
    • changedInput schema / properties / smokeHvac / properties / exhaustPressureDropPa / description
      Previous value: -"Exhaust duct and damper aerodynamic pressure loss in Pa."New value: +"Exhaust duct and damper aerodynamic pressure loss in pascals (Pa)."
    • addedInput schema / properties / smokeHvac / properties / exhaustPressureDropPa / minimum
      Added value: +0
    • changedInput schema / properties / smokeHvac / properties / fireDoorOrDamperRating / description
      Previous value: -"Compartment fire barrier rating (\"EI60\", \"EI120\", \"EI180\")."New value: +"Compartment fire barrier resistance rating (\"EI60\", \"EI120\", \"EI180\")."
    • changedInput schema / properties / smokeHvac / properties / heightM / description
      Previous value: -"Enclosure interior ceiling clear height in meters."New value: +"Enclosure interior ceiling clear height in meters (m)."
    • addedInput schema / properties / smokeHvac / properties / heightM / minimum
      Added value: +1
    • addedInput schema / properties / smokeHvac / properties / installedExhaustM3H / minimum
      Added value: +0
    • addedInput schema / properties / smokeHvac / properties / installedSueM2 / minimum
      Added value: +0
    • changedInput schema / properties / smokeHvac / properties / intakePressureDropPa / description
      Previous value: -"Supply intake louver/filter aerodynamic pressure loss in Pa."New value: +"Supply intake louver and filter aerodynamic pressure loss in pascals (Pa)."
    • addedInput schema / properties / smokeHvac / properties / intakePressureDropPa / minimum
      Added value: +0
    • changedInput schema / properties / smokeHvac / properties / lengthM / description
      Previous value: -"Enclosure interior room length in meters."New value: +"Enclosure interior room clear length in meters (m)."
    • addedInput schema / properties / smokeHvac / properties / lengthM / minimum
      Added value: +0.5
    • addedInput schema / properties / smokeHvac / properties / normalAch / minimum
      Added value: +0
    • addedInput schema / properties / smokeHvac / properties / pressureDropMarginFactor / minimum
      Added value: +1
    • changedInput schema / properties / smokeHvac / properties / smokeExtractionMode / description
      Previous value: -"Smoke extraction ventilation mechanism (\"natural\" vents or \"mechanical\" fans)."New value: +"Smoke extraction mechanism (\"natural\" vents or \"mechanical\" fans)."
    • changedInput schema / properties / smokeHvac / properties / thermalLossesKw / description
      Previous value: -"Total continuous equipment heat rejection losses in kW."New value: +"Total continuous equipment heat rejection losses in kW (>= 0 kW)."
    • addedInput schema / properties / smokeHvac / properties / thermalLossesKw / minimum
      Added value: +0
    • changedInput schema / properties / smokeHvac / properties / widthM / description
      Previous value: -"Enclosure interior room width in meters."New value: +"Enclosure interior room clear width in meters (m)."
    • addedInput schema / properties / smokeHvac / properties / widthM / minimum
      Added value: +0.5
    • changedInput schema / properties / thermalLossesKw / description
      Previous value: -"Total continuous equipment heat rejection losses in kW."New value: +"Total continuous equipment heat rejection losses in kW (>= 0 kW)."
    • addedInput schema / properties / thermalLossesKw / minimum
      Added value: +0
    • addedInput schema / properties / totalSf6Kg / minimum
      Added value: +0
    • changedInput schema / properties / trenchVolumeM3 / description
      Previous value: -"Communicating below-floor cable trench air volume in m3 where dense gas pools."New value: +"Communicating below-floor cable trench air volume in m3 where heavy gas pools."
    • addedInput schema / properties / trenchVolumeM3 / minimum
      Added value: +0
    • addedInput schema / properties / wallAllowableOverpressureKpa / minimum
      Added value: +0.1
    • changedInput schema / properties / widthM / description
      Previous value: -"Enclosure interior room width in meters."New value: +"Enclosure interior room clear width in meters (m)."
    • addedInput schema / properties / widthM / minimum
      Added value: +0.5
    • changedOutput schema / properties / complianceScore / description
      Previous value: -"Room air & safety compliance score (0..100)."New value: +"Composite room air & arc-safety compliance score (0..100)."
    • addedOutput schema / properties / internalArcAndFgas / properties / estimatedArcEnergyMj
      Added value: +{
      +  "description": "Estimated internal arc thermal energy released in MJ.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / internalArcAndFgas / properties / estimatedRoomOverpressureKpa
      Added value: +{
      +  "description": "Net enclosure peak overpressure after duct/absorber relief in kPa.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / internalArcAndFgas / properties / exceeds500tCo2eThreshold
      Added value: +{
      +  "description": "True when inventory exceeds 500 tCO2e leak-check reporting threshold.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / internalArcAndFgas / properties / hasGasDuctOrAbsorber
      Added value: +{
      +  "description": "True when switchgear vents through an external pressure duct or absorber.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / internalArcAndFgas / properties / internalArcDurationS
      Added value: +{
      +  "description": "Evaluated internal arc fault clearing duration in seconds (s).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / internalArcAndFgas / properties / internalArcKa
      Added value: +{
      +  "description": "Evaluated internal arc fault current magnitude in kA.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / internalArcAndFgas / properties / overpressureCompliant
      Added value: +{
      +  "description": "True when room overpressure remains below structural wall capacity.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / internalArcAndFgas / properties / totalCo2EquivalentTonnes
      Added value: +{
      +  "description": "Total installed SF6 greenhouse inventory in tonnes CO2 equivalent (tCO2e).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / internalArcAndFgas / properties / wallAllowableOverpressureKpa
      Added value: +{
      +  "description": "Allowable building wall/roof transient pressure limit in kPa.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / metrology / properties / aisleClearancesM
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Switchgear operating aisle clearances and compliance verdict.",
      +  "properties": {
      +    "aislesCompliant": {
      +      "description": "True when all operator and maintenance aisle widths pass.",
      +      "type": "boolean"
      +    },
      +    "frontAisleM": {
      +      "description": "Installed front operating aisle width in meters (m).",
      +      "type": "number"
      +    },
      +    "rearAisleM": {
      +      "description": "Installed rear maintenance corridor width in meters (m).",
      +      "type": "number"
      +    },
      +    "sideAisleM": {
      +      "description": "Installed lateral access aisle width in meters (m).",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / metrology / properties / freeAirVolumeM3
      Added value: +{
      +  "description": "Net free mixing air volume in cubic meters (m3).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / metrology / properties / grossAreaM2
      Added value: +{
      +  "description": "Gross switchgear hall floor area in square meters (m2).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / metrology / properties / grossVolumeM3
      Added value: +{
      +  "description": "Gross switchgear hall enclosure volume in cubic meters (m3).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / metrology / properties / heightCompliant
      Added value: +{
      +  "description": "True when ceiling clear height meets minimum switchgear clearance.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / metrology / properties / installationType
      Added value: +{
      +  "description": "Evaluated switchgear tier (\"gis_hv\" or \"mv_sf6_switchgear\").",
      +  "type": "string"
      +}
    • addedOutput schema / properties / metrology / properties / netOperatingAreaM2
      Added value: +{
      +  "description": "Net free operator floor area around bays in m2.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / metrology / properties / trenchVolumeM3
      Added value: +{
      +  "description": "Communicating below-floor cable trench air volume in m3.",
      +  "type": "number"
      +}
    • changedOutput schema / properties / mode / description
      Previous value: -"Executed GIS / MV SF6 room air audit mode."New value: +"Executed GIS / MV SF6 room air audit mode (\"gis_mv_room_air_audit\")."
    • changedOutput schema / properties / overallStatus / description
      Previous value: -"Overall room safety compliance status."New value: +"Overall switchgear room air safety compliance verdict."
    • addedOutput schema / properties / presetId
      Added value: +{
      +  "description": "Resolved GIS/MV room preset identifier, or null for custom dimensions.",
      +  "oneOf": [
      +    {
      +      "description": "Resolved GIS/MV room preset identifier, or null for custom dimensions.",
      +      "type": "string"
      +    },
      +    {
      +      "description": "Null when no named reference preset identifier was supplied.",
      +      "type": "null"
      +    }
      +  ]
      +}
    • addedOutput schema / properties / recommendations
      Added value: +{
      +  "description": "Prioritized room ventilation, gas detection, and overpressure recommendations.",
      +  "items": {
      +    "additionalProperties": true,
      +    "description": "Prioritized fire, smoke, or switchgear room air safety recommendation.",
      +    "properties": {
      +      "code": {
      +        "description": "Machine-readable recommendation finding identifier code.",
      +        "type": "string"
      +      },
      +      "detailFr": {
      +        "description": "Detailed remediation measure and physical threshold text.",
      +        "type": "string"
      +      },
      +      "domain": {
      +        "description": "Engineering subsystem domain identifier slug.",
      +        "type": "string"
      +      },
      +      "priority": {
      +        "description": "Recommendation urgency tier (\"HIGH\", \"MEDIUM\", or \"INFO\").",
      +        "type": "string"
      +      },
      +      "titleFr": {
      +        "description": "Localized concise recommendation headline summary text.",
      +        "type": "string"
      +      }
      +    },
      +    "type": "object"
      +  },
      +  "type": "array"
      +}
    • addedOutput schema / properties / sf6DispersionAndO2 / properties / homogeneousSf6Ppmv
      Added value: +{
      +  "description": "Well-mixed room SF6 concentration in ppmv.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sf6DispersionAndO2 / properties / maxCompartmentSf6Kg
      Added value: +{
      +  "description": "Largest single pressurized gas compartment SF6 mass in kg.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sf6DispersionAndO2 / properties / minSafeRoomVolumeO2M3
      Added value: +{
      +  "description": "Minimum free room air volume keeping O2 >= 19.5% in m3.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sf6DispersionAndO2 / properties / releasedSf6M3
      Added value: +{
      +  "description": "Expanded SF6 gas release volume at atmospheric pressure in m3.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sf6DispersionAndO2 / properties / residualO2HomogeneousPct
      Added value: +{
      +  "description": "Well-mixed residual oxygen volume concentration in % O2.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sf6DispersionAndO2 / properties / residualO2LowLayerPct
      Added value: +{
      +  "description": "Stratified low-layer (z <= 1.0 m) residual O2 in % O2.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sf6DispersionAndO2 / properties / residualO2TrenchPct
      Added value: +{
      +  "description": "Cable-trench residual oxygen concentration in % O2.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sf6DispersionAndO2 / properties / rhoSf6KgM3
      Added value: +{
      +  "description": "SF6 heavy gas density at ambient conditions in kg/m3 (6.17 kg/m3).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / sf6DispersionAndO2 / properties / thresholdsPct
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Occupational oxygen depletion threshold percentages.",
      +  "properties": {
      +    "alarmN1": {
      +      "description": "First-level hypoxia alarm oxygen threshold in % (19.5%).",
      +      "type": "number"
      +    },
      +    "criticalN2": {
      +      "description": "Critical asphyxiation evacuation oxygen threshold in % (17.0%).",
      +      "type": "number"
      +    },
      +    "normal": {
      +      "description": "Normal ambient atmospheric oxygen percentage (20.9%).",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / sf6DispersionAndO2 / properties / totalSf6Kg
      Added value: +{
      +  "description": "Total installed SF6 inventory mass across all bays in kg.",
      +  "type": "number"
      +}
    • changedOutput schema / properties / smokeExtractionAndHvac / description
      Previous value: -"Smoke extraction vent area, pressure drops, and cooling airflow balance."New value: +"Smoke extraction vent area, aerodynamic pressure drops, and cooling airflow balance."
    • addedOutput schema / properties / smokeExtractionAndHvac / properties / detectionAndSsiInterlocks
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Air-dilution detector spacing, aspirating detection, and fire damper interlocks.",
      +  "properties": {
      +    "damperCompliant": {
      +      "description": "True when installed fire dampers meet compartmentation rating.",
      +      "type": "boolean"
      +    },
      +    "detectorCoverageM2": {
      +      "description": "Maximum point smoke detector coverage area in m2/detector.",
      +      "type": "number"
      +    },
      +    "effectiveAch": {
      +      "description": "Effective room air change rate in volumes/hour (vol/h).",
      +      "type": "number"
      +    },
      +    "fireDoorOrDamperRating": {
      +      "description": "Evaluated fire barrier / damper resistance rating.",
      +      "type": "string"
      +    },
      +    "minPointSmokeDetectors": {
      +      "description": "Minimum required point smoke detectors for ceiling area.",
      +      "type": "integer"
      +    },
      +    "vewfdAspirationMandatory": {
      +      "description": "True when high air-change rate mandates aspirating detection.",
      +      "type": "boolean"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / smokeExtractionAndHvac / properties / geometry
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Enclosure geometry and smoke-layer height outputs.",
      +  "properties": {
      +    "cantonCount": {
      +      "description": "Required smoke-reservoir canton partition count.",
      +      "type": "integer"
      +    },
      +    "grossAreaM2": {
      +      "description": "Gross enclosure floor area in square meters (m2).",
      +      "type": "number"
      +    },
      +    "minClearHeightBelowSmokeM": {
      +      "description": "Minimum smoke-free clear height above floor in meters (m).",
      +      "type": "number"
      +    },
      +    "roomType": {
      +      "description": "Evaluated enclosure room role identifier.",
      +      "type": "string"
      +    },
      +    "roomVolumeM3": {
      +      "description": "Gross enclosure air volume in cubic meters (m3).",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / smokeExtractionAndHvac / properties / hvacThermalAndPressureDrop
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Sensible-heat HVAC airflow, pressure loss (Pa), and fan power balance.",
      +  "properties": {
      +    "deltaTMaxK": {
      +      "description": "Maximum allowable room air temperature rise in Kelvin (K).",
      +      "type": "number"
      +    },
      +    "estimatedFanPowerKw": {
      +      "description": "Estimated absorbed aerodynamic fan shaft power in kW.",
      +      "type": "number"
      +    },
      +    "evaluatedExhaustM3h": {
      +      "description": "Evaluated fan exhaust volumetric flow rate in m3/h.",
      +      "type": "number"
      +    },
      +    "smokeExtractionMode": {
      +      "description": "Evaluated extraction mechanism (\"natural\" or \"mechanical\").",
      +      "type": "string"
      +    },
      +    "thermalFlowCompliant": {
      +      "description": "True when cooling airflow holds temperature rise within Delta-T.",
      +      "type": "boolean"
      +    },
      +    "thermalLossesKw": {
      +      "description": "Continuous equipment sensible heat dissipation in kW.",
      +      "type": "number"
      +    },
      +    "thermalVentFlowM3h": {
      +      "description": "Thermodynamic sensible cooling ventilation airflow in m3/h.",
      +      "type": "number"
      +    },
      +    "totalPressureDropPa": {
      +      "description": "Design total aerodynamic duct and louver pressure drop in Pa.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / smokeExtractionAndHvac / properties / mechanicalSmokeExtraction
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Mechanical smoke exhaust fan capacity and thermal rating outputs.",
      +  "properties": {
      +    "fanRating": {
      +      "description": "Required high-temperature smoke exhaust fan thermal rating.",
      +      "type": "string"
      +    },
      +    "installedExhaustM3H": {
      +      "description": "Installed mechanical exhaust flow in m3/h, or null when omitted.",
      +      "oneOf": [
      +        {
      +          "description": "Installed mechanical exhaust flow in m3/h, or null when omitted.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is omitted or inapplicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "mechFlowCompliant": {
      +      "description": "True when mechanical smoke exhaust meets volumetric targets.",
      +      "type": "boolean"
      +    },
      +    "recommendedMakeupAirM3h": {
      +      "description": "Recommended fresh makeup airflow rate in m3/h.",
      +      "type": "number"
      +    },
      +    "requiredMechExhaustM3h": {
      +      "description": "Minimum required mechanical smoke exhaust rate in m3/h.",
      +      "type": "number"
      +    },
      +    "requiredMechExhaustM3s": {
      +      "description": "Minimum required mechanical smoke exhaust rate in m3/s.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / smokeExtractionAndHvac / properties / naturalSmokeExtraction
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Natural buoyancy smoke extraction vent area requirements.",
      +  "properties": {
      +    "buildingClassification": {
      +      "description": "Applied occupancy fire-safety regime identifier.",
      +      "type": "string"
      +    },
      +    "exutorCount": {
      +      "description": "Recommended number of distributed natural smoke vents.",
      +      "type": "integer"
      +    },
      +    "installedSueM2": {
      +      "description": "Installed effective SUE vent area in m2, or null when omitted.",
      +      "oneOf": [
      +        {
      +          "description": "Installed effective SUE vent area in m2, or null when omitted.",
      +          "type": "number"
      +        },
      +        {
      +          "description": "Null when value is omitted or inapplicable in active mode.",
      +          "type": "null"
      +        }
      +      ]
      +    },
      +    "requiredGeometricAreaM2": {
      +      "description": "Minimum required geometric roof/facade vent area in m2.",
      +      "type": "number"
      +    },
      +    "requiredSueM2": {
      +      "description": "Minimum required aerodynamic smoke vent area SUE in m2.",
      +      "type": "number"
      +    },
      +    "sueCompliant": {
      +      "description": "True when installed natural smoke venting satisfies SUE rules.",
      +      "type": "boolean"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / ventilationAndPurge / properties / dualO2Sf6DetectionRequired
      Added value: +{
      +  "description": "True when combined O2 depletion and SF6 gas sensing is required.",
      +  "type": "boolean"
      +}
    • addedOutput schema / properties / ventilationAndPurge / properties / emergencyExhaustAch
      Added value: +{
      +  "description": "Emergency post-leak low-point purge rate in vol/h.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / ventilationAndPurge / properties / emergencyFlowM3h
      Added value: +{
      +  "description": "Emergency purge exhaust volumetric flow in m3/h.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / ventilationAndPurge / properties / exposureLimitsPpm
      Added value: +{
      +  "additionalProperties": true,
      +  "description": "Occupational gas and arc-decomposition byproduct limits in ppmv.",
      +  "properties": {
      +    "hfNewMax": {
      +      "description": "Arc-byproduct hydrogen fluoride HF ceiling in ppmv.",
      +      "type": "number"
      +    },
      +    "sf6Vme": {
      +      "description": "Occupational SF6 exposure limit in ppmv.",
      +      "type": "number"
      +    },
      +    "sof2Vme": {
      +      "description": "Arc-byproduct thionyl fluoride SOF2 limit in ppmv.",
      +      "type": "number"
      +    }
      +  },
      +  "type": "object"
      +}
    • addedOutput schema / properties / ventilationAndPurge / properties / lowPointExtractionMaxHeightM
      Added value: +{
      +  "description": "Maximum floor elevation of low-point SF6 exhaust pickup in m (0.30 m).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / ventilationAndPurge / properties / normalAch
      Added value: +{
      +  "description": "Continuous normal-operation room air change rate in vol/h.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / ventilationAndPurge / properties / normalFlowM3h
      Added value: +{
      +  "description": "Continuous normal fresh-air ventilation flow in m3/h.",
      +  "type": "number"
      +}
    • addedOutput schema / properties / ventilationAndPurge / properties / purgeTime95PctMin
      Added value: +{
      +  "description": "Exponential 95%-dilution purge time t_95% in minutes (min).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / ventilationAndPurge / properties / purgeTime95PctSec
      Added value: +{
      +  "description": "Exponential 95%-dilution purge time t_95% in seconds (s).",
      +  "type": "number"
      +}
    • addedOutput schema / properties / ventilationAndPurge / properties / zeroRecirculationRequired
      Added value: +{
      +  "description": "True when 100% outside-air once-through ventilation is mandatory.",
      +  "type": "boolean"
      +}
  2. Changed41 schema fields changed
    • addedInput schema / additionalProperties
      Added value: +true
    • addedInput schema / properties / buildingClassification / description
      Added value: +"Fire safety building occupancy regime (e.g. \"industrial_code_travail\")."
    • addedInput schema / properties / deltaTMaxK / description
      Added value: +"Maximum permissible room air temperature rise Delta-T in Kelvin."
    • addedInput schema / properties / emergencyExhaustAch / description
      Added value: +"Emergency post-leak mechanical purge extraction rate in vol/h."
    • addedInput schema / properties / equipmentFootprintM2 / description
      Added value: +"Total plan floor footprint occupied by switchgear bays in m2."
    • addedInput schema / properties / equipmentVolumeM3 / description
      Added value: +"Displaced solid enclosure equipment volume deducted from free air in m3."
    • addedInput schema / properties / exhaustPressureDropPa / description
      Added value: +"Exhaust duct and damper aerodynamic pressure loss in Pa."
    • addedInput schema / properties / fireDoorOrDamperRating / description
      Added value: +"Compartment fire barrier rating (\"EI60\", \"EI120\", \"EI180\")."
    • addedInput schema / properties / frontAisleM / description
      Added value: +"Clear front operator & breaker withdrawal aisle width in meters."
    • addedInput schema / properties / gisRoom / additionalProperties
      Added value: +true
    • addedInput schema / properties / gisRoom / description
      Added value: +"Structured GIS / MV SF6 switchgear room geometry and gas inventory overrides."
    • addedInput schema / properties / gisRoom / properties
      Added value: +{
      +  "emergencyExhaustAch": {
      +    "description": "Emergency post-leak mechanical purge extraction rate in vol/h.",
      +    "type": "number"
      +  },
      +  "equipmentFootprintM2": {
      +    "description": "Total plan floor footprint occupied by switchgear bays in m2.",
      +    "type": "number"
      +  },
      +  "equipmentVolumeM3": {
      +    "description": "Displaced solid enclosure equipment volume deducted from free air in m3.",
      +    "type": "number"
      +  },
      +  "frontAisleM": {
      +    "description": "Clear front operator & breaker withdrawal aisle width in meters.",
      +    "type": "number"
      +  },
      +  "hasGasDuctOrAbsorber": {
      +    "description": "True when internal arc relief vents through an external pressure duct or absorber.",
      +    "type": "boolean"
      +  },
      +  "heightM": {
      +    "description": "Enclosure interior ceiling clear height in meters.",
      +    "type": "number"
      +  },
      +  "installationType": {
      +    "description": "Gas-insulated switchgear tier (\"gis_hv\" or \"mv_sf6_switchgear\").",
      +    "enum": [
      +      "gis_hv",
      +      "mv_sf6_switchgear"
      +    ],
      +    "type": "string"
      +  },
      +  "internalArcDurationS": {
      +    "description": "Internal arc fault clearing duration in seconds.",
      +    "type": "number"
      +  },
      +  "internalArcKa": {
      +    "description": "Rated switchgear internal arc fault current magnitude in kA.",
      +    "type": "number"
      +  },
      +  "lengthM": {
      +    "description": "Enclosure interior room length in meters.",
      +    "type": "number"
      +  },
      +  "maxCompartmentSf6Kg": {
      +    "description": "Largest single pressurized gas compartment SF6 mass release in kg.",
      +    "type": "number"
      +  },
      +  "normalAch": {
      +    "description": "Continuous normal-operation air change rate in volumes/hour (vol/h).",
      +    "type": "number"
      +  },
      +  "rearAisleM": {
      +    "description": "Clear rear maintenance and gas-sampling aisle width in meters.",
      +    "type": "number"
      +  },
      +  "sideAisleM": {
      +    "description": "Clear lateral access corridor width in meters.",
      +    "type": "number"
      +  },
      +  "totalSf6Kg": {
      +    "description": "Total substation inventory mass of SF6 insulating gas in kg.",
      +    "type": "number"
      +  },
      +  "trenchVolumeM3": {
      +    "description": "Communicating below-floor cable trench air volume in m3 where dense gas pools.",
      +    "type": "number"
      +  },
      +  "wallAllowableOverpressureKpa": {
      +    "description": "Building wall/roof structural allowable transient overpressure in kPa.",
      +    "type": "number"
      +  },
      +  "widthM": {
      +    "description": "Enclosure interior room width in meters.",
      +    "type": "number"
      +  }
      +}
    • addedInput schema / properties / hasGasDuctOrAbsorber / description
      Added value: +"True when internal arc relief vents through an external pressure duct or absorber."
    • addedInput schema / properties / heightM / description
      Added value: +"Enclosure interior ceiling clear height in meters."
    • addedInput schema / properties / installationType / description
      Added value: +"Gas-insulated switchgear tier (\"gis_hv\" or \"mv_sf6_switchgear\")."
    • addedInput schema / properties / installedExhaustM3H / description
      Added value: +"Installed mechanical smoke/heat exhaust volumetric flow rate in m3/h."
    • addedInput schema / properties / installedSueM2 / description
      Added value: +"Installed effective natural geometric smoke vent free area SUE in m2."
    • addedInput schema / properties / intakePressureDropPa / description
      Added value: +"Supply intake louver/filter aerodynamic pressure loss in Pa."
    • addedInput schema / properties / internalArcDurationS / description
      Added value: +"Internal arc fault clearing duration in seconds."
    • addedInput schema / properties / internalArcKa / description
      Added value: +"Rated switchgear internal arc fault current magnitude in kA."
    • addedInput schema / properties / lang / default
      Added value: +"fr"
    • addedInput schema / properties / lang / description
      Added value: +"Response localization language code (\"fr\" for French or \"en\" for English, defaults to \"fr\")."
    • addedInput schema / properties / lengthM / description
      Added value: +"Enclosure interior room length in meters."
    • addedInput schema / properties / maxCompartmentSf6Kg / description
      Added value: +"Largest single pressurized gas compartment SF6 mass release in kg."
    • addedInput schema / properties / nominalVoltageKv / description
      Added value: +"Nominal switchgear operating voltage in kV."
    • addedInput schema / properties / normalAch / description
      Added value: +"Continuous normal-operation air change rate in volumes/hour (vol/h)."
    • addedInput schema / properties / presetId / description
      Added value: +"Reference GIS or MV switchgear room preset identifier (e.g. \"gis_225_20kv_reference_2x85mva\")."
    • addedInput schema / properties / pressureDropMarginFactor / description
      Added value: +"Fan static pressure design safety multiplier (>= 1.0)."
    • addedInput schema / properties / rearAisleM / description
      Added value: +"Clear rear maintenance and gas-sampling aisle width in meters."
    • addedInput schema / properties / roomType / description
      Added value: +"Enclosure room role (\"transformer_vault\", \"gis_hall\", \"mv_switchroom\", \"control_room\")."
    • addedInput schema / properties / sideAisleM / description
      Added value: +"Clear lateral access corridor width in meters."
    • addedInput schema / properties / smokeExtractionMode / description
      Added value: +"Smoke extraction ventilation mechanism (\"natural\" vents or \"mechanical\" fans)."
    • addedInput schema / properties / smokeHvac / additionalProperties
      Added value: +true
    • addedInput schema / properties / smokeHvac / description
      Added value: +"Structured room thermal HVAC and smoke extraction geometry overrides."
    • addedInput schema / properties / smokeHvac / properties
      Added value: +{
      +  "buildingClassification": {
      +    "description": "Fire safety building occupancy regime (e.g. \"industrial_code_travail\").",
      +    "type": "string"
      +  },
      +  "deltaTMaxK": {
      +    "description": "Maximum permissible room air temperature rise Delta-T in Kelvin.",
      +    "type": "number"
      +  },
      +  "exhaustPressureDropPa": {
      +    "description": "Exhaust duct and damper aerodynamic pressure loss in Pa.",
      +    "type": "number"
      +  },
      +  "fireDoorOrDamperRating": {
      +    "description": "Compartment fire barrier rating (\"EI60\", \"EI120\", \"EI180\").",
      +    "type": "string"
      +  },
      +  "heightM": {
      +    "description": "Enclosure interior ceiling clear height in meters.",
      +    "type": "number"
      +  },
      +  "installedExhaustM3H": {
      +    "description": "Installed mechanical smoke/heat exhaust volumetric flow rate in m3/h.",
      +    "type": "number"
      +  },
      +  "installedSueM2": {
      +    "description": "Installed effective natural geometric smoke vent free area SUE in m2.",
      +    "type": "number"
      +  },
      +  "intakePressureDropPa": {
      +    "description": "Supply intake louver/filter aerodynamic pressure loss in Pa.",
      +    "type": "number"
      +  },
      +  "lengthM": {
      +    "description": "Enclosure interior room length in meters.",
      +    "type": "number"
      +  },
      +  "normalAch": {
      +    "description": "Continuous normal-operation air change rate in volumes/hour (vol/h).",
      +    "type": "number"
      +  },
      +  "pressureDropMarginFactor": {
      +    "description": "Fan static pressure design safety multiplier (>= 1.0).",
      +    "type": "number"
      +  },
      +  "roomType": {
      +    "description": "Enclosure room role (\"transformer_vault\", \"gis_hall\", \"mv_switchroom\", \"control_room\").",
      +    "type": "string"
      +  },
      +  "smokeExtractionMode": {
      +    "description": "Smoke extraction ventilation mechanism (\"natural\" vents or \"mechanical\" fans).",
      +    "enum": [
      +      "natural",
      +      "mechanical"
      +    ],
      +    "type": "string"
      +  },
      +  "thermalLossesKw": {
      +    "description": "Total continuous equipment heat rejection losses in kW.",
      +    "type": "number"
      +  },
      +  "widthM": {
      +    "description": "Enclosure interior room width in meters.",
      +    "type": "number"
      +  }
      +}
    • addedInput schema / properties / thermalLossesKw / description
      Added value: +"Total continuous equipment heat rejection losses in kW."
    • addedInput schema / properties / totalSf6Kg / description
      Added value: +"Total substation inventory mass of SF6 insulating gas in kg."
    • addedInput schema / properties / trenchVolumeM3 / description
      Added value: +"Communicating below-floor cable trench air volume in m3 where dense gas pools."
    • addedInput schema / properties / wallAllowableOverpressureKpa / description
      Added value: +"Building wall/roof structural allowable transient overpressure in kPa."
    • addedInput schema / properties / widthM / description
      Added value: +"Enclosure interior room width in meters."
    • changedOutput schema / (root)
      Previous value: -nullNew value: +{
      +  "additionalProperties": true,
      +  "description": "GIS/MV SF6 switchgear room air safety audit with calculationTrace and legalNotice.",
      +  "properties": {
      +    "calculationTrace": {
      +      "additionalProperties": true,
      +      "description": "Transparent audit trail detailing inputs, injected defaults, formulas, constants, principles, and assumptions.",
      +      "properties": {
      +        "defaultsApplied": {
      +          "additionalProperties": true,
      +          "description": "Default physical or engineering assumptions injected when optional inputs were omitted.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "engineeringAssumptions": {
      +          "description": "Explicit boundary assumptions required to interpret the numerical output.",
      +          "items": {
      +            "description": "Boundary condition or validity assumption for the calculation.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "formulasAndConstants": {
      +          "additionalProperties": true,
      +          "description": "Mathematical formulas and SI physical constants bound to this calculation mode.",
      +          "properties": {
      +            "constants": {
      +              "additionalProperties": true,
      +              "description": "Map of physical constants, resistivities, and design coefficients in SI units.",
      +              "properties": {},
      +              "type": "object"
      +            },
      +            "formulas": {
      +              "description": "Ordered list of physical equations evaluated by the calculation engine.",
      +              "items": {
      +                "description": "Symbolic engineering formula string used during evaluation.",
      +                "type": "string"
      +              },
      +              "type": "array"
      +            }
      +          },
      +          "type": "object"
      +        },
      +        "inputsProvided": {
      +          "additionalProperties": true,
      +          "description": "Non-empty normalized input parameters explicitly supplied by the caller.",
      +          "properties": {},
      +          "type": "object"
      +        },
      +        "mode": {
      +          "description": "Normalized calculation mode executed for the current payload.",
      +          "type": "string"
      +        },
      +        "physicalPrinciples": {
      +          "description": "Key physical principles governing the computed result.",
      +          "items": {
      +            "description": "Concise statement of an underlying electrical or thermal principle.",
      +            "type": "string"
      +          },
      +          "type": "array"
      +        },
      +        "tool": {
      +          "description": "Resolved Brain tool identifier audited by the calculation tracer.",
      +          "type": "string"
      +        }
      +      },
      +      "type": "object"
      +    },
      +    "complianceScore": {
      +      "description": "Room air & safety compliance score (0..100).",
      +      "type": "number"
      +    },
      +    "installationType": {
      +      "description": "Evaluated switchgear tier (\"gis_hv\" or \"mv_sf6_switchgear\").",
      +      "type": "string"
      +    },
      +    "internalArcAndFgas": {
      +      "additionalProperties": true,
      +      "description": "Internal-arc transient wall overpressure (kPa) and SF6 tCO2e greenhouse inventory.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "legalNotice": {
      +      "description": "Informational engineering compliance notice confirming SI physical scope and intellectual property rules.",
      +      "type": "string"
      +    },
      +    "metrology": {
      +      "additionalProperties": true,
      +      "description": "Floor area, aisle clearances, and free net air volume breakdown.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "mode": {
      +      "description": "Executed GIS / MV SF6 room air audit mode.",
      +      "type": "string"
      +    },
      +    "overallStatus": {
      +      "description": "Overall room safety compliance status.",
      +      "type": "string"
      +    },
      +    "sf6DispersionAndO2": {
      +      "additionalProperties": true,
      +      "description": "Worst-case homogeneous vs stratified z <= 1.0 m / trench SF6 ppm and residual O2 %.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "smokeExtractionAndHvac": {
      +      "additionalProperties": true,
      +      "description": "Smoke extraction vent area, pressure drops, and cooling airflow balance.",
      +      "properties": {},
      +      "type": "object"
      +    },
      +    "ventilationAndPurge": {
      +      "additionalProperties": true,
      +      "description": "Normal ACH, emergency low-point exhaust flow, and exponential t_95% purge duration.",
      +      "properties": {},
      +      "type": "object"
      +    }
      +  },
      +  "type": "object"
      +}
  3. First observed

TDQS

A4.4/5.0
Behavior4/5

Does the description disclose side effects, auth requirements, rate limits, or destructive behavior?

Annotations already declare readOnlyHint/idempotentHint/destructiveHint=false and openWorldHint=false, so the 'stateless, read-only SI pass with zero mutations' sentence largely restates structured data. The description nonetheless adds real value beyond annotations: JSON-RPC -32602 on invalid argument types and the fact that omitted inputs fall back to reference GIS hall parameters with lang="fr". It stops short of covering computational assumptions or limits of validity for the physics.

Agents need to know what a tool does to the world before calling it. Descriptions should go beyond structured annotations to explain consequences.

Conciseness4/5

Is the description appropriately sized, front-loaded, and free of redundancy?

Front-loaded with the audit scope, then segmented by 'When to use', 'Do not use for', 'Behavior', and 'Returns' labels, which makes it skimmable despite the density. The 'Returns' enumeration is partly redundant against the existing output schema, and the long quantity list in the opening sentence could be trimmed.

Shorter descriptions cost fewer tokens and are easier for agents to parse. Every sentence should earn its place.

Completeness5/5

Given the tool's complexity, does the description cover enough for an agent to succeed on first attempt?

For a 34-parameter, zero-required tool with nested override objects and an output schema, the definition supplies the missing pieces an agent needs: domain exclusions, error contract, default behavior, and the unit system. The only residual gap, override precedence between flat and nested keys, is mitigated by 100% schema coverage and a live output schema.

Complex tools with many parameters or behaviors need more documentation. Simple tools need less. This dimension scales expectations accordingly.

Parameters3/5

Does the description clarify parameter syntax, constraints, interactions, or defaults beyond what the schema provides?

Schema description coverage is 100% across 34 parameters including nested objects, so the schema carries parameter meaning and baseline 3 applies. The description adds domain constants (6.17 kg/m3 SF6 density, 19.5%/17.0% O2 limits, 95% purge target, z <= 1.0 m low layer) that frame how inputs are evaluated, but it never explains the precedence between the duplicated top-level keys and their gisRoom/smokeHvac overrides.

Input schemas describe structure but not intent. Descriptions should explain non-obvious parameter relationships and valid value ranges.

Purpose5/5

Does the description clearly state what the tool does and how it differs from similar tools?

Names a specific verb (Audit) plus a precisely bounded resource (indoor GIS and MV SF6 switchgear halls) and enumerates the computed quantities: free air volume, SF6 stratification, residual O2 thresholds, purge time, smoke extraction, arc overpressure, tCO2e. The scope qualifier 'without transformers' and the SI-unit constraint separate it cleanly from the calc siblings.

Agents choose between tools based on descriptions. A clear purpose with a specific verb and resource helps agents select the right tool.

Usage Guidelines5/5

Does the description explain when to use this tool, when not to, or what alternatives exist?

Explicit 'When to use' and 'Do not use for' clauses name the excluded domains (transformer oil-fire separation, water deluge hydraulics, outdoor oil retention bunds) and route the agent to the concrete alternative, brain_calc_fm_global_fire_smoke_gis. Nothing about task selection is left to inference.

Agents often have multiple tools that could apply. Explicit usage guidance like "use X instead of Y when Z" prevents misuse.

Try in Browser

Glama MCP Gateway

Add one secure layer between your agents and this server.

Resources