changedInput schema / properties / buildingClassification / description
Previous value: -"Fire safety building occupancy regime (e.g. \"industrial_code_travail\")."New value: +"Fire safety building occupancy class (\"erp\" for public assembly or industrial default)."
changedInput schema / properties / deltaTMaxK / description
Previous value: -"Maximum permissible room air temperature rise Delta-T in Kelvin."New value: +"Maximum permissible room air temperature rise Delta-T in Kelvin (K)."
addedInput schema / properties / deltaTMaxK / minimum
Added value: +1
addedInput schema / properties / emergencyExhaustAch / minimum
Added value: +0
addedInput schema / properties / equipmentFootprintM2 / minimum
Added value: +0
changedInput schema / properties / equipmentVolumeM3 / description
Previous value: -"Displaced solid enclosure equipment volume deducted from free air in m3."New value: +"Displaced solid switchgear enclosure volume deducted from free air in m3."
addedInput schema / properties / equipmentVolumeM3 / minimum
Added value: +0
changedInput schema / properties / exhaustPressureDropPa / description
Previous value: -"Exhaust duct and damper aerodynamic pressure loss in Pa."New value: +"Exhaust duct and damper aerodynamic pressure loss in pascals (Pa)."
addedInput schema / properties / exhaustPressureDropPa / minimum
Added value: +0
changedInput schema / properties / fireDoorOrDamperRating / description
Previous value: -"Compartment fire barrier rating (\"EI60\", \"EI120\", \"EI180\")."New value: +"Compartment fire barrier resistance rating (\"EI60\", \"EI120\", \"EI180\")."
changedInput schema / properties / frontAisleM / description
Previous value: -"Clear front operator & breaker withdrawal aisle width in meters."New value: +"Clear front operator and circuit-breaker withdrawal aisle width in meters (m)."
addedInput schema / properties / frontAisleM / minimum
Added value: +0
addedInput schema / properties / gisRoom / properties / emergencyExhaustAch / minimum
Added value: +0
addedInput schema / properties / gisRoom / properties / equipmentFootprintM2 / minimum
Added value: +0
changedInput schema / properties / gisRoom / properties / equipmentVolumeM3 / description
Previous value: -"Displaced solid enclosure equipment volume deducted from free air in m3."New value: +"Displaced solid switchgear enclosure volume deducted from free air in m3."
addedInput schema / properties / gisRoom / properties / equipmentVolumeM3 / minimum
Added value: +0
changedInput schema / properties / gisRoom / properties / frontAisleM / description
Previous value: -"Clear front operator & breaker withdrawal aisle width in meters."New value: +"Clear front operator and circuit-breaker withdrawal aisle width in meters (m)."
addedInput schema / properties / gisRoom / properties / frontAisleM / minimum
Added value: +0
changedInput schema / properties / gisRoom / properties / hasGasDuctOrAbsorber / description
Previous value: -"True when internal arc relief vents through an external pressure duct or absorber."New value: +"True when internal arc relief vents via an external pressure duct or absorber."
changedInput schema / properties / gisRoom / properties / heightM / description
Previous value: -"Enclosure interior ceiling clear height in meters."New value: +"Enclosure interior ceiling clear height in meters (m)."
addedInput schema / properties / gisRoom / properties / heightM / minimum
Added value: +1
changedInput schema / properties / gisRoom / properties / internalArcDurationS / description
Previous value: -"Internal arc fault clearing duration in seconds."New value: +"Internal arc fault clearing duration in seconds (s)."
addedInput schema / properties / gisRoom / properties / internalArcDurationS / minimum
Added value: +0
addedInput schema / properties / gisRoom / properties / internalArcKa / minimum
Added value: +0
changedInput schema / properties / gisRoom / properties / lengthM / description
Previous value: -"Enclosure interior room length in meters."New value: +"Enclosure interior room clear length in meters (m)."
addedInput schema / properties / gisRoom / properties / lengthM / minimum
Added value: +0.5
addedInput schema / properties / gisRoom / properties / maxCompartmentSf6Kg / minimum
Added value: +0
addedInput schema / properties / gisRoom / properties / normalAch / minimum
Added value: +0
changedInput schema / properties / gisRoom / properties / rearAisleM / description
Previous value: -"Clear rear maintenance and gas-sampling aisle width in meters."New value: +"Clear rear maintenance and gas-sampling corridor width in meters (m)."
addedInput schema / properties / gisRoom / properties / rearAisleM / minimum
Added value: +0
changedInput schema / properties / gisRoom / properties / sideAisleM / description
Previous value: -"Clear lateral access corridor width in meters."New value: +"Clear lateral switchgear access corridor width in meters (m)."
addedInput schema / properties / gisRoom / properties / sideAisleM / minimum
Added value: +0
addedInput schema / properties / gisRoom / properties / totalSf6Kg / minimum
Added value: +0
changedInput schema / properties / gisRoom / properties / trenchVolumeM3 / description
Previous value: -"Communicating below-floor cable trench air volume in m3 where dense gas pools."New value: +"Communicating below-floor cable trench air volume in m3 where heavy gas pools."
addedInput schema / properties / gisRoom / properties / trenchVolumeM3 / minimum
Added value: +0
addedInput schema / properties / gisRoom / properties / wallAllowableOverpressureKpa / minimum
Added value: +0.1
changedInput schema / properties / gisRoom / properties / widthM / description
Previous value: -"Enclosure interior room width in meters."New value: +"Enclosure interior room clear width in meters (m)."
addedInput schema / properties / gisRoom / properties / widthM / minimum
Added value: +0.5
changedInput schema / properties / hasGasDuctOrAbsorber / description
Previous value: -"True when internal arc relief vents through an external pressure duct or absorber."New value: +"True when internal arc relief vents via an external pressure duct or absorber."
changedInput schema / properties / heightM / description
Previous value: -"Enclosure interior ceiling clear height in meters."New value: +"Enclosure interior ceiling clear height in meters (m)."
addedInput schema / properties / heightM / minimum
Added value: +1
addedInput schema / properties / installedExhaustM3H / minimum
Added value: +0
addedInput schema / properties / installedSueM2 / minimum
Added value: +0
changedInput schema / properties / intakePressureDropPa / description
Previous value: -"Supply intake louver/filter aerodynamic pressure loss in Pa."New value: +"Supply intake louver and filter aerodynamic pressure loss in pascals (Pa)."
addedInput schema / properties / intakePressureDropPa / minimum
Added value: +0
changedInput schema / properties / internalArcDurationS / description
Previous value: -"Internal arc fault clearing duration in seconds."New value: +"Internal arc fault clearing duration in seconds (s)."
addedInput schema / properties / internalArcDurationS / minimum
Added value: +0
addedInput schema / properties / internalArcKa / minimum
Added value: +0
changedInput schema / properties / lengthM / description
Previous value: -"Enclosure interior room length in meters."New value: +"Enclosure interior room clear length in meters (m)."
addedInput schema / properties / lengthM / minimum
Added value: +0.5
addedInput schema / properties / maxCompartmentSf6Kg / minimum
Added value: +0
changedInput schema / properties / nominalVoltageKv / description
Previous value: -"Nominal switchgear operating voltage in kV."New value: +"Nominal switchgear operating phase-to-phase voltage in kV."
addedInput schema / properties / nominalVoltageKv / minimum
Added value: +0.4
addedInput schema / properties / normalAch / minimum
Added value: +0
addedInput schema / properties / pressureDropMarginFactor / minimum
Added value: +1
changedInput schema / properties / rearAisleM / description
Previous value: -"Clear rear maintenance and gas-sampling aisle width in meters."New value: +"Clear rear maintenance and gas-sampling corridor width in meters (m)."
addedInput schema / properties / rearAisleM / minimum
Added value: +0
changedInput schema / properties / sideAisleM / description
Previous value: -"Clear lateral access corridor width in meters."New value: +"Clear lateral switchgear access corridor width in meters (m)."
addedInput schema / properties / sideAisleM / minimum
Added value: +0
changedInput schema / properties / smokeExtractionMode / description
Previous value: -"Smoke extraction ventilation mechanism (\"natural\" vents or \"mechanical\" fans)."New value: +"Smoke extraction mechanism (\"natural\" vents or \"mechanical\" fans)."
changedInput schema / properties / smokeHvac / properties / buildingClassification / description
Previous value: -"Fire safety building occupancy regime (e.g. \"industrial_code_travail\")."New value: +"Fire safety building occupancy class (\"erp\" for public assembly or industrial default)."
changedInput schema / properties / smokeHvac / properties / deltaTMaxK / description
Previous value: -"Maximum permissible room air temperature rise Delta-T in Kelvin."New value: +"Maximum permissible room air temperature rise Delta-T in Kelvin (K)."
addedInput schema / properties / smokeHvac / properties / deltaTMaxK / minimum
Added value: +1
changedInput schema / properties / smokeHvac / properties / exhaustPressureDropPa / description
Previous value: -"Exhaust duct and damper aerodynamic pressure loss in Pa."New value: +"Exhaust duct and damper aerodynamic pressure loss in pascals (Pa)."
addedInput schema / properties / smokeHvac / properties / exhaustPressureDropPa / minimum
Added value: +0
changedInput schema / properties / smokeHvac / properties / fireDoorOrDamperRating / description
Previous value: -"Compartment fire barrier rating (\"EI60\", \"EI120\", \"EI180\")."New value: +"Compartment fire barrier resistance rating (\"EI60\", \"EI120\", \"EI180\")."
changedInput schema / properties / smokeHvac / properties / heightM / description
Previous value: -"Enclosure interior ceiling clear height in meters."New value: +"Enclosure interior ceiling clear height in meters (m)."
addedInput schema / properties / smokeHvac / properties / heightM / minimum
Added value: +1
addedInput schema / properties / smokeHvac / properties / installedExhaustM3H / minimum
Added value: +0
addedInput schema / properties / smokeHvac / properties / installedSueM2 / minimum
Added value: +0
changedInput schema / properties / smokeHvac / properties / intakePressureDropPa / description
Previous value: -"Supply intake louver/filter aerodynamic pressure loss in Pa."New value: +"Supply intake louver and filter aerodynamic pressure loss in pascals (Pa)."
addedInput schema / properties / smokeHvac / properties / intakePressureDropPa / minimum
Added value: +0
changedInput schema / properties / smokeHvac / properties / lengthM / description
Previous value: -"Enclosure interior room length in meters."New value: +"Enclosure interior room clear length in meters (m)."
addedInput schema / properties / smokeHvac / properties / lengthM / minimum
Added value: +0.5
addedInput schema / properties / smokeHvac / properties / normalAch / minimum
Added value: +0
addedInput schema / properties / smokeHvac / properties / pressureDropMarginFactor / minimum
Added value: +1
changedInput schema / properties / smokeHvac / properties / smokeExtractionMode / description
Previous value: -"Smoke extraction ventilation mechanism (\"natural\" vents or \"mechanical\" fans)."New value: +"Smoke extraction mechanism (\"natural\" vents or \"mechanical\" fans)."
changedInput schema / properties / smokeHvac / properties / thermalLossesKw / description
Previous value: -"Total continuous equipment heat rejection losses in kW."New value: +"Total continuous equipment heat rejection losses in kW (>= 0 kW)."
addedInput schema / properties / smokeHvac / properties / thermalLossesKw / minimum
Added value: +0
changedInput schema / properties / smokeHvac / properties / widthM / description
Previous value: -"Enclosure interior room width in meters."New value: +"Enclosure interior room clear width in meters (m)."
addedInput schema / properties / smokeHvac / properties / widthM / minimum
Added value: +0.5
changedInput schema / properties / thermalLossesKw / description
Previous value: -"Total continuous equipment heat rejection losses in kW."New value: +"Total continuous equipment heat rejection losses in kW (>= 0 kW)."
addedInput schema / properties / thermalLossesKw / minimum
Added value: +0
addedInput schema / properties / totalSf6Kg / minimum
Added value: +0
changedInput schema / properties / trenchVolumeM3 / description
Previous value: -"Communicating below-floor cable trench air volume in m3 where dense gas pools."New value: +"Communicating below-floor cable trench air volume in m3 where heavy gas pools."
addedInput schema / properties / trenchVolumeM3 / minimum
Added value: +0
addedInput schema / properties / wallAllowableOverpressureKpa / minimum
Added value: +0.1
changedInput schema / properties / widthM / description
Previous value: -"Enclosure interior room width in meters."New value: +"Enclosure interior room clear width in meters (m)."
addedInput schema / properties / widthM / minimum
Added value: +0.5
changedOutput schema / properties / complianceScore / description
Previous value: -"Room air & safety compliance score (0..100)."New value: +"Composite room air & arc-safety compliance score (0..100)."
addedOutput schema / properties / internalArcAndFgas / properties / estimatedArcEnergyMj
Added value: +{
+ "description": "Estimated internal arc thermal energy released in MJ.",
+ "type": "number"
+}
addedOutput schema / properties / internalArcAndFgas / properties / estimatedRoomOverpressureKpa
Added value: +{
+ "description": "Net enclosure peak overpressure after duct/absorber relief in kPa.",
+ "type": "number"
+}
addedOutput schema / properties / internalArcAndFgas / properties / exceeds500tCo2eThreshold
Added value: +{
+ "description": "True when inventory exceeds 500 tCO2e leak-check reporting threshold.",
+ "type": "boolean"
+}
addedOutput schema / properties / internalArcAndFgas / properties / hasGasDuctOrAbsorber
Added value: +{
+ "description": "True when switchgear vents through an external pressure duct or absorber.",
+ "type": "boolean"
+}
addedOutput schema / properties / internalArcAndFgas / properties / internalArcDurationS
Added value: +{
+ "description": "Evaluated internal arc fault clearing duration in seconds (s).",
+ "type": "number"
+}
addedOutput schema / properties / internalArcAndFgas / properties / internalArcKa
Added value: +{
+ "description": "Evaluated internal arc fault current magnitude in kA.",
+ "type": "number"
+}
addedOutput schema / properties / internalArcAndFgas / properties / overpressureCompliant
Added value: +{
+ "description": "True when room overpressure remains below structural wall capacity.",
+ "type": "boolean"
+}
addedOutput schema / properties / internalArcAndFgas / properties / totalCo2EquivalentTonnes
Added value: +{
+ "description": "Total installed SF6 greenhouse inventory in tonnes CO2 equivalent (tCO2e).",
+ "type": "number"
+}
addedOutput schema / properties / internalArcAndFgas / properties / wallAllowableOverpressureKpa
Added value: +{
+ "description": "Allowable building wall/roof transient pressure limit in kPa.",
+ "type": "number"
+}
addedOutput schema / properties / metrology / properties / aisleClearancesM
Added value: +{
+ "additionalProperties": true,
+ "description": "Switchgear operating aisle clearances and compliance verdict.",
+ "properties": {
+ "aislesCompliant": {
+ "description": "True when all operator and maintenance aisle widths pass.",
+ "type": "boolean"
+ },
+ "frontAisleM": {
+ "description": "Installed front operating aisle width in meters (m).",
+ "type": "number"
+ },
+ "rearAisleM": {
+ "description": "Installed rear maintenance corridor width in meters (m).",
+ "type": "number"
+ },
+ "sideAisleM": {
+ "description": "Installed lateral access aisle width in meters (m).",
+ "type": "number"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / metrology / properties / freeAirVolumeM3
Added value: +{
+ "description": "Net free mixing air volume in cubic meters (m3).",
+ "type": "number"
+}
addedOutput schema / properties / metrology / properties / grossAreaM2
Added value: +{
+ "description": "Gross switchgear hall floor area in square meters (m2).",
+ "type": "number"
+}
addedOutput schema / properties / metrology / properties / grossVolumeM3
Added value: +{
+ "description": "Gross switchgear hall enclosure volume in cubic meters (m3).",
+ "type": "number"
+}
addedOutput schema / properties / metrology / properties / heightCompliant
Added value: +{
+ "description": "True when ceiling clear height meets minimum switchgear clearance.",
+ "type": "boolean"
+}
addedOutput schema / properties / metrology / properties / installationType
Added value: +{
+ "description": "Evaluated switchgear tier (\"gis_hv\" or \"mv_sf6_switchgear\").",
+ "type": "string"
+}
addedOutput schema / properties / metrology / properties / netOperatingAreaM2
Added value: +{
+ "description": "Net free operator floor area around bays in m2.",
+ "type": "number"
+}
addedOutput schema / properties / metrology / properties / trenchVolumeM3
Added value: +{
+ "description": "Communicating below-floor cable trench air volume in m3.",
+ "type": "number"
+}
changedOutput schema / properties / mode / description
Previous value: -"Executed GIS / MV SF6 room air audit mode."New value: +"Executed GIS / MV SF6 room air audit mode (\"gis_mv_room_air_audit\")."
changedOutput schema / properties / overallStatus / description
Previous value: -"Overall room safety compliance status."New value: +"Overall switchgear room air safety compliance verdict."
addedOutput schema / properties / presetId
Added value: +{
+ "description": "Resolved GIS/MV room preset identifier, or null for custom dimensions.",
+ "oneOf": [
+ {
+ "description": "Resolved GIS/MV room preset identifier, or null for custom dimensions.",
+ "type": "string"
+ },
+ {
+ "description": "Null when no named reference preset identifier was supplied.",
+ "type": "null"
+ }
+ ]
+}
addedOutput schema / properties / recommendations
Added value: +{
+ "description": "Prioritized room ventilation, gas detection, and overpressure recommendations.",
+ "items": {
+ "additionalProperties": true,
+ "description": "Prioritized fire, smoke, or switchgear room air safety recommendation.",
+ "properties": {
+ "code": {
+ "description": "Machine-readable recommendation finding identifier code.",
+ "type": "string"
+ },
+ "detailFr": {
+ "description": "Detailed remediation measure and physical threshold text.",
+ "type": "string"
+ },
+ "domain": {
+ "description": "Engineering subsystem domain identifier slug.",
+ "type": "string"
+ },
+ "priority": {
+ "description": "Recommendation urgency tier (\"HIGH\", \"MEDIUM\", or \"INFO\").",
+ "type": "string"
+ },
+ "titleFr": {
+ "description": "Localized concise recommendation headline summary text.",
+ "type": "string"
+ }
+ },
+ "type": "object"
+ },
+ "type": "array"
+}
addedOutput schema / properties / sf6DispersionAndO2 / properties / homogeneousSf6Ppmv
Added value: +{
+ "description": "Well-mixed room SF6 concentration in ppmv.",
+ "type": "number"
+}
addedOutput schema / properties / sf6DispersionAndO2 / properties / maxCompartmentSf6Kg
Added value: +{
+ "description": "Largest single pressurized gas compartment SF6 mass in kg.",
+ "type": "number"
+}
addedOutput schema / properties / sf6DispersionAndO2 / properties / minSafeRoomVolumeO2M3
Added value: +{
+ "description": "Minimum free room air volume keeping O2 >= 19.5% in m3.",
+ "type": "number"
+}
addedOutput schema / properties / sf6DispersionAndO2 / properties / releasedSf6M3
Added value: +{
+ "description": "Expanded SF6 gas release volume at atmospheric pressure in m3.",
+ "type": "number"
+}
addedOutput schema / properties / sf6DispersionAndO2 / properties / residualO2HomogeneousPct
Added value: +{
+ "description": "Well-mixed residual oxygen volume concentration in % O2.",
+ "type": "number"
+}
addedOutput schema / properties / sf6DispersionAndO2 / properties / residualO2LowLayerPct
Added value: +{
+ "description": "Stratified low-layer (z <= 1.0 m) residual O2 in % O2.",
+ "type": "number"
+}
addedOutput schema / properties / sf6DispersionAndO2 / properties / residualO2TrenchPct
Added value: +{
+ "description": "Cable-trench residual oxygen concentration in % O2.",
+ "type": "number"
+}
addedOutput schema / properties / sf6DispersionAndO2 / properties / rhoSf6KgM3
Added value: +{
+ "description": "SF6 heavy gas density at ambient conditions in kg/m3 (6.17 kg/m3).",
+ "type": "number"
+}
addedOutput schema / properties / sf6DispersionAndO2 / properties / thresholdsPct
Added value: +{
+ "additionalProperties": true,
+ "description": "Occupational oxygen depletion threshold percentages.",
+ "properties": {
+ "alarmN1": {
+ "description": "First-level hypoxia alarm oxygen threshold in % (19.5%).",
+ "type": "number"
+ },
+ "criticalN2": {
+ "description": "Critical asphyxiation evacuation oxygen threshold in % (17.0%).",
+ "type": "number"
+ },
+ "normal": {
+ "description": "Normal ambient atmospheric oxygen percentage (20.9%).",
+ "type": "number"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / sf6DispersionAndO2 / properties / totalSf6Kg
Added value: +{
+ "description": "Total installed SF6 inventory mass across all bays in kg.",
+ "type": "number"
+}
changedOutput schema / properties / smokeExtractionAndHvac / description
Previous value: -"Smoke extraction vent area, pressure drops, and cooling airflow balance."New value: +"Smoke extraction vent area, aerodynamic pressure drops, and cooling airflow balance."
addedOutput schema / properties / smokeExtractionAndHvac / properties / detectionAndSsiInterlocks
Added value: +{
+ "additionalProperties": true,
+ "description": "Air-dilution detector spacing, aspirating detection, and fire damper interlocks.",
+ "properties": {
+ "damperCompliant": {
+ "description": "True when installed fire dampers meet compartmentation rating.",
+ "type": "boolean"
+ },
+ "detectorCoverageM2": {
+ "description": "Maximum point smoke detector coverage area in m2/detector.",
+ "type": "number"
+ },
+ "effectiveAch": {
+ "description": "Effective room air change rate in volumes/hour (vol/h).",
+ "type": "number"
+ },
+ "fireDoorOrDamperRating": {
+ "description": "Evaluated fire barrier / damper resistance rating.",
+ "type": "string"
+ },
+ "minPointSmokeDetectors": {
+ "description": "Minimum required point smoke detectors for ceiling area.",
+ "type": "integer"
+ },
+ "vewfdAspirationMandatory": {
+ "description": "True when high air-change rate mandates aspirating detection.",
+ "type": "boolean"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / smokeExtractionAndHvac / properties / geometry
Added value: +{
+ "additionalProperties": true,
+ "description": "Enclosure geometry and smoke-layer height outputs.",
+ "properties": {
+ "cantonCount": {
+ "description": "Required smoke-reservoir canton partition count.",
+ "type": "integer"
+ },
+ "grossAreaM2": {
+ "description": "Gross enclosure floor area in square meters (m2).",
+ "type": "number"
+ },
+ "minClearHeightBelowSmokeM": {
+ "description": "Minimum smoke-free clear height above floor in meters (m).",
+ "type": "number"
+ },
+ "roomType": {
+ "description": "Evaluated enclosure room role identifier.",
+ "type": "string"
+ },
+ "roomVolumeM3": {
+ "description": "Gross enclosure air volume in cubic meters (m3).",
+ "type": "number"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / smokeExtractionAndHvac / properties / hvacThermalAndPressureDrop
Added value: +{
+ "additionalProperties": true,
+ "description": "Sensible-heat HVAC airflow, pressure loss (Pa), and fan power balance.",
+ "properties": {
+ "deltaTMaxK": {
+ "description": "Maximum allowable room air temperature rise in Kelvin (K).",
+ "type": "number"
+ },
+ "estimatedFanPowerKw": {
+ "description": "Estimated absorbed aerodynamic fan shaft power in kW.",
+ "type": "number"
+ },
+ "evaluatedExhaustM3h": {
+ "description": "Evaluated fan exhaust volumetric flow rate in m3/h.",
+ "type": "number"
+ },
+ "smokeExtractionMode": {
+ "description": "Evaluated extraction mechanism (\"natural\" or \"mechanical\").",
+ "type": "string"
+ },
+ "thermalFlowCompliant": {
+ "description": "True when cooling airflow holds temperature rise within Delta-T.",
+ "type": "boolean"
+ },
+ "thermalLossesKw": {
+ "description": "Continuous equipment sensible heat dissipation in kW.",
+ "type": "number"
+ },
+ "thermalVentFlowM3h": {
+ "description": "Thermodynamic sensible cooling ventilation airflow in m3/h.",
+ "type": "number"
+ },
+ "totalPressureDropPa": {
+ "description": "Design total aerodynamic duct and louver pressure drop in Pa.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / smokeExtractionAndHvac / properties / mechanicalSmokeExtraction
Added value: +{
+ "additionalProperties": true,
+ "description": "Mechanical smoke exhaust fan capacity and thermal rating outputs.",
+ "properties": {
+ "fanRating": {
+ "description": "Required high-temperature smoke exhaust fan thermal rating.",
+ "type": "string"
+ },
+ "installedExhaustM3H": {
+ "description": "Installed mechanical exhaust flow in m3/h, or null when omitted.",
+ "oneOf": [
+ {
+ "description": "Installed mechanical exhaust flow in m3/h, or null when omitted.",
+ "type": "number"
+ },
+ {
+ "description": "Null when value is omitted or inapplicable in active mode.",
+ "type": "null"
+ }
+ ]
+ },
+ "mechFlowCompliant": {
+ "description": "True when mechanical smoke exhaust meets volumetric targets.",
+ "type": "boolean"
+ },
+ "recommendedMakeupAirM3h": {
+ "description": "Recommended fresh makeup airflow rate in m3/h.",
+ "type": "number"
+ },
+ "requiredMechExhaustM3h": {
+ "description": "Minimum required mechanical smoke exhaust rate in m3/h.",
+ "type": "number"
+ },
+ "requiredMechExhaustM3s": {
+ "description": "Minimum required mechanical smoke exhaust rate in m3/s.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / smokeExtractionAndHvac / properties / naturalSmokeExtraction
Added value: +{
+ "additionalProperties": true,
+ "description": "Natural buoyancy smoke extraction vent area requirements.",
+ "properties": {
+ "buildingClassification": {
+ "description": "Applied occupancy fire-safety regime identifier.",
+ "type": "string"
+ },
+ "exutorCount": {
+ "description": "Recommended number of distributed natural smoke vents.",
+ "type": "integer"
+ },
+ "installedSueM2": {
+ "description": "Installed effective SUE vent area in m2, or null when omitted.",
+ "oneOf": [
+ {
+ "description": "Installed effective SUE vent area in m2, or null when omitted.",
+ "type": "number"
+ },
+ {
+ "description": "Null when value is omitted or inapplicable in active mode.",
+ "type": "null"
+ }
+ ]
+ },
+ "requiredGeometricAreaM2": {
+ "description": "Minimum required geometric roof/facade vent area in m2.",
+ "type": "number"
+ },
+ "requiredSueM2": {
+ "description": "Minimum required aerodynamic smoke vent area SUE in m2.",
+ "type": "number"
+ },
+ "sueCompliant": {
+ "description": "True when installed natural smoke venting satisfies SUE rules.",
+ "type": "boolean"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / ventilationAndPurge / properties / dualO2Sf6DetectionRequired
Added value: +{
+ "description": "True when combined O2 depletion and SF6 gas sensing is required.",
+ "type": "boolean"
+}
addedOutput schema / properties / ventilationAndPurge / properties / emergencyExhaustAch
Added value: +{
+ "description": "Emergency post-leak low-point purge rate in vol/h.",
+ "type": "number"
+}
addedOutput schema / properties / ventilationAndPurge / properties / emergencyFlowM3h
Added value: +{
+ "description": "Emergency purge exhaust volumetric flow in m3/h.",
+ "type": "number"
+}
addedOutput schema / properties / ventilationAndPurge / properties / exposureLimitsPpm
Added value: +{
+ "additionalProperties": true,
+ "description": "Occupational gas and arc-decomposition byproduct limits in ppmv.",
+ "properties": {
+ "hfNewMax": {
+ "description": "Arc-byproduct hydrogen fluoride HF ceiling in ppmv.",
+ "type": "number"
+ },
+ "sf6Vme": {
+ "description": "Occupational SF6 exposure limit in ppmv.",
+ "type": "number"
+ },
+ "sof2Vme": {
+ "description": "Arc-byproduct thionyl fluoride SOF2 limit in ppmv.",
+ "type": "number"
+ }
+ },
+ "type": "object"
+}
addedOutput schema / properties / ventilationAndPurge / properties / lowPointExtractionMaxHeightM
Added value: +{
+ "description": "Maximum floor elevation of low-point SF6 exhaust pickup in m (0.30 m).",
+ "type": "number"
+}
addedOutput schema / properties / ventilationAndPurge / properties / normalAch
Added value: +{
+ "description": "Continuous normal-operation room air change rate in vol/h.",
+ "type": "number"
+}
addedOutput schema / properties / ventilationAndPurge / properties / normalFlowM3h
Added value: +{
+ "description": "Continuous normal fresh-air ventilation flow in m3/h.",
+ "type": "number"
+}
addedOutput schema / properties / ventilationAndPurge / properties / purgeTime95PctMin
Added value: +{
+ "description": "Exponential 95%-dilution purge time t_95% in minutes (min).",
+ "type": "number"
+}
addedOutput schema / properties / ventilationAndPurge / properties / purgeTime95PctSec
Added value: +{
+ "description": "Exponential 95%-dilution purge time t_95% in seconds (s).",
+ "type": "number"
+}
addedOutput schema / properties / ventilationAndPurge / properties / zeroRecirculationRequired
Added value: +{
+ "description": "True when 100% outside-air once-through ventilation is mandatory.",
+ "type": "boolean"
+}