Radiator flow temperature
radiator_flow_temperatureWork out the flow temperature a heat pump must produce to heat a room through a given radiator, and the resulting MCS Heat Emitter Guide star rating, following section 4 of MGD 007.
This is the calculation that decides whether a heat pump will be cheap or expensive to run. A heat pump's efficiency falls as the water temperature rises, by roughly two to three per cent per degree, and the temperature it must produce is set by the radiators, not by the machine.
Supply the room's design heat loss in watts, from a room-by-room calculation, and the rated output of the radiator in that room. British catalogues normally quote at a mean-water-to-air difference of 50 K; if yours quotes 60, say so and the figure is restated.
The result gives the oversize factor, which is the radiator's output at 50 K divided by the room's heat loss, and converts it to a required flow temperature through the BS EN 442 output law. Star ratings run from 0 to 6, one star per five degrees of flow temperature, with six stars at 35 degrees.
Run this for every room. A house runs at the flow temperature its worst room demands, so one undersized radiator sets the running cost for the whole house.
Method from MGD 007. These calculators follow the published MCS methods, for understanding a system and checking a quotation. Anything that gets installed still needs a design and a site survey from a certified installer.
Input Schema
| Name | Required | Description | Default |
|---|---|---|---|
| roomTemp | No | Internal design temperature of the room in Celsius. Defaults to 21. | |
| systemDeltaT | No | Designed drop in water temperature between flow and return, in kelvin. Heat pump systems commonly use 5; boiler systems used 10 or 20. Defaults to 5. | |
| ratedAtDeltaT | No | The mean-water-to-air temperature difference the rated output was quoted at. British catalogues normally quote 50; some older ones quote 60. Defaults to 50. | |
| roomHeatLossW | Yes | The room's design heat loss in watts, from a room-by-room heat loss calculation. Required. | |
| radiatorOutputW | Yes | Rated output of the radiator or radiators in that room, in watts, at the catalogue temperature. Required. |
Output Schema
| Name | Required | Description | Default |
|---|---|---|---|
| notes | Yes | ||
| method | Yes | ||
| verdict | Yes | ||
| references | Yes | ||
| starRating | Yes | Temperature star rating from the MCS Heat Emitter Guide, 0 to 6. More stars mean a lower flow temperature and a more efficient system. | |
| meanWaterTemp | Yes | Average of flow and return temperature needed to deliver the room's heat loss through this radiator. | |
| ratedAtDeltaT | Yes | ||
| roomHeatLossW | Yes | ||
| oversizeFactor | Yes | Radiator output at 50 K divided by the room's heat loss. The single number the Heat Emitter Guide turns into a star rating. | |
| flowTemperature | Yes | The flow temperature the heat pump must produce, in Celsius. | |
| radiatorOutputW | Yes | ||
| starRatingLabel | Yes | ||
| outputAtDeltaT50 | Yes | The radiator's output restated at a mean-water-to-air difference of 50 K, so oversize factors are comparable between catalogues. | |
| returnTemperature | Yes | ||
| outputAtDesignFlowW | Yes | What this radiator actually gives at the flow temperature worked out here. | |
| radiatorOutputForFiveStarsW | Yes | The radiator output at 50 K that would reach a five star rating, meaning a 40 degree flow temperature. |